Plan Review Details - Permit 01040479
Plan Review Stops For Permit 01040479
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2002-03-27 Cont ID  
Sent By jwitmer Date 2002-03-27 Time 09:55 Rev Time 1.11
Received By jwitmer Date 2002-03-27 Time 09:55 Sent To  
Notes
2002-03-27 00:00:00SUBMITTAL- NO. S-73
 REF: A/S-1 ON SK-1 ALTERNATE
 CONNECTION DETAIL
  
 THE CITY HAS REVIEWED THE INFORMATION
 PROVIDED FOR THE ALTERNATE CONNECTION
 DETAIL. WE CAN NOT ACCEPT THIS INFORMA-
 TION AS IS. THE ENGINEER OF RECORD HAS
 THE OPTIONS OF :
 1)- A PEER REVIEW HAS BEEN ACCOMPLISHED
 BY MOODY ENGINEERING, THE ENGINEER OF RE
 CORD HAS SIGNED BUT NOT SEALED THE
 LETTER HEAD PROVIDED BY MOODY. MR WALSH
 MAY SEAL HIS SIGNATURE OR
 2)- MR WALSH AS ENGINEER OF RECORD MAY
 ON HIS OWN LETTER HEAD INDICATE THAT
 HE HAS REVIEWED THE INFORMATION, IS IN
 AGREEMENT WITH THE FINDINGS AND SIGN
 AND SEAL HIS OWN LETTER HEAD AND ATTACH
 IT TO THE PACKAGE OR
 3)- MR WALSH MAY DO A FIELD INSPECTION
 CHECKING THE CONNECTIONS WITH A TORQUE
 WRENCH AND CERTIFYING THE INSTALLATION
 BY AFFIDAVIT, SIGNED & SEALED.
 THE CITY WILL ACCEPT ANY OF THE THREE
 OPTIONS LISTED ABOVE.
 PLAN REVIEW BUILDING
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2001-12-26 Cont ID  
Sent By jwitmer Date 2001-12-26 Time 10:13 Rev Time 1.25
Received By jwitmer Date 2001-12-26 Time 10:13 Sent To  
Notes
2001-12-26 00:00:00REFUSE CHUTE SHOP DRAW
 PERMIT:
 BLDG A: 01040479
 BLDG B: 01040480
 BLDG C: 01040481
 BLDG D: 01040482
  
 STANDARD BUILDING CODE 705.2.4.2.
 REFUSE CHUTE ENCLOSURES:
 ALL OPENINGS INTO SHAFT ENCLOSURES SHALL
 BE PROTECTED IN ACCORDANCE WITH
 TABLE 705.1.2 REUSE CHUTE REQUIRE A
 2 HR RATING, SHOP DRAWINGS NOTE #5 INDIC
 ATES THE CHUTE THROUGH THE ROOF LINE
 WITH NO SHAFT ENCLOSURE THROUGH THE
 TRUSSES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-10-29 Cont ID  
Sent By jwitmer Date 2001-10-29 Time 08:59 Rev Time 1.00
Received By jwitmer Date 2001-10-29 Time 08:59 Sent To  
Notes
2001-10-29 00:00:00REVISIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-10-01 Cont ID  
Sent By jwitmer Date 2001-10-01 Time 12:29 Rev Time 3.00
Received By jwitmer Date 2001-10-01 Time 12:29 Sent To  
Notes
2001-10-01 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01040479
 BLDG "A"
 605 EXECUTIVE CENTER DR
  
 REVISIONS : CITY RECEIVED DATE 9/20/01
 1)- SHEET A2.0 MISING RED LINE NOTE FOR
 TRASH ROOM
  
 2)- SHEET A2.3 DETAIL #8 SBC 1608.2.2.3
 SHOW COMPLIANCE WITH GAURD RAIL TO
 RESIST 200 LBS CONCENTRATED HORIZONTAL
 LOADS APPLIED ON A 1 FT SQ AREA. AT ANY
 POINT IN THE SYSTEM INCLUDING INTERMED-
 IATE RAILS OR OTHER ELEMENTS SERVING
 THIS PURPOSE.
  
 3)- SHEET A.6 MISSING RED LINE CORREC-
 TIONS,
 A)- ROOFING COMMENTS
 B)- ROOF A/C AIR HANDLERS & SUP-
 PORTS MIN. 18" CLEARENCE IS
 MISSING.
 C)- A/C CLOSET - INCREASE THE DOOR
 HEIGTH FOR FULL ACCESS.
  
 4)- SHEET #7 NOTE MISSING DETAIL #2,
 FLOOR DRAINS, INACTUALLITY, OVERFLOW
 SCUPPERS (SBC 1517.6.4.3) NOT LESS THAN
 2" ABOVE THE ROOF DECK NOR 4" MAXIMUM.
  
 5)- SHEET A8.1 IS MISING RED LINE CORREC
 TIONS TO THE FAIR HOUSING ACT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-08-12 Cont ID  
Sent By jwitmer Date 2001-08-12 Time 10:21 Rev Time 1.50
Received By jwitmer Date 2001-08-12 Time 10:21 Sent To  
Notes
2001-08-12 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01001040479
 605 EXECUTIVE CENTER DRIVE
  
 REVISION: #1
  
 1)- SBC 104.2.2 ADDITIONAL INFORMATION
 REQUIRED, THE PLANS SUBMITTED FROM
 SSTEVEN WALSH DATED 7/26/01 DO NOT INDIC
 ATE THE SCALE THEY ARE DRAWN BY NOR DO
 THEY GIVE ANY DIMENSIONS IN WIDTH,
 WIDTH OR IN HEIGHT BETWEEN FLOORS.
  
 2)- SHEET S-2 INDICATES A FLOOR OPENING
 THAT ISN'T INDICATED ON THE STRUCTURAL
 DRAWINGS, PLEASE INDICATE THE USAGE, IF
 IT IS FOR VENTING, PLEASE GIVE THE U.L.
 RATING FOR THE CHASE.
  
 3)- SHEET SEC-AD TYPICAL COLUMN DETAIL:
 PLEASE GIVE THE ASSEMBLY RATING FOR THIS
 DETAIL, THANK YOU.
  
 4)- DISCREPANCY: THE SOILS REPORT FROM
 ARDAMAN & ASSOCIATES 8.3 FOUNDATIONS:
 " ALL CONTINUOUS FOUNDATIONS SHOULD BE
 AT LEAST 30" WIDE, AND ALL INDIVIDUAL
 COLUMN FOOTINGS SHOULD HAVE A MINIMUM
 WIDTH OF 30 INCHES". HAS THE NEW DESIGN
 FROM WALSH BEEN REVIEWED BY THE SOILS
 ENGINEER, A LETTER FROM ARDAMAN WILL BE
 REQUIRED ADDRESSING THE NEW FOUNDATION
 DESIGN AND THE NEW CONFIGURATION OF
 FOOTING & FOUNDATIONS, (SIGNED/SEALED).
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-20 Cont ID  
Sent By jwitmer Date 2001-05-18 Time 09:34 Rev Time 0.00
Received By sjohnson Date   Time   Sent To  
Notes
2001-07-20 00:00:00APPROVED PER JIM WITMER
2001-05-18 00:00:00BUILDING PLAN CHECK
 PLAN REVIEW# 01040479
 605 EXECUTIVE CENTER DR
 BUILDING A ( 3 STORY)
  
 1)- SHEET A.6 DETAIL 2 DEPICTS THE ROOF-
 ING TO BE ATTACHED TO PURLINS, AMENDMENT
 11503.1.2.2 REQUIRES ALL ROOFING TO BE
 APPLIED TO SOLID OR CLOSELY FITTED
 DECKING OR SHEATHING.
  
 2)- PROVISO: WINDOW BUCK ATTACHMENT:
 THE DESIGN PROFESSIONALS WOULD LIKE TO
 USE THE INFORMATION SUPPLIED BY THE
 PRODUCT APPROVAL FORWINDOWS AND DOORS.
 IF THE PRODUCT APPROVAL HAS A DISCLAIMER
 AS TO IT BE UP TO THE DESIGN
 PROFESSIONAL FOR THE ATTACHMENT DETAIL,
 THEY WILL BE REQUIRED TO PRODUCE THIS
 ADDITIONAL INFORMATION.
  
 3)- A NOTE WILL BE APPLIED TO THE DETAIL
 SBC 705.2.4.2 SEE A-2.1/ A2.2
  
 4)- PROVISO: SEE CITY POLICY FOR ALL
 GLAZED OPENINGS, WINDOWS WILL REQUIRE
 PRODUCT TESTING FOR SMALL & LARGE MISSLE
 IMPACT TESTING FOR GLAZED OPENINGS, AND
 COMPLY WITH LOW, MID & HIGH RISE STRUC-
 TURES IN ACCORDANCE WITH 1606.4 &
 1707.4.1 AMENDMENTS AND ALSO COMPLY WITH
 THE IMPLEMENTATION STANDARDS & POLICY
 OF WPB.
  
 5)- PROVISO: ROOFING WILL BE UNDER SEPER
 ATE PERMIT WITH ADITIONAL FEES. PRODUCT
 APPROVAL WILL BE REQUIRED AS PER SBC
 1503.3.2.
  
 6)- A.6DEPICTS THE ROOFING WITH WIRE
 LATH, THE BACKING OR SSHEATHING DOESN'T
 DESCRIBE THE MATERIAL?
  
 7)- S.5 THE TRUSS PLAN DOESN'T GIVE
 THE LOADS ATTACHED TO THE TRUSSES.
 ANCHORS SPECED DEPICT NAILS FOR METAL
 TRUSSES?
  
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-05-07 Cont ID  
Sent By jwitmer Date 2001-05-07 Time 18:02 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-05-07 00:00:00BUILDING PLAN CHECK
 PLAN REVIEW # 01040479
 605 EXECUTIVE CENTER DRIVE
 BUILDING: A (3 STORY)

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-29 Cont ID  
Sent By dpalmer Date 2001-10-29 Time 15:41 Rev Time 0.00
Received By dpalmer Date 2001-10-29 Time 15:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-05-18 Cont ID  
Sent By dpalmer Date 2001-05-18 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2001-05-18 Time 12:55 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-05-24 Cont ID  
Sent By mamini Date 2001-05-24 Time 08:14 Rev Time 1.00
Received By mamini Date 2001-05-24 Time 08:14 Sent To  
Notes
2001-05-24 00:00:00PASSED :
 1. SEE PERMIT NUMBER 01030517 FOR REVIEW
 COMMENTS.
 IF ANY QUESTION PLEASE CONTACT 561-659-
 8096 EXT. 8492

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2001-12-27 Cont ID  
Sent By mcarsill Date 2001-12-27 Time 09:28 Rev Time 0.00
Received By mcarsill Date 2001-12-27 Time 09:28 Sent To  
Notes
2001-12-27 00:00:00TRASH CHUTE ENSLOSURE NOT PROPER. IT
 APPEARS THAT NEAR THE ROOF TERMINATION
 POINT AN ATTEMPT HAS BEEN MADE TO
 DECREASE THE CODE REQUIREMENTS FOR THE
 TRASH CHUTE ENCLOSURE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-05-23 Cont ID  
Sent By mcarsill Date 2001-05-23 Time 16:24 Rev Time 0.00
Received By mcarsill Date 2001-05-23 Time 16:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-05-18 Cont ID  
Sent By mcarsill Date 2001-05-18 Time 13:09 Rev Time 0.00
Received By mcarsill Date 2001-05-18 Time 13:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-01 Cont ID  
Sent By mcarsill Date 2001-05-01 Time 15:47 Rev Time 0.00
Received By mcarsill Date 2001-05-01 Time 15:47 Sent To  
Notes
2001-05-01 00:00:001) ALL UNDERGROUND FIRE MAINS ARE TO BE
 LISTED FOR FIRE PROTECTION SERVICE AND
 COMPLY WITH NFPA 24, FIRE SERVICE MAINS
 AND THEIR APPURTENANCES.
 2) INGRESS AND EGRESS INTO THE COMPLEX
 SHALL BE A MINIMUM OF TWENTY FEET IN
 CLEAR WIDTH. BATTERY BACK-UP FEATURE
 SHALL BE PROVIDED FOR GATE-ARMS SHOULD
 LOSS OF POWER OCCUR. TRAFFIC CALMING
 HUMPS ARE NOT TO INTERFERE WITH FIRE
 RESCUE MOVEMENT INTO THE COMPLEX.
 3) BUILDING LETTERS A,B,C,AND D, ARE TO
 BE PLACED ON THE BUILDINGS SINCE IT
 APPEARS TO BE A SINGLE ADDRESS FOR THE
 APARTMENT COMPLEX.
 4) AT LEAST ONE STAIR IS TO BE
 PROVIDED AT EACH BUILDING DURING
 CONSTRUCTION. TEMPORARY STANDPIPES ARE
 REQUIRED IN ALL BUILDINGS UNDER
 CONSTRUCTION WHEN THEY ARE REQUIRED TO
 HAVE STANDPIPE SYSTEMS.
 5) HOW IS COMBUSTIBLE LINT REMOVED FROM
 THE DRYER CHASE. NO ACCESS PANELS HAVE
 BEEN PROVIDED.
 6) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATIONS OF THE FIRE
 SPRINKLER SYSTEMS. NO HYDRAULIC
 CALCULATIONS PROVIDED WITH SPRINKLER
 DRAWINGS. STANDPIPE SYSTEMS ARE REQUIRED
 IN ALL BUILDINGS THREE STORIES AND MORE
 THAN FIFTY FEET IN HEIGHT. ALL VERTICAL
 SHAFTS ARE TO BE FIRE SPRINKLER
 PROTECTED. PLEASE EXPLAIN RATIONALE FOR
 SINGLE FIRE DEPARTMENT CONNECTION SHOWN
 ON THE DRAWINGS.
 7) DOOR SWINGS IN STAIRWELLS ARE TO
 SWING IN THE DIRECTION OF EXIT TRAVEL.
 8) SMOKE DETECTORS WHEN INSTALLED ARE
 TO BE A MINIMUM OF THREE FEET FROM
 AIR CONDITIONER DIFFUSERS.
 9) TRASH CHUTES TO COMPLY WITH NFPA 82,
 STANDARD ON INCINERATORS, WASTE AND
 LINEN HANDLING SYSTEMS AND EQUIPMENT.
 10) PLEASE INDICATE PORTABLE FIRE
 EXTINGUISHER LOCATIONS.
 11)SIGNS ARE REQUIRED FOR ALL
 BUILDINGS FOUR OR MORE STORIES. SIGNS
 SHALL INDICATE FLOOR LEVEL, THE IDENTITY
 OF THE STAIR, THE TERMINUS OF THE STAIR,
 TOP AND BOTTOM.
 12) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE FIRE ALARM SYSTEM.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2002-04-23 Cont ID  
Sent By pkrauss Date 2002-04-23 Time 08:43 Rev Time 0.30
Received By pkrauss Date 2002-04-23 Time 08:01 Sent To  
Notes
2002-04-23 00:00:00MECH PERMIT 01071091 - DUCT REV

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2002-04-12 Cont ID  
Sent By pkrauss Date 2002-04-10 Time 14:28 Rev Time 0.45
Received By pkrauss Date 2002-04-10 Time 14:28 Sent To  
Notes
2002-04-10 00:00:00PROVISO:MECH PERMIT 01071091
  
 2 COPIES OF ORIGINAL LETTER FOR MONTHLY
 MAINTENANCE FOR THE CLEANING OF THE
 BOOSTER FAN.TWO NOTARIZED LETTERS TO
 FOLLOW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-03-12 Cont ID  
Sent By pkrauss Date 2002-03-12 Time 09:52 Rev Time 0.30
Received By pkrauss Date 2002-03-12 Time 09:52 Sent To  
Notes
2002-03-12 00:00:00SUBMITTAL LOUVERS FOR THE ELEVATOR SHAFT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2002-03-12 Cont ID  
Sent By pkrauss Date 2002-03-12 Time 08:22 Rev Time 1.00
Received By pkrauss Date 2002-03-11 Time 16:05 Sent To  
Notes
2002-03-12 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT 01071091
 CALCULATIONS FOR DRYER EXHAUST
  
