|
 |
 |
 |
 |
 |
Plan Review Details - Permit 01040717
| Plan Review Stops For Permit 01040717 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-04-25 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-04-25 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-25 00:00:00 | TEST AND OR PRODUCT ACCEPTANCE REPORTS | | | FOR THE DOORS WINDOWS AND ROOF COVERING | | | WILL BE REQUIRED WITH THE PERMIT. | | | | | | IF FIRE RATED PARTITIONS ARE INSTALLED A | | | FIRE DESIGN NUMBER WILL BE NECESARY. | | | SEE SBC 701.5 | | | | | | SECTION 6 A/5.0 TERMS SUCH AS "ANCHORED | | | WITH APPROVED FASTENERS" ARE NOT AN | | | ACCEPTABLE SUBSTITUTE FOR SPECIFIC | | | DESIGN INFORMATION.SEE SBC 104.2. | | | | | | SECTION 1/S1SPECIFY ANCHOR BOLT LENGTH | | | AND WELD SIZE. | | | | | | SHEET S 2.0SBC 1997 INVOKES ASCE 7-95 | | | NOT 7-93. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-04-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-26 |
Time |
21:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-26 |
Time |
21:27 |
Sent To |
|
|
| Notes |
| 2001-04-26 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED TO | | | BE SIGNED AND SEALED BY THE | | | ARCHS/ENGINEER OF RECORD PER 417.025 | | | AND 481.221 | | | F.A.C. | | | | | | 2)NOTE: PLEASE NOTE THAT COLD WATER | | | PIPE ISMISSING FROM GROUNDING | | | ELECTRODE SYSTEM PER 250-50. | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | AIC RATING IS GIVEN FOR PANEL BUT NOT | | | FOR MAIN. IS MAIN FUSED OR BRKR? | | | | | | 4)NOTE: PLEASE SEE ELECTRICAL PLAN | | | SUBMITTED FOR SITE LIGHTING.E-5 | | | PLANS SHOW ALL OUTSIDE EQUIPMENT AS | | | NEMA-1(INDOOR). ALL EQUIPMENT NEEDS TO | | | BE RATED FOR LOCATION OF ENVIROMENT. | | | TYPE-O? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-04-27 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-04-27 |
Time |
14:00 |
Rev Time |
4.00 |
| Received By |
mamini |
Date |
2001-04-27 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2001-04-27 00:00:00 | FAILED: | | | 1. PLEASE PROVIDE STORM WATER | | | CALCULATION FOR OUR REVIEW IF YOU HAVE | | | NOT SUBMITTED TO JOSE DEL RIO, STORM | | | WATER ENGINEER AT 1000 45TH STREET WEST | | | PALM BEACH,FL 33407. | | | 2. PERVIOUS & IMPERVIOUS CALCULATION | | | MUST BE SHOWN ON CIVIL PLAN, PLEASE | | | STATE EITHER ADDRESS OR PROPERTY CONTROL | | | NUMBER. | | | 3. PLEASE PROVIDE POLLUTION PREVENTION | | | PLAN.THE POLLUTION PREVENTION PLAN | | | MUST BE INSTALLED IN THE FIELD PRIOR TO | | | ANY EARTHWORK. | | | 4. AN APPROVED BACKFLOW PREVENTER | | | ASSEMBLY WILL NEED TO BE INSTALLED, IF | | | NOT ALREADY IN PLACE AT THE POINT OF | | | SERVICE ON PROPERTY.ALL BACKFLOW | | | PREVENTERS SHALL BE COMPLETLY HIDDEN | | | FROM VIEW WITH SHRUBS PRIOR TO | | | ACTIVATION. | | | 5. A CLEAN-OUT WILL NEED TO BE INSTALLED | | | IN THE SANITARY LATERAL, ON THE PROPERTY | | | , AT THE BACK OF THE SIDEWALK, IF NOT | | | ALREADY INSTALLED. | | | 6. ALL DRIVEWAY APPROACHES MUST BE (AT A | | | MIN.) PER CITY STANDARD.SEE ATTACHED | | | 7. ALL GRADES FOR CITY SIDEWALKS MUST BE | | | SET BY THE CITY SURVEY CREW, CALL 659- | | | 8040. | | | 8. DETAILS FOR EXFILTRATION TRENCH, | | | SHOWS 2 IN. TYPE II ASPHALT, SECTION B-B | | | SHOWS 1 1/2 IN. TYPE II, PLEASE VERIFY. | | | 8. PLEASE SPECIFY THICKNESS FOR | | | SIDEWALKS. | | | 9. PLEASE REFER TO APPROPRIATE SHEET FOR | | | HANDICAP PARKING SIGN DETAILS AND | | | INSTALLATION. | | | IF ANY QUESTION PLEASE CONTACT 561-659- | | | 8096 EXT. 8492. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-04-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-20 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-20 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2001-04-20 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY | | | CODE REQUIREMENTS. | | | 2) WRONG TRAVEL DISTANCE NOTED ON PLANS. | | | MAXIMUM TRAVEL DISTANCE ALLOWED BY THE | | | CURRENT FIRE CODE IS 150 FEET MAXIMUM. | | | 3) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 4) PLANS NOT SIGNED AND SEALED. | | | 5) PLEASE EXPLAIN USE OF CLASSROOMS, | | | HOURS OF OPERATION, AND AGE OF CHILDREN. | | | 6) THIS PROPERTY MAY BE LOCATED IN THE | | | CITY FIRE LIMITS. IF THE BUILDING IS | | | LOCATED IN THE FIRE LIMITS CERTAIN | | | RESTRICTIONS MAY APPLY TO IT. | | | 7) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED FOR WALLS AND | | | CEILING. | | | 8) PLEASE PROVIDE OCCUPANT LOAD | | | CALCULATIONS FOR THE BUILDING. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-05-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-08 |
Time |
11:45 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-05-08 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2001-05-08 00:00:00 | ********************DENIED************** | | | | | | FIRE DAMPERS ARE REQUIRED WHEN DUCTS | | | PENETRATE RATED WALLS AS PER 1997 SMC | | | 610.1.1.PLEASE INDICATE FIRE DAMPERS | | | AND ACCESS FOR MAINTENANCE/RESETTING ON | | | PLANS. | | | | | | MECHANICAL DRAWINGS SHALL BE SIGNED AND | | | SEALED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT.8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-05-08 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-05-08 |
Time |
07:01 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-08 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | REFERENCE CODES,STD PLBG 94,FACBC 97 | | | (1) SHT A2.1 FACBC SEC4.1.6 ACCESSIBLE | | | BUILDINGS, SHOW H/C ACCESSIBLE ROUTE, | | | TURNING RADIUS IN EACH REST RM,DRINKING | | | FOUNTAIN REQ,W/CLEAR FLR SPACE,FOR EA | | | FIXTURE. | | | (2) SHT MP.2 SHOW LOCATION OF BACK FLOW | | | PREVENTER ON WATER SERVICE,LOCAL ORD | | | #2938-96. | | | AIR CHAMBERS TO COMPLY WITH SEC 607.8.3 | | | ACCESSIBLE,RECHARGEABLE | | | END OF COMMENTSP[AUL SCHMITZ | | | QUESTIONS561-659-8096 X 8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-05-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-08 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |