Plan Review Details - Permit 01040626
Plan Review Stops For Permit 01040626
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-04-16 Cont ID  
Sent By pkrauss Date 2001-04-16 Time 11:18 Rev Time 0.40
Received By pkrauss Date 2001-04-16 Time 11:18 Sent To  
Notes
2001-04-16 00:00:00*******************PROVISO**************
  
 NO COMBUSTIBLES ABOVE CEILING IN RETURN
 AIR PLENUM, 1997 SMC 609.1.1.
  
 VAV-5, IF PENETRATING A RATED WALL WILL
 ALSO REQUIRE A FIRE DAMPER WITH A MEANS
 FOR ACCESS.