| 2001-05-01 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | ADDITIONAL INFORMATION REQUIRED PER |
| | 104.2.1 OF THE CITY OF W.P.B. AMENDMENTS |
| | TO THE 97 STANDARD BUILDING CODE. |
| | |
| | 1) INDICATED TYPE OF ROOF CONSTRUCTION |
| | ( TRUSSES OR RAFTERS ). INDICATE SPACING |
| | OF TRUSSES OR SIZE AND SPACING OF |
| | RAFTERS AND CEILING JOISTS. |
| | |
| | 2) INDICATE TYPE OF ROOF SHEATHING |
| | (5/8" PLYWOOD, ETC.) AND SPECIAL NAILING |
| | REQUIREMENTS(2306 CITY AMENDMENTS). |
| | |
| | 3) INDICATE SPACING OF 2X4 STUDS IN |
| | EXTERIOR WALLS. ( 16"ON CENTER,ETC.) |
| | |
| | 4) INDICATE ROOF OVERHANG,IF ANY. |
| | |
| | 5) INDICATE DIMENSIONS OF THE BUILDING. |
| | |
| | 6) INDICATE ROOF BRACING AND TYPE OF |
| | CEILING MATERIAL (IF ANY). |
| | |
| | 7) SHOW NUMBER AND SIZE OF ATTIC VENTS. |
| | |
| | 8) INDICATE FOOTING SIZE AND TYPE OF |
| | REINFORCEMENT. ( MINIMUM OF 16"H X 12"W |
| | WITH 2- 5/8" REBARS FOR THICKENED EDGE |
| | OF MONOLITHIC SLAB) |
| | |
| | 9) INDICATE CONNECTOR TYPES THAT WILL BE |
| | USED TO ANCHOR BOTTOM PLATE TO SLAB, |
| | STUDS TO TOP AND BOTTOM PLATES, RAFTERS/ |
| | TRUSSES TO TOP PLATES, AND RAFTERS TO |
| | RIDGE BOARD. |
| | |
| | 10) INDICATE PITCH OF ROOF ON PLANS. |
| | |
| | 11)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - EXTERIOR WINDOWS |
| | - EXTERIOR DOORS |
| | - ROOF COVERING (SINGLES,ETC.) |
| | - CEMENT SIDING |
| | |
| | 12) PROVIDE MANUFACTURERS SPECIFICATIONS |
| | FOR CEMENT SIDING. |
| | |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |