| Plan Review Stops For Permit 01040482 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-10-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-01 |
Time |
13:21 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2001-10-01 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2001-10-01 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01040482 | | | BLDG "D" | | | 617 EXECUTIVE CENTER DR | | | | | | | | | REVISIONS SAME AS 01040482 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-08-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-12 |
Time |
11:12 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2001-08-12 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2001-08-12 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT# 01040482 | | | 617 EXECUTIVE CENTER DRIVE | | | | | | REVISION #1 | | | | | | COMMENTS ARE THE SAME AS PREMIT 01040479 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-07-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-18 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-07-20 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2001-07-20 00:00:00 | APPROVED PER JIM WITMER | | 2001-05-18 00:00:00 | BUILDING PLAN REVIEW | | | PLAN CHECK # 01040482 | | | 617 EXECUTIVE CENTER DR | | | BUILDING:D (4 STORY) | | | | | | | | | SEE PLAN CHECK FOR NOTES 01040479 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-05-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-07 |
Time |
17:51 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-05-07 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2001-05-07 00:00:00 | BUILDING PLAN CHECK | | | PLAN CHECK 01040482 | | | 617 EXECUTIVE CENTER DRIVE | | | BUILDING: D (4 STORY) | | | | | | COMMENTS ARE THE SAME AS FOR PERMIT | | | 01040479. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-29 |
Time |
17:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-29 |
Time |
17:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-18 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-18 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2001-05-24 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-05-24 |
Time |
08:37 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2001-05-24 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | PASSED : | | | 1. SEE PERMIT NUMBER 01030517 FOR REVIEW | | | COMMENTS. | | | IF ANY QUESTIONS PLEASE CONTACT 561-659- | | | 8096 EXT. 8492 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-05-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-23 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-23 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-05-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-18 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-18 |
Time |
13:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-05-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-03 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-03 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2001-05-03 00:00:00 | 1) ALL UNDERGROUND FIRE MAINS ARE TO BE | | | LISTED FOR FIRE PROTECTION SERVICE AND | | | COMPLY WITH NFPA 24, FIRE SERVICE MAINS | | | AND THEIR APPURTENANCES. | | | 2) INGRESS AND EGRESS INTO THE COMPLEX | | | SHALL BE A MINIMUM OF TWENTY FEET IN | | | CLEAR WIDTH. BATTERY BACK-UP FEATURE | | | SHALL BE PROVIDED FOR GATE-ARMS SHOULD | | | LOSS OF POWER OCCUR. TRAFFIC CALMING | | | HUMPS ARE NOT TO INTERFERE WITH FIRE | | | RESCUE MOVEMENT INTO THE COMPLEX. | | | 3) BUILDING LETTERS A,B,C AND D, ARE TO | | | BE PLACED ON THE BUILDING SINCE IT | | | APPEARS TO BE A SINGLE ADDRESS FOR THE | | | APARTMENT COMPLEX. | | | 4) AT LEAST ONE STAIR IS TO BE PROVIDED | | | DURING CONSTRUCTION. TEMPORARY | | | STANDPIPES ARE REQUIRED IN ALL BUILDINGS | | | UNDER CONSTRUCTION WHEN THEY ARE | | | REQUIRED TO HAVE STANDPIPE SYSTEMS. | | | 5) HOW IS THE COMBUSTIBLE LINT REMOVED | | | FROM THE DRYER CHASE. NO ACCESS PANELS | | | HAVE BEEN PROVIDED. | | | 6) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE INSTALLATIONS OF THE FIRE | | | SPRINKLER SYSTEMS. NO HYDRAULIC | | | CALCULATIONS PROVIDED WITH FIRE | | | SPRINKLER DRAWINGS. STANDPIPE SYSTEMS | | | REQUIRED IN ALL BUILDINGS THREE STORIES | | | AND MORE THAN FIFTY IN HEIGHT. ALL | | | VERTICAL SHAFTS ARE TO BE FIRE | | | SPRINKLER PROTECTED. PLEASE EXPLAIN | | | RATIONALE FOR THE SINGLE FIRE | | | DEPARTMENT CONNECTION SHOWN ON THE | | | DRAWINGS. | | | 7) DOOR SWINGS IN THE STAIRWELLS ARE TO | | | SWING IN THE DIRECTION OF EXIT TRAVEL. | | | 8) SMOKE DETECTORS WHEN INSTALLED ARE | | | TO BE A MINIMUM OF THREE FEET FROM | | | AIR CONDITIONER DIFFUSERS. | | | 9) TRASH CHUTES TO COMPLY WITH NFPA 82, | | | THE STANDARD ON INCINERATORS,WASTE AND | | | LINEN HANDLING SYSTEMS AND EQUIPMENT. | | | 10) PLEASE INDICATE PORTABLE FIRE | | | EXTINGUISHER LOCATIONS. | | | 11) SIGNS ARE REQUIRED FOR ALL BUILDINGS | | | FOUR OR MORE STORIES. SIGNS SHALL | | | INDICATE FLOOR LEVEL, THE IDENTITY OF | | | THE STAIR, THE TERMINUS OF THE STAIR, | | | TOP AND BOTTOM. | | | 12) PLEASE INDICATE THE DISTANCES | | | BETWEEN THE TRANSFORMER PADS AND THE | | | EXITWAYS FROM THE BUILDING. | | | 13) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE FIRE ALARM SYSTEMS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
P |
Date |
2002-04-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-23 |
Time |
09:10 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-23 00:00:00 | MECH PERMIT 01071107PLAN UNDER PERMIT | | | 01040479 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2002-04-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-15 |
Time |
12:16 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-15 00:00:00 | PROVISO:MECH PERMIT 01071107 | | | | | | 2 COPIES OF ORIGINAL LETTER FOR MONTHLY | | | MAINTENANCE FOR THE CLEANING OR THE | | | BOOSTER FAN.TWO NOTARIZED LETTERS TO | | | FOLLOW. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2002-03-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-12 |
Time |
09:56 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-12 00:00:00 | SUBMITTAL-LOUVERS FOR THE ELEVATOR SHAFT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2002-03-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-12 |
Time |
09:18 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-03-12 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2002-03-12 00:00:00 | ********************DENIED************** | | | | | | MECHANICAL PERMIT 01071107 | | | CALCULATIONS FOR DRYER EXHAUST | | | | | | PROVIDE SPECIFIC MANUFACTURER SUBMITTAL | | | DATA & PURCHASE ORDER FOR DRYERS. | | | DRYERS TO BE INSTALLED AT THE TIME OF | | | FINAL INSPECTION.DUCTWORK TO BE | | | INSTALLED AS PER SPECIFIC MANUFACTURERS | | | INSTRUCTIONS. RESIDENTIAL DRYER | | | EXHAUST DUCTS WHICH ARE NOT DESIGNED | | | FOR SPECIFIC DRYER SHALL COMPLY WITH | | | 1997 SMC 509.3. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2002-02-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-08 |
Time |
09:31 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-02-08 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2002-02-08 00:00:00 | | | | | | | MECH PERMIT 01071107 | | | | | | LETTER FROM ENGINEER ON BATHROOM EXHAUST | | | TERMINATING AT A RATED WALL WHICH IS AN | | | EGRESS CORRIDOR.FIRE DAMPERS ARE NOT | | | PERMITTED IN DRYER EXHAUST. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-05-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-24 |
Time |
07:49 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | NOTES UNDER PERMIT 01040480. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2001-05-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-24 |
Time |
07:48 |
Rev Time |
1.30 |
| Received By |
pkrauss |
Date |
2001-05-17 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | REVIEW UNDER PERMIT 01040480 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-05-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-10 |
Time |
11:07 |
Rev Time |
3.00 |
| Received By |
pkrauss |
Date |
2001-05-10 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2001-05-10 00:00:00 | REVIEW NOTES ON PERMIT 01040480. | | | THIS SET IS NOT A FULL SET OF AC | | | DRAWINGS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2003-01-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-22 |
Time |
