| Plan Review Stops For Permit 01040479 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2002-03-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-03-27 |
Time |
09:55 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2002-03-27 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2002-03-27 00:00:00 | SUBMITTAL- NO. S-73 | | | REF: A/S-1 ON SK-1 ALTERNATE | | | CONNECTION DETAIL | | | | | | THE CITY HAS REVIEWED THE INFORMATION | | | PROVIDED FOR THE ALTERNATE CONNECTION | | | DETAIL. WE CAN NOT ACCEPT THIS INFORMA- | | | TION AS IS. THE ENGINEER OF RECORD HAS | | | THE OPTIONS OF : | | | 1)- A PEER REVIEW HAS BEEN ACCOMPLISHED | | | BY MOODY ENGINEERING, THE ENGINEER OF RE | | | CORD HAS SIGNED BUT NOT SEALED THE | | | LETTER HEAD PROVIDED BY MOODY. MR WALSH | | | MAY SEAL HIS SIGNATURE OR | | | 2)- MR WALSH AS ENGINEER OF RECORD MAY | | | ON HIS OWN LETTER HEAD INDICATE THAT | | | HE HAS REVIEWED THE INFORMATION, IS IN | | | AGREEMENT WITH THE FINDINGS AND SIGN | | | AND SEAL HIS OWN LETTER HEAD AND ATTACH | | | IT TO THE PACKAGE OR | | | 3)- MR WALSH MAY DO A FIELD INSPECTION | | | CHECKING THE CONNECTIONS WITH A TORQUE | | | WRENCH AND CERTIFYING THE INSTALLATION | | | BY AFFIDAVIT, SIGNED & SEALED. | | | THE CITY WILL ACCEPT ANY OF THE THREE | | | OPTIONS LISTED ABOVE. | | | PLAN REVIEW BUILDING | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2001-12-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-12-26 |
Time |
10:13 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
2001-12-26 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2001-12-26 00:00:00 | REFUSE CHUTE SHOP DRAW | | | PERMIT: | | | BLDG A: 01040479 | | | BLDG B: 01040480 | | | BLDG C: 01040481 | | | BLDG D: 01040482 | | | | | | STANDARD BUILDING CODE 705.2.4.2. | | | REFUSE CHUTE ENCLOSURES: | | | ALL OPENINGS INTO SHAFT ENCLOSURES SHALL | | | BE PROTECTED IN ACCORDANCE WITH | | | TABLE 705.1.2 REUSE CHUTE REQUIRE A | | | 2 HR RATING, SHOP DRAWINGS NOTE #5 INDIC | | | ATES THE CHUTE THROUGH THE ROOF LINE | | | WITH NO SHAFT ENCLOSURE THROUGH THE | | | TRUSSES. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-29 |
Time |
08:59 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2001-10-29 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | REVISIONS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-10-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-01 |
Time |
12:29 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2001-10-01 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2001-10-01 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01040479 | | | BLDG "A" | | | 605 EXECUTIVE CENTER DR | | | | | | REVISIONS : CITY RECEIVED DATE 9/20/01 | | | 1)- SHEET A2.0 MISING RED LINE NOTE FOR | | | TRASH ROOM | | | | | | 2)- SHEET A2.3 DETAIL #8 SBC 1608.2.2.3 | | | SHOW COMPLIANCE WITH GAURD RAIL TO | | | RESIST 200 LBS CONCENTRATED HORIZONTAL | | | LOADS APPLIED ON A 1 FT SQ AREA. AT ANY | | | POINT IN THE SYSTEM INCLUDING INTERMED- | | | IATE RAILS OR OTHER ELEMENTS SERVING | | | THIS PURPOSE. | | | | | | 3)- SHEET A.6 MISSING RED LINE CORREC- | | | TIONS, | | | A)- ROOFING COMMENTS | | | B)- ROOF A/C AIR HANDLERS & SUP- | | | PORTS MIN. 18" CLEARENCE IS | | | MISSING. | | | C)- A/C CLOSET - INCREASE THE DOOR | | | HEIGTH FOR FULL ACCESS. | | | | | | 4)- SHEET #7 NOTE MISSING DETAIL #2, | | | FLOOR DRAINS, INACTUALLITY, OVERFLOW | | | SCUPPERS (SBC 1517.6.4.3) NOT LESS THAN | | | 2" ABOVE THE ROOF DECK NOR 4" MAXIMUM. | | | | | | 5)- SHEET A8.1 IS MISING RED LINE CORREC | | | TIONS TO THE FAIR HOUSING ACT. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-08-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-12 |
