| Plan Review Stops For Permit 01040480 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-29 |
Time |
10:23 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-10-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-01 |
Time |
12:55 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2001-10-01 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2001-10-01 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01040480 | | | BLDG "B" | | | 609 EXECUTIVE CENTER DR | | | | | | | | | SEE 01040479 SAME COMMENTS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-08-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-23 |
Time |
16:59 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2001-08-23 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2001-08-23 00:00:00 | STRUCTURAL REVISIONS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-07-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-18 |
Time |
11:18 |
Rev Time |
2.00 |
| Received By |
sjohnson |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-20 00:00:00 | APPROVED PER JIM WITMER | | 2001-05-18 00:00:00 | BUILDING PLAN REVIEW | | | PLAN CHECK 01040480 | | | 609 EXECUTIVE CENTER DR | | | BUILDING "B" (5 STORY) | | | | | | SEE PLAN REVIEW 01040479 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-05-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-07 |
Time |
17:16 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-07 00:00:00 | BUILDING PLAN REVIEW | | | PLAN CHECK 01040480 | | | 609 EXECUTIVE CENTER DRIVE | | | BUILDING: B (5 STORY) | | | | | | 1)- SHEET A.6 DETAIL 2 DEPICTS THE ROOF- | | | ING TO BE ATTACHED TO PURLINS, AMENDMENT | | | 1503.1.2.2. REQUIRES ALLROOFING TO BE AP | | | PLIED TO SOLID OR CLOSELY FITTED DECKING | | | OR SHEATHING. | | | | | | 2)- SOILS REPORT REQUIRED AMENMENTS | | | 1804.2.7.2. | | | | | | 3)- COMPONENTS & CLADDING THERE IS NO | | | WINDOW BUCK ATTACHMENT. | | | | | | 4)- SHEET 2.3 DETAILS FOR THE REFUSE | | | SHUTE ARE MISSING, A (2 HR) WALL WILL BE | | | REQUIRED TO PROTECT THE SHUTE, | | | SBC 705.2.4.2/ 705.2.4.3. | | | | | | 5)- PRODUCT APPROVALS FOR ALL GLAZED | | | OPENINGS CAN BE SUBMITTED AFTER THE PER- | | | MIT IS ISSUED, A "PROVISO". THE CITY'S | | | POLICY FOR GLAZED OPENINGS WILL BE | | | ENFORCED!SBC 1606.4/1707.4.1. | | | | | | 6)- ROOFING CAN ALSO BE ISSUED UNDER SEP | | | ERATE PERMIT PRODUCT APPROVAL WILL BE RE | | | QUIRED. | | | | | | 7)- FL. SATUTE 553.895 REQUIRES FIRE | | | SPRINKLER PLANS. | | | | | | 8)- SHEET A.6 DEPICTS THE ROOFING WITH | | | WIRE LATH THE BACKING OR SHEATHING | | | DOESN'T DESCRIBE THE MATERIAL. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-29 |
Time |
17:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-29 |
Time |
17:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-07-20 |
|
|
Cont ID |
|
| Sent By |
sjohnson |
Date |
2001-07-20 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
sjohnson |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-20 00:00:00 | APPROVED PER D V PALMER | | | APPROVED PER D V PALMER |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2001-05-24 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-05-24 |
Time |
08:24 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2001-05-24 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | PASSED : | | | 1. SEE PERMIT NUMBER 01030517 FOR REVIEW | | | COMMENTS. | | | IF ANY QUESTION PLEASE CONTACT 561-659- | | | 8096 EXT. 8096 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-05-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-23 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-23 |
Time |
16:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-05-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-18 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-18 |
Time |
13:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-05-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-03 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-03 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2001-05-03 00:00:00 | 1) ALL UNDERGOUND FIRE MAINS ARE TO BE | | | LISTED FOR FIRE PROTECTION SERVICE AND | | | COMPLY WITH NFPA 24, FIRE SERVICE MAINS | | | AND THEIR APPURTENANCES. | | | 2) INGRESS AND EGRESS INTO THE COMPLEX | | | SHALL BE A MINIMUM OF TWENTY FEET IN | | | CLEAR WIDTH. BATTERY BACK-UP FEATURE | | | SHALL BE PROVIDED FOR GATE-ARMS SHOULD | | | LOSS OF POWER OCCURS. TRAFFIC CALMING | | | HUMPS ARE NOT TO INTERFERE WITH FIRE | | | RESCUE MOVEMENT INTO THE COMPLEX. | | | 3) BUILDING LETTERS A,B,C, AND D, ARE TO | | | BE PLACED ON THE BUILDING SINCE IT | | | APPEARS TO BE A SINGLE ADDRESS FOR THE | | | APARTMENT COMPLEX. | | | 4) AT LEAST ONE STAIR IS TO BE PROVIDED | | | DURING CONSTRUCTION. TEMPORARY | | | STANDPIPES ARE REQUIRED IN ALL BUILDINGS | | | UNDER CONSTRUCTION WHEN THEY ARE | | | REQUIRED TO HAVE STANDPIPE SYSTEMS. | | | 5) HOW IS COMBUSTIBLE LINT REMOVED | | | FROM THE DRYER CHASE. NO ACCESS PANELS | | | HAVE BEEN PROVIDED. | | | 6) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE INSTALLATIONS OF THE FIRE | | | SPRINKLER SYSTEMS. NO HYDRAULIC | | | CALCULATIONS PROVIDED WITH FIRE | | | SPRINKLER DRAWINGS. STANDPIPE SYSTEMS | | | ARE REQUIRED IN ALL BUILDINGS THREE | | | STORIES AND MORE THAN 50 FIFTY FEET | | | IN HEIGHT. ALL VERTICAL SHAFTS ARE TO | | | BE FIRE SPRINKLER PROTECTED. PLEASE | | | EXPLAIN RATIONALE FOR THE SINGLE | | | FIRE DEPARTMENT CONNECTION SHOWN ON | | | THE DRAWINGS. | | | 7) DOOR SWINGS IN THE STAIRWELLS ARE TO | | | SWING IN THE DIRECTION OF EXIT TRAVEL. | | | 8) SMOKE DETECTORS WHEN INSTALLED ARE TO | | | BE A MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 9) TRASH CHUTES TO COMPLY WITH NFPA 82, | | | THE STANDARD ON INCINERATORS, WASTE AND | | | LINEN HANDLING SYSTEMS AND EQUIPMENT. | | | 10) PLEASE INDICATE PORTABLE FIRE | | | EXTINGUISHER LOCATIONS. | | | 11) SIGNS ARE REQUIRED FOR ALL BUILDINGS | | | FOUR OR MORE STORIES. SIGNS SHALL | | | INDICATE FLOOR LEVEL, THE IDENTITY OF | | | THE STAIR, THE TERMINUS OF THE STAIR, | | | TOP AND BOTTOM. | | | 12) PLEASE INDICATE THE DISTANCES | | | BETWEEN THE TRANSFORMER PADS AND THE | | | EXITWAYS FROM THE BUILDING. | | | 13) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE FIRE ALARM SYSTEMS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
P |
Date |
2002-04-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-23 |
Time |
08:44 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-23 00:00:00 | MECH PERMIT 01071097 - DUCT REVISION | | | PLAN UNDER PERMIT01040479 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2002-04-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-15 |
Time |
12:12 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-15 00:00:00 | PROVISO:MECH PERMIT 01071097 | | | | | | 2 COPIES OF ORIGINAL LETTER FOR MONTHLY | | | MAINTENANCE FOR THE CLEANING OF THE | | | BOOSTER FAN.TWO NOTARIZED LETTERS TO | | | FOLLOW. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2002-03-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-12 |
Time |
09:54 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-12 00:00:00 | SUBMITTAL FOR LOUVERS FOR THE ELEVATOR | | | SHAFT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2002-03-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-11 |
Time |
14:53 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-03-11 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2002-03-11 00:00:00 | ********************DENIED************** | | | | | | MECHANICAL PERMIT 01071097 | | | CALCULATIONS FOR DRYER EXHAUST - | | | | | | PROVIDE SPECIFIC MANUFACTURER SUBMITTAL | | | DATA & PURCHASE ORDER FOR DRYERS. | | | DRYERS TO BE INSTALLED AT THE TIME OF | | | FINAL INSPECTION.DUCTWORK TO BE | | | INSTALLED AS PER SPECIFIC MANUFACTURERS | | | INSTRUCTIONS. RESIDENTIAL DRYER EXHAUST | | | DUCTS WHICH ARE NOT DESIGNED FOR A | | | SPECIFIC DRYER SHALL COMPLY WITH 1997 | | | SMC 509.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2002-02-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-13 |
Time |
16:22 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-02-08 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2002-02-08 00:00:00 | | | | MECHANICAL PERMIT 01071097 | | | | | | LETTER FROM ENGINEER ON BATHROOM | | | EXHAUSTCALCULATIONS - APPROVED. | | | | | | PLANS SUBMITTED ARE DENIED.DRYER | | | EXHAUST TERMINATING AT A RATE WALL | | | WHICH IS AN EGRESS CORRIDOR.FIRE | | | DAMPERS ARE NOT PERMITTED IN DRYER | | | EXHAUST. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-05-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-22 |
Time |
15:48 |
Rev Time |
1.30 |
| Received By |
pkrauss |
Date |
2001-05-22 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2001-05-22 00:00:00 | ******************PROVISO*************** | | | | | | | | | PLEASE PROVIDE DETAIL FOR THE ELEVATOR | | | SHAFT IS INCLUDED.(VENTILATION/FIRE | | | PROTECTION 1997 SBC 3003.6) | | | | | | APARTMENTS CONSTRUCTED TO COMPLY WITH | | | THE FAIR HOUSING ACT SHALL MEET THE | | | HEIGHT REQUIREMENT FOR THERMOSATS AS | | | PER SECTION 5.5 OF THE FAIR HOUSING ACT | | | DESIGN MANUAL. | | | | | | CLUBHOUSE:SHOULD WALLS BETWEEN "CARD | | | ROOM" AND "UTILITY ROOM"BE RATED, | | | FIRE DAMPERS WILL BE REQUIRED AS PER | | | 1997 SMC 610.1.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2001-05-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-17 |
Time |
12:20 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-05-17 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2001-05-17 00:00:00 | COMMENTS FROM FRIST REVIEW STAND...HAVE | | | NOT CHANGED ANY MECHANICAL PLANS.SPOKE | | | WITH SEAN REVISIONS TO COME LATER. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-05-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-10 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2001-05-10 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2001-05-10 00:00:00 | PERMIT 01040480 - 609 EXEC. CTR. DR. | | | PERMIT 5 STORY, PLAN REFLECT 3 STORY | | | | | | | | | 1.DRYER SUBDUCT NEEDS TO INDICATE | | | ACCESS FOR CLEANOUT. | | | | | | 2.DRYER SUBDUCT NEEDS TO INDICATE | | | MEANS OF FIRE PROTECTION AS PER | | | NFPA 13 4-4.8. | | | | | | 3.GALV. STL. SUBDUCT FOR DYER VENT | | | & TOILET EXHAUST - IS INSIDE OF | | | SUBDUCT GALVENIZED? | | | | | | 4.DRAWING A6.0 DEPICTS AHU AND WATER | | | HEATER CLOSET,AHU MUST HAVE CLEAR | | | ACCESS FOR REPLACEMENT OF AHU & | | | FOR CONECTION OF DUCT TO UNIT AS | | | WELL AS FOR INSPECTION. | | | | | | 5.CONDENSATE TO DRYWELL OKAY, WHAT | | | ABOUT OVERFLOW PROTECTION FOR | | | AUXILIARY DRAIN PAN AS PER 1997 | | | SMC 304.8.6.1.(DWG P-2) | | | | | | 6.PLEASE SUBMIT DETAIL OF CONDENSER | | | UNIT STANDS,MINIMUM OF 18" FROM | | | ROOF SURFACE TO BOTTOM OF SUPPORT | | | RAIL (AMENDED 1997 SMC 304.2.5) | | | DETAIL MUST BE AN ENGINEERED | | | DRAWING.(UPLIFT/WINDLOAD AND | | | HOW TO ATTACH TO ROOF STRUCTURE.) | | | | | | 7.NO DETAIL FOR THE ELEVATOR SHAFT | | | IS INCLUDED.(VENTILATION/FIRE | | | PROTECTION 1997 SBC 3003.6) |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
10 |
Status |
P |
Date |
2003-01-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-22 |
Time |
08:46 |
Rev Time |
0.10 |
| Received By |
kstevens |
Date |
2003-01-22 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2003-01-22 00:00:00 | SUBMITTALS - PUMP SKID |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
P |
Date |
2002-09-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-09-26 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-09-26 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2002-09-26 00:00:00 | REVISION OK - ADDING 2 6" SCUPPER LINES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2002-04-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-10 |
Time |
19:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-10 |
Time |
19:47 |
Sent To |
|
|
| Notes |
| 2002-04-10 00:00:00 | SUBMITTAL OK - NEW DOMESTIC PUMPS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2002-03-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-01 |
Time |
14:32 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-03-01 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2002-03-01 00:00:00 | RESUBMITTAL OF SUBMITTAL FOR PUMP ROOM | | | REVISED MANIFOLD CONFIGURATION TO FIT RM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2002-02-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-28 |
Time |
14:05 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-02-28 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2002-02-28 00:00:00 | SUBMITTALS FOR BOOSTER PUMB 0K |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2001-11-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-29 |
Time |
15:51 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-11-29 |
Time |
15:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2001-10-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-19 |
Time |
16:20 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-10-19 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2001-10-19 00:00:00 | DENIED | | | SEE COMMENTS FROM PERMIT #1040479 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-09-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-28 |
Time |
15:00 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-09-28 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2001-09-28 00:00:00 | DENIED | | | | | | SEE COMMENTS FROM PERMIT #01040479 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-09-22 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-09-22 |
Time |
10:08 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-22 00:00:00 | REVISION,PLUMBING FOUNDATION ONLY. PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-05-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-05-16 |
Time |
18:57 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
2001-05-17 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2001-05-16 00:00:00 | REVIEW NOTES. PASSED...PROVISO... | | | | | | 1) GENERAL NOTES #15 COPIES OF ALL DOC- | | | UMENTS TO BE FILED WITH THE DEPARTMENT | | | OF CONSTRUCTION SERVICES. CHANGE "L" TO | | | CITY OF WEST PALM BEACH. GNI 1 OF 1. | | | | | | 2) TYPICAL WATER RISER DIAGRAM - MAXIMUM | | | FIXTURES ON 1/2" COLD IS 2 FIXTURES. | | | MODEL COUNTYWIDE AMENDMENTS TO SPC-94 | | | 607.7 | | | | | | 3) AIR CHAMBERS TO COMPLY WITH SPC-94 | | | 607.8.2 & 607.8.3 | | | | | | 4) PAGE P-4, P/T #1 ON FLOOR PLAN SHOWS | | | 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS | | | A SINGLE RISER. TWO RISERS ARE REQUIRED. | | | | | | 5) FAIR HOUSING ACT 1996 AMENDED 1998 | | | REQUIREMENT 7B REQUIRES THAT SPEC. A OR | | | B BE SHOWN ON PLAN. | | | | | | 6) PAGE A8.1 BACKING AT TUB TO BE 1'-5" | | | NOT 1'-2" AS SHOWN ON PLAN. FHA-96 | | | AMEND. - 98 REQUIREMENT 6. | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-07-20 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-05-04 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
sjohnson |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-04 00:00:00 | NEED MINOR AMENDMENT |
|
|