09:18 |
Rev Time |
0.10 |
| Received By |
kstevens |
Date |
2003-01-22 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2003-01-22 00:00:00 | SUBMITTAL - DOMESTIC BOOSTER PUMP PKG |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2002-09-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-09-26 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-09-26 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2002-09-26 00:00:00 | REVISION OK - ADD 2 6" OVERFLOW SCUPPERS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2001-11-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-29 |
Time |
16:03 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-11-29 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2001-10-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-19 |
Time |
16:23 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-10-19 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2001-10-19 00:00:00 | DENIED | | | | | | SEE COMMENTS FROM PERMIT #01040479 | | | | | | REVEIW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2001-09-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-28 |
Time |
14:57 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-09-28 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2001-09-28 00:00:00 | DENIED | | | | | | SEE COMMENTS FROM PERMIT #01040479 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-09-22 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-09-22 |
Time |
08:46 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-22 00:00:00 | REVISION, PLUMBING FOUNDATION ONLY.PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-05-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-05-24 |
Time |
07:34 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2001-05-24 |
Time |
07:34 |
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | REVIEW NOTES ....PASSED.... | | | | | | ....PROVISO... | | | | | | 1) GENERAL NOTES #15 COPIES OF ALL DOC- | | | UMENTS TO FILED WITH THE DEPARTMENT OF | | | CONSTRUCTION SERVICES. CHANGE "L" TO | | | CITY OF WEST PALM BEACH. GNI 1 OF 1. | | | | | | 2) TYPICAL WATER RISER DIAGRAM - MAXIMUM | | | FIXTURES ON 1/2" COLD IS 2 FIXTURES. | | | MODEL COUNTYWIDE AMENDMENTS TO SPC-94 | | | 607.7 | | | | | | 3) AIRCHAMBERS TO COMPLY WITH SPC-94 | | | 607.8.2 & 607.8.3 | | | | | | 4) PAGE P-4, P/T #1 ON FLOOR PLAN SHOWS | | | 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS | | | A SINGLE RISER. TWO RISERS ARE REQUIRED. | | | | | | 5) FAIR HOUSING ACT 1996 AMENDED 1998 | | | REQUIREMENT 7B REQUIRES THAT SPEC.A OR | | | B BE SHOWN ON PLAN. | | | | | | 6) PAGE A8.1 BACKING AT TUB TO BE 1'-5" | | | NOT 1'-2" AS SHOWN ON PLAN. FHA-96 | | | AMEND. - 98 REQUIREMENT 6. | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8389 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-05-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-05-16 |
Time |
19:22 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2001-05-17 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2001-05-16 00:00:00 | REVIEW NOTES. PASSED...PROVISO... | | | | | | 1) GENERAL NOTES #15 COPIES OF ALL DOC- | | | UMENTS TO BE FILED WITH THE DEPARTMENT | | | OF CONSTRUCTION SERVICES. CHANGE "L" TO | | | CITY OF WEST PALM BEACH. GNI 1 0F 1 | | | | | | 2) TYPICAL WATER RISER DIAGRAM - MAXIMUM | | | FIXTURES ON 1/2" COLD IS 2 FIXTURES. | | | MODEL COUNTYWIDE AMENDMENTS TO SPC-94 | | | 607.7 | | | | | | 3) AIR CHAMBERS TO COMPLY WITH SPC-94 | | | 607.8.2 & 607.8.3 | | | | | | 4) PAGE P-5, P/T #1 ON FLOOR PLAN SHOWS | | | 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS | | | A SINGLE RISER. TWO RISERS ARE REQUIRED. | | | | | | 5) FAIR HOUSING ACT 1996 AMENDED 1998 | | | REQUIREMENT 7B REQUIRES THAT SPEC. A OR | | | B BE SHOWN ON PLAN. | | | | | | 6) PAGE A8.1 BACKING AT TUB TO BE 1'-5" | | | NOT 1'-2" AS SHOWN ON PLAN. FHA-96 | | | AMEND-98 REQUIREMENT 6. | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-05-22 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-05-04 |
Time |
14:04 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-22 00:00:00 | APPROVED BY ANGELLA VANN | | 2001-05-04 00:00:00 | NEED MINOR AMENDENT |
|
|