| 2001-04-19 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01040612 |
| | 1100 TECHNOLOGY PLACE SUITE 120 |
| | HEDRICK BROTHERS |
| | 689-8880 |
| | |
| | 1)- A COPY OF THE CODE COMMENTARY THAT |
| | PERTAINS TO CALCULATING AREA FOR A |
| | MEZZANINE IS ENCLOSED FOR REFRENCE, SEE |
| | AREA FOR OPEN AREA & AREA THAT IS |
| | ENCLOSED UNDER THE MEZZANINE. |
| | SBC 503.2.3.2. THE TOTAL SQ. FT. OF THE |
| | INTERIOR 24'-6" X 81'-9"= 2002.875 SQ FT |
| | CALC AREA MEZZANINE: |
| | 29'-8"X24'-6"=726' |
| | 12'-0"X16'-0"=192' |
| | TOTAL SQ FT918 SQ FT |
| | |
| | ALLOWABLE IF OPEN BELOW: |
| | 2002.875'X .33%= 660.948 SQ FT |
| | |
| | ALLOWABLE AREA ENCLOSED: |
| | 40'-6"X24'-6"=992.25X.33%=327.44 SQ FT |
| | |
| | 2)- DISCREPANCIES: |
| | A)- SHEET A-1 MEZZANINE DETAIL: DEPICTS |
| | A DOOR ON THE MEZZANINE LEVEL SWING |
| | ING FROM AREA BELOW? |
| | B)- SHEET A-1 DEPICT 1ST FLOOR UNDER |
| | THE PROPOSED MEZZANINE AS FILE |
| | STORAGE WHERE AS S-3 FLOOR LOADS |
| | INDICATES THE UAS AS A OFFICE. |
| | C)- S-3 FLOOR LOADS ALSO INDICATES A |
| | CATWALK? |
| | D)- S-3 ALSO INDICATES THE MECH. ROOM |
| | AS 125 LBS. FLOOR LOAD BUT NOT THE |
| | MEZZANINE FLOOR. |
| | |
| | 3)- THE TYPE OF STORAGE FOR THE PROPOSED |
| | MEZZANINE NEEDS TO BE DETERMINED: |
| | STORAGE SBC TABLE 204.1 |
| | MODERATE HAZARD S1- 3 HR |
| | LOW HAZARDS2- 2 HR |
| | DEPENDING ON THE TYPE OF MATERIALS TO BE |
| | CLASSIFIED (S1/S2), WE MAY NEED TO |
| | ADDRESS THE TENANT SEPERATION WALLS, |
| | WHAT MATERIALS ARE THEY MADE OF? |
| | |
| | 4)- ADMINISTRATIVE CODE/ CITY AMENDMENTS |
| | 106.4.2 IT SHALL BE THE RESPONSIBLITY OF |
| | THE OWNER,AGENT,PROPREITOR OR OCCUPANT |
| | OF GROUP S & GROUP F OCCUPANCIES,OR ANY |
| | OCCUPANCY WHERE EXCESSIVE FLOOR LOADING |
| | IS LIKELY TO OCCUR, TO EMPLOY A COMPE- |
| | TANT ARCHITECT OR ENGINEER IN COMPUTING |
| | THE SAFE LOAD CAPACITY. ALL SUCH COMPU- |
| | TATIONS SHALL BE ACCOMPANIED BY AN AFFI- |
| | DAVIT FROM THE ARCHITECT OR ENGINEER |
| | STATING THE SAFE FLOOR LOAD ON EACH |
| | FLOOR IN POUNDS PER SQUARE FOOT UNIFORM- |
| | LY DISTRIBUTED. THE COMPUTATIONS AND AFF |
| | IDAVIT SHALL BE FILED AS A PERMANENT |
| | RECORD OF THE BUILDING DEPARTMENT. |
| | |
| | 5)- ADMINISTRATIVE CODE/ CITY AMENDMENTS |
| | 106.4.3. IN EVERY BUILDING OR PART OF |
| | BUILDING USED FOR STORAGE, THE SAFE |
| | FLOOR LOADS, AS REVIEWED BY THE BUILDING |
| | OFFICIAL ON THTE PLAN, SHALL BE MARKED |
| | ON PLATES OF APPROVED DESIGN WHICH SHALL |
| | BE SUPPLIED AND SECURELY AFFIXED BY THE |
| | OWNER OF THE BUILDING IN A CONSPICUOUS |
| | PLACE IN EACH STORY, TO WHICH THEY RE- |
| | LATE. |
| | |