 PROVIDE SPECIFIC MANUFACTURER SUBMITTAL
 DATA & PURCHASE ORDER FOR DRYERS.
 DRYERS TO BE INSTALLED AT THE TIME OF
 FINAL INSPECTION.DUCTWORK TO BE
 INSTALLED AS PER SPECIFIC MANUFACTURERS
 INSTRUCTIONS.RESIDENTIAL DRYER
 EXHAUST DUCTS WHICH ARE NOT DESIGNED
 FOR SPECIFIC DRYER SHALL COMPLY WITH
 1997 SMC 509.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-02-13 Cont ID  
Sent By pkrauss Date 2002-02-08 Time 08:59 Rev Time 0.35
Received By pkrauss Date 2002-02-08 Time 08:59 Sent To  
Notes
2002-02-08 00:00:00 
 MECHANICAL PERMIT 01071091
  
 LETTER FROM ENGINEER ON BATHROOM EXHAUST
 CALCULATIONS APPROVED.
  
 PLANS SUBMITTED ARE DENIED. DRYER
 EXHAUST TERMINATING AT A RATED WALL
 WHICH IS AN EGRESS CORRIDOR.FIRE
 DAMPERS ARE NOT PERMITTED IN DRYER
 EXHAUST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.
 `

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-05-24 Cont ID  
Sent By pkrauss Date 2001-05-24 Time 07:46 Rev Time 0.20
Received By pkrauss Date 2001-05-24 Time 07:46 Sent To  
Notes
2001-05-24 00:00:00NOTES ON PERMIT 01040480.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-05-10 Cont ID  
Sent By pkrauss Date 2001-05-10 Time 11:15 Rev Time 3.00
Received By pkrauss Date 2001-05-10 Time 11:15 Sent To  
Notes
2001-05-10 00:00:00PERMIT 01040479605 EXEC CTR DR.
 3 STORY DWG A4.1 REFLECTS 5 STORY.
 REVIEW DONE UNDER PERMIT 01040480.

Review Stop P PLUMBING
Rev No 7 Status P Date 2003-01-22 Cont ID  
Sent By kstevens Date 2003-01-22 Time 09:02 Rev Time 0.10
Received By kstevens Date 2003-01-22 Time 09:02 Sent To  
Notes
2003-01-22 00:00:00SUBMITTAL BOOSTER PUMP DOMESTIC

Review Stop P PLUMBING
Rev No 6 Status P Date 2002-09-26 Cont ID  
Sent By kstevens Date 2002-09-26 Time 11:18 Rev Time 0.00
Received By kstevens Date 2002-09-26 Time 11:18 Sent To  
Notes
2002-09-26 00:00:00REVISION OK - ADDED 2 6" SCUPPER LINES

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-11-29 Cont ID  
Sent By kstevens Date 2001-11-29 Time 15:21 Rev Time 0.50
Received By kstevens Date 2001-11-29 Time 15:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-10-19 Cont ID  
Sent By kstevens Date 2001-10-19 Time 10:49 Rev Time 0.75
Received By kstevens Date 2001-10-19 Time 10:49 Sent To  
Notes
2001-10-19 00:00:00DENIED
 REFERENCE: SPC-94 - FHA-AMEND-98 DESIGN
 MANUAL.
 1) SHEET A1.0 CODE ANALYSIS/BLDG DATA.
 FHA-98 D. MANUAL - STILL REQUIRED TO
 SPECIFY "A" OR "B", NOT A AND B AS STAT-
 ED.
 2) SHEEET P1 WATER RISER DIAGRAMS. AIR
 CHAMBERS SHALL COMPLY WITH SPC-94 SEC.
 607.8.3 ACCESSIBLE & RECHARGEABLE. IF
 WATER HAMMER ARRESTORS ARE USED THEY
 WILL BE SIZED AND LOCATED PER MANUFACT-
 URE'S INSTALLATION INSTRUCTIONS AND PER
 WH-PDI 201.
 3) PAGE P-1 WATER RISER DIAGRAM TYPICAL.
 MAXIMUM FIXTURES ON 1/2" COLD IS 2 FIX-
 TURES. MODEL COUNTYWIDE AMENDMENTS TO
 SPC-94 SEC 607.7
 4) PAGE P-2, P/T #1 ON FLOOR PLAN SHOWS
 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS
 A SINGLE RISER. TWWO RISERS ARE REQUIRED
 SPC-94 SEC 507.8.2 & 507.8.4.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-09-28 Cont ID  
Sent By kstevens Date 2001-09-28 Time 13:13 Rev Time 2.50
Received By kstevens Date 2001-09-28 Time 13:13 Sent To  
Notes
2001-09-28 00:00:00DENIED
 REFERENCE: SPC-94 - FHA-98
  
 1) SHEET A1.0 CODE ANALYSIS/BLDG DATA.
 FHA-REVISED 1998 DESIGN MANUAL ADDRESS
 REQUIREMENTS 1 THRU 7 - SPECIFY "A" OR
 "B" OPTION.
 2) SHEET A8.1 DETAIL MENS ROOM URNAL TO
 BE 17" AFF TO LIP. FACBC-98 4.18.2
 3) SHEET A8.1 KITCHENETTE SINK TO BE
 34"TO COUNTER TOP. FACBC-98 4.24
 4) SHEET P-1 WATER RISER DIAGRAMS. AIR
 CHAMBERS SHALL COMPLY WITH SPC-94 SEC
 607.8.3 ACCESSIBLE & RECHARGEABLE. IF
 WATER HAMMER ARRESTORS ARE USED THEY
 WILL BE SIZED AND LOCATED PER MANUFACT-
 URES INSTALLATION INSTRUCTIONS AND PER
 WH-PDI 201.
 5) PAGE P-1 WATER RISER DIAGRAM TYPICAL.
 MAXIMUM FIXTURES ON 1/2" COLD IS 2 FIX-
 TURES. MODEL COUNTRWIDE AMENDMENTS TO
 SPC-94 SEC 607.7
 6) PAGE P-2, P/T #1 ON FLOOR PLAN SHOWS
 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS
 A SINGLE RISER. TWO RISERS ARE REQUIRED.
 SPC-94 SEC 507.8.2 & 507.8.4
 7) PAGE A8.1 BACKING AT TUB TO BE 1'5"
 NOT 1'2" AS SHOWN. FHA-98 REQUIREMENT 6.
 PLEASE SHOW ALL BACKING WITH CORRECT
 DISTANCE OFF FLOOR WITH CORRECT LENGTH
 AND WIDTH SHOWN.
  
 REVIEW KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-09-22 Cont ID  
Sent By pschmitz Date 2001-09-22 Time 10:01 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-09-22 00:00:00REVISION,PLUMBING FOUNDATION, ONLY. PES

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-17 Cont ID  
Sent By kstevens Date 2001-05-16 Time 18:28 Rev Time 1.50
Received By kstevens Date 2001-05-17 Time 09:11 Sent To  
Notes
2001-05-16 00:00:00REVIEW NOTES: PASSED...PROVISO...
  
 1) GENERAL NOTES #15 COPIES OF ALL DOC-
 UMENTS TO BE FILED WITH THE DEPARTMENT
 OF CONSTRUCTION SERVICES. CHANGE "L" TO
 CITY OF WEST PALM BEACH. GNI 1 OF 1.
  
 2) TYPICAL WATER RISER DIAGRAM - MAXIMUM
 FIXTURES ON 1/2" COLD IS 2 FIXTURES.
 MODEL COUNTYWIDE AMENDMENTS TO SPC-94
 607.7
  
 3) AIR CHAMBERS TO COMPLY WITH SPC-94
 607.8.2 & 607.8.3
  
 4) PAGE P-4, P/T #1 ON FLOOR PLAN SHOWS
 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS
 A SINGLE RISER. TWO RISERS REQUIRED.
  
 5) FAIR HOUSING ACT 1996 AMENDED 1998
 REQUIREMENT 7B REQUIRES THAT SPEC. A OR
 B BE SHOWN ON PLAN.
  
 6) PAGE A8.1 BACKING AT TUB TO BE 1'-5"
 NOT 1'-2" AS SHOWN ON PLAN. FHA-96
 AMEND.-98 REQUIREMENT 6.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-22 Cont ID  
Sent By sgraham Date 2001-05-04 Time 14:04 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-05-22 00:00:00APPROVED ANGELLA VANN
2001-05-04 00:00:00NEED MINOR AMENDENT