Time |
10:21 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2001-08-12 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2001-08-12 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01001040479 | | | 605 EXECUTIVE CENTER DRIVE | | | | | | REVISION: #1 | | | | | | 1)- SBC 104.2.2 ADDITIONAL INFORMATION | | | REQUIRED, THE PLANS SUBMITTED FROM | | | SSTEVEN WALSH DATED 7/26/01 DO NOT INDIC | | | ATE THE SCALE THEY ARE DRAWN BY NOR DO | | | THEY GIVE ANY DIMENSIONS IN WIDTH, | | | WIDTH OR IN HEIGHT BETWEEN FLOORS. | | | | | | 2)- SHEET S-2 INDICATES A FLOOR OPENING | | | THAT ISN'T INDICATED ON THE STRUCTURAL | | | DRAWINGS, PLEASE INDICATE THE USAGE, IF | | | IT IS FOR VENTING, PLEASE GIVE THE U.L. | | | RATING FOR THE CHASE. | | | | | | 3)- SHEET SEC-AD TYPICAL COLUMN DETAIL: | | | PLEASE GIVE THE ASSEMBLY RATING FOR THIS | | | DETAIL, THANK YOU. | | | | | | 4)- DISCREPANCY: THE SOILS REPORT FROM | | | ARDAMAN & ASSOCIATES 8.3 FOUNDATIONS: | | | " ALL CONTINUOUS FOUNDATIONS SHOULD BE | | | AT LEAST 30" WIDE, AND ALL INDIVIDUAL | | | COLUMN FOOTINGS SHOULD HAVE A MINIMUM | | | WIDTH OF 30 INCHES". HAS THE NEW DESIGN | | | FROM WALSH BEEN REVIEWED BY THE SOILS | | | ENGINEER, A LETTER FROM ARDAMAN WILL BE | | | REQUIRED ADDRESSING THE NEW FOUNDATION | | | DESIGN AND THE NEW CONFIGURATION OF | | | FOOTING & FOUNDATIONS, (SIGNED/SEALED). | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-07-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-18 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
sjohnson |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-20 00:00:00 | APPROVED PER JIM WITMER | | 2001-05-18 00:00:00 | BUILDING PLAN CHECK | | | PLAN REVIEW# 01040479 | | | 605 EXECUTIVE CENTER DR | | | BUILDING A ( 3 STORY) | | | | | | 1)- SHEET A.6 DETAIL 2 DEPICTS THE ROOF- | | | ING TO BE ATTACHED TO PURLINS, AMENDMENT | | | 11503.1.2.2 REQUIRES ALL ROOFING TO BE | | | APPLIED TO SOLID OR CLOSELY FITTED | | | DECKING OR SHEATHING. | | | | | | 2)- PROVISO: WINDOW BUCK ATTACHMENT: | | | THE DESIGN PROFESSIONALS WOULD LIKE TO | | | USE THE INFORMATION SUPPLIED BY THE | | | PRODUCT APPROVAL FORWINDOWS AND DOORS. | | | IF THE PRODUCT APPROVAL HAS A DISCLAIMER | | | AS TO IT BE UP TO THE DESIGN | | | PROFESSIONAL FOR THE ATTACHMENT DETAIL, | | | THEY WILL BE REQUIRED TO PRODUCE THIS | | | ADDITIONAL INFORMATION. | | | | | | 3)- A NOTE WILL BE APPLIED TO THE DETAIL | | | SBC 705.2.4.2 SEE A-2.1/ A2.2 | | | | | | 4)- PROVISO: SEE CITY POLICY FOR ALL | | | GLAZED OPENINGS, WINDOWS WILL REQUIRE | | | PRODUCT TESTING FOR SMALL & LARGE MISSLE | | | IMPACT TESTING FOR GLAZED OPENINGS, AND | | | COMPLY WITH LOW, MID & HIGH RISE STRUC- | | | TURES IN ACCORDANCE WITH 1606.4 & | | | 1707.4.1 AMENDMENTS AND ALSO COMPLY WITH | | | THE IMPLEMENTATION STANDARDS & POLICY | | | OF WPB. | | | | | | 5)- PROVISO: ROOFING WILL BE UNDER SEPER | | | ATE PERMIT WITH ADITIONAL FEES. PRODUCT | | | APPROVAL WILL BE REQUIRED AS PER SBC | | | 1503.3.2. | | | | | | 6)- A.6DEPICTS THE ROOFING WITH WIRE | | | LATH, THE BACKING OR SSHEATHING DOESN'T | | | DESCRIBE THE MATERIAL? | | | | | | 7)- S.5 THE TRUSS PLAN DOESN'T GIVE | | | THE LOADS ATTACHED TO THE TRUSSES. | | | ANCHORS SPECED DEPICT NAILS FOR METAL | | | TRUSSES? | | | | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-05-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-07 |
Time |
18:02 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-07 00:00:00 | BUILDING PLAN CHECK | | | PLAN REVIEW # 01040479 | | | 605 EXECUTIVE CENTER DRIVE | | | BUILDING: A (3 STORY) |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-29 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-29 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-18 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-18 |
Time |
12:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2001-05-24 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-05-24 |
Time |
08:14 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2001-05-24 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | PASSED : | | | 1. SEE PERMIT NUMBER 01030517 FOR REVIEW | | | COMMENTS. | | | IF ANY QUESTION PLEASE CONTACT 561-659- | | | 8096 EXT. 8492 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2001-12-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-27 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-27 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2001-12-27 00:00:00 | TRASH CHUTE ENSLOSURE NOT PROPER. IT | | | APPEARS THAT NEAR THE ROOF TERMINATION | | | POINT AN ATTEMPT HAS BEEN MADE TO | | | DECREASE THE CODE REQUIREMENTS FOR THE | | | TRASH CHUTE ENCLOSURE. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-05-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-23 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-23 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-05-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-18 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-18 |
Time |
13:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-05-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-01 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-01 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2001-05-01 00:00:00 | 1) ALL UNDERGROUND FIRE MAINS ARE TO BE | | | LISTED FOR FIRE PROTECTION SERVICE AND | | | COMPLY WITH NFPA 24, FIRE SERVICE MAINS | | | AND THEIR APPURTENANCES. | | | 2) INGRESS AND EGRESS INTO THE COMPLEX | | | SHALL BE A MINIMUM OF TWENTY FEET IN | | | CLEAR WIDTH. BATTERY BACK-UP FEATURE | | | SHALL BE PROVIDED FOR GATE-ARMS SHOULD | | | LOSS OF POWER OCCUR. TRAFFIC CALMING | | | HUMPS ARE NOT TO INTERFERE WITH FIRE | | | RESCUE MOVEMENT INTO THE COMPLEX. | | | 3) BUILDING LETTERS A,B,C,AND D, ARE TO | | | BE PLACED ON THE BUILDINGS SINCE IT | | | APPEARS TO BE A SINGLE ADDRESS FOR THE | | | APARTMENT COMPLEX. | | | 4) AT LEAST ONE STAIR IS TO BE | | | PROVIDED AT EACH BUILDING DURING | | | CONSTRUCTION. TEMPORARY STANDPIPES ARE | | | REQUIRED IN ALL BUILDINGS UNDER | | | CONSTRUCTION WHEN THEY ARE REQUIRED TO | | | HAVE STANDPIPE SYSTEMS. | | | 5) HOW IS COMBUSTIBLE LINT REMOVED FROM | | | THE DRYER CHASE. NO ACCESS PANELS HAVE | | | BEEN PROVIDED. | | | 6) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE INSTALLATIONS OF THE FIRE | | | SPRINKLER SYSTEMS. NO HYDRAULIC | | | CALCULATIONS PROVIDED WITH SPRINKLER | | | DRAWINGS. STANDPIPE SYSTEMS ARE REQUIRED | | | IN ALL BUILDINGS THREE STORIES AND MORE | | | THAN FIFTY FEET IN HEIGHT. ALL VERTICAL | | | SHAFTS ARE TO BE FIRE SPRINKLER | | | PROTECTED. PLEASE EXPLAIN RATIONALE FOR | | | SINGLE FIRE DEPARTMENT CONNECTION SHOWN | | | ON THE DRAWINGS. | | | 7) DOOR SWINGS IN STAIRWELLS ARE TO | | | SWING IN THE DIRECTION OF EXIT TRAVEL. | | | 8) SMOKE DETECTORS WHEN INSTALLED ARE | | | TO BE A MINIMUM OF THREE FEET FROM | | | AIR CONDITIONER DIFFUSERS. | | | 9) TRASH CHUTES TO COMPLY WITH NFPA 82, | | | STANDARD ON INCINERATORS, WASTE AND | | | LINEN HANDLING SYSTEMS AND EQUIPMENT. | | | 10) PLEASE INDICATE PORTABLE FIRE | | | EXTINGUISHER LOCATIONS. | | | 11)SIGNS ARE REQUIRED FOR ALL | | | BUILDINGS FOUR OR MORE STORIES. SIGNS | | | SHALL INDICATE FLOOR LEVEL, THE IDENTITY | | | OF THE STAIR, THE TERMINUS OF THE STAIR, | | | TOP AND BOTTOM. | | | 12) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE FIRE ALARM SYSTEM. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2002-04-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-23 |
Time |
08:43 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-04-23 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2002-04-23 00:00:00 | MECH PERMIT 01071091 - DUCT REV |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2002-04-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-10 |
Time |
14:28 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-04-10 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2002-04-10 00:00:00 | PROVISO:MECH PERMIT 01071091 | | | | | | 2 COPIES OF ORIGINAL LETTER FOR MONTHLY | | | MAINTENANCE FOR THE CLEANING OF THE | | | BOOSTER FAN.TWO NOTARIZED LETTERS TO | | | FOLLOW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2002-03-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-12 |
Time |
09:52 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-03-12 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2002-03-12 00:00:00 | SUBMITTAL LOUVERS FOR THE ELEVATOR SHAFT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2002-03-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-12 |
Time |
08:22 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-03-11 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2002-03-12 00:00:00 | *******************DENIED*************** | | | | | | MECHANICAL PERMIT 01071091 | | | CALCULATIONS FOR DRYER EXHAUST | | | | | | PROVIDE SPECIFIC MANUFACTURER SUBMITTAL | | | DATA & PURCHASE ORDER FOR DRYERS. | | | DRYERS TO BE INSTALLED AT THE TIME OF | | | FINAL INSPECTION.DUCTWORK TO BE | | | INSTALLED AS PER SPECIFIC MANUFACTURERS | | | INSTRUCTIONS.RESIDENTIAL DRYER | | | EXHAUST DUCTS WHICH ARE NOT DESIGNED | | | FOR SPECIFIC DRYER SHALL COMPLY WITH | | | 1997 SMC 509.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2002-02-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-08 |
Time |
08:59 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-02-08 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2002-02-08 00:00:00 | | | | MECHANICAL PERMIT 01071091 | | | | | | LETTER FROM ENGINEER ON BATHROOM EXHAUST | | | CALCULATIONS APPROVED. | | | | | | PLANS SUBMITTED ARE DENIED. DRYER | | | EXHAUST TERMINATING AT A RATED WALL | | | WHICH IS AN EGRESS CORRIDOR.FIRE | | | DAMPERS ARE NOT PERMITTED IN DRYER | | | EXHAUST. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. | | | ` |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-05-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-24 |
