| Plan Review Stops For Permit 01040531 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-05-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-14 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-14 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2001-05-14 00:00:00 | 1) SMOKE DETECTORS ARE TO BE INSTALLED | | | A MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 2) FIRE ALARM CIRCUITS TO BE CLASS A, | | | STYLE D. | | | 3) FIRE ALARM SYSTEM TO BE MONITORED | | | BY A LICENSED UL LISTED CENTRAL STATION | | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-04-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-11 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-11 |
Time |
15:47 |
Sent To |
|
|
| Notes |