Plan Review Details - Permit 01040538
Plan Review Stops For Permit 01040538
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-28 Cont ID  
Sent By jwitmer Date 2001-04-28 Time 09:53 Rev Time 0.15
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-26 Cont ID  
Sent By jwitmer Date 2001-04-26 Time 11:23 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-26 00:00:00BUILDING PLAN REVIEW
 PERMIT 01040538
 315 26TH ST
 O/B COLOME, ELIZABETH
 833-8539
  
 1)- FL ACCESSIBILITY CODE 4.13.6 LEFT
 FRONT ENTRY DOESN'T MEET THE MANEUVERING
 CLEARENCES AT DOORS.
  
 2)- SHOW DETAILS OF RAMP. THE PLAN
 DEPICTS A NEW CONCRETE RAMP 5"-0" WITH A
 BREAK LINE INDICATING TTHERE IS CON-
 TINUED SLOPE TO THE FRONT DOOR. DETAIL
 RAMP, WHAT TYPE OF MATERIAL IS UNDER THE
 FRONT PORCH, IT MAY BE POSSIBLE THAT
 HAND RAILS MAY BE REQUIRED PER FL ACC
 CODE 4.8.5.
  
 3)- FL ACCESS CODE REQUIRES LANDINGS AT
 THE BOTTOM AND TOP OF EACH RAMP AND EACH
 RAMP RUN (4.8.4).
  
 4)- FL ACCES CODE 4.13.9 DOOR HARDWARE
 LEVER OPERATED MECHANISMS, PUSH-TYPE
 MECHANISMS, AND U- SHAPED HANDLES ARE
 ACCEPTABLE DESIGNS.
  
 5)- SEND THE PLANS TO THE COUNTY BUILD-
 ING DEPARTMENT TO BE ASSESSED FOR COUNTY
 IMPACT FEES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659 -8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-30 Cont ID  
Sent By dpalmer Date 2001-04-30 Time 08:03 Rev Time 0.00
Received By dpalmer Date 2001-04-30 Time 08:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-25 Cont ID  
Sent By dpalmer Date 2001-04-25 Time 18:42 Rev Time 0.00
Received By dpalmer Date 2001-04-25 Time 18:42 Sent To  
Notes
2001-04-25 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT MORE
 INFORMATION IS NEEDED FOR REVIEW.
 LIGHTING REQ`D IN BATHS PER 210-70?
  
 2)NOTE: PLEASE PROVIDE ALL BRANCH
 CIRCUIT #`S ON PLANS FOR T.I.
 IMPROVEMENTS PER215-5. PLEAS SUBMIT A
 PANEL SCHEDULE THATS CORRELATES W/BR #`S
 3)NOTE: PLEASE PROVIDE INFORMATION ON
 EXISTING OUTLET SPACING FOR COMMERICAL
 OFFICE PER 210-50 OF
 COUNTY-WIDE/CITY-WIDE ADMINISTRATIVE
 CODE.
  
 4)NOTE: PLEASE PROVIDE INFORMATION ON
 EXISTING OR NEW EGRESS LIGHTING REQ`D .
 FOR EXITING OUTSIDE ILLUMINATION.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 CLARIFICATION AND REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-04-26 Cont ID  
Sent By mcarsill Date 2001-04-26 Time 07:49 Rev Time 0.00
Received By mcarsill Date 2001-04-26 Time 07:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-04-28 Cont ID  
Sent By kstevens Date 2001-04-28 Time 07:36 Rev Time 0.25
Received By kstevens Date 2001-04-28 Time 07:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-04-25 Cont ID  
Sent By kstevens Date 2001-04-25 Time 17:30 Rev Time 0.25
Received By kstevens Date 2001-04-25 Time 17:30 Sent To  
Notes
2001-04-25 00:00:00PLUMBING PLAN REVIEW.
  
 DENIED:
 REFERANCE FACBC-97
  
 (1) HDCP RESTROOMS REQUIRED FOR EACH SEX
 PROVIDE DIMENTIONS FOR FOR EACH ROOM
 4.1.6 2-III
  
 (2) 2ND BATHROOM DOES NOT MEET ADA
 REQUIREMENTS.
 DOOR IS NOT LARGE ENOUGH AND IT
 SWINGS INTO THE CLEAR FLOOR SPACE.
  
 PLAN REVIEW BY KEN STEVENS
 (561) 659-8096 X'S 8389/8377