Time |
07:46 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2001-05-24 |
Time |
07:46 |
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | NOTES ON PERMIT 01040480. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-05-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-10 |
Time |
11:15 |
Rev Time |
3.00 |
| Received By |
pkrauss |
Date |
2001-05-10 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2001-05-10 00:00:00 | PERMIT 01040479605 EXEC CTR DR. | | | 3 STORY DWG A4.1 REFLECTS 5 STORY. | | | REVIEW DONE UNDER PERMIT 01040480. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2003-01-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-22 |
Time |
09:02 |
Rev Time |
0.10 |
| Received By |
kstevens |
Date |
2003-01-22 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2003-01-22 00:00:00 | SUBMITTAL BOOSTER PUMP DOMESTIC |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2002-09-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-09-26 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-09-26 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2002-09-26 00:00:00 | REVISION OK - ADDED 2 6" SCUPPER LINES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2001-11-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-29 |
Time |
15:21 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-11-29 |
Time |
15:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2001-10-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-19 |
Time |
10:49 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2001-10-19 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2001-10-19 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FHA-AMEND-98 DESIGN | | | MANUAL. | | | 1) SHEET A1.0 CODE ANALYSIS/BLDG DATA. | | | FHA-98 D. MANUAL - STILL REQUIRED TO | | | SPECIFY "A" OR "B", NOT A AND B AS STAT- | | | ED. | | | 2) SHEEET P1 WATER RISER DIAGRAMS. AIR | | | CHAMBERS SHALL COMPLY WITH SPC-94 SEC. | | | 607.8.3 ACCESSIBLE & RECHARGEABLE. IF | | | WATER HAMMER ARRESTORS ARE USED THEY | | | WILL BE SIZED AND LOCATED PER MANUFACT- | | | URE'S INSTALLATION INSTRUCTIONS AND PER | | | WH-PDI 201. | | | 3) PAGE P-1 WATER RISER DIAGRAM TYPICAL. | | | MAXIMUM FIXTURES ON 1/2" COLD IS 2 FIX- | | | TURES. MODEL COUNTYWIDE AMENDMENTS TO | | | SPC-94 SEC 607.7 | | | 4) PAGE P-2, P/T #1 ON FLOOR PLAN SHOWS | | | 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS | | | A SINGLE RISER. TWWO RISERS ARE REQUIRED | | | SPC-94 SEC 507.8.2 & 507.8.4. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-09-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-28 |
Time |
13:13 |
Rev Time |
2.50 |
| Received By |
kstevens |
Date |
2001-09-28 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2001-09-28 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FHA-98 | | | | | | 1) SHEET A1.0 CODE ANALYSIS/BLDG DATA. | | | FHA-REVISED 1998 DESIGN MANUAL ADDRESS | | | REQUIREMENTS 1 THRU 7 - SPECIFY "A" OR | | | "B" OPTION. | | | 2) SHEET A8.1 DETAIL MENS ROOM URNAL TO | | | BE 17" AFF TO LIP. FACBC-98 4.18.2 | | | 3) SHEET A8.1 KITCHENETTE SINK TO BE | | | 34"TO COUNTER TOP. FACBC-98 4.24 | | | 4) SHEET P-1 WATER RISER DIAGRAMS. AIR | | | CHAMBERS SHALL COMPLY WITH SPC-94 SEC | | | 607.8.3 ACCESSIBLE & RECHARGEABLE. IF | | | WATER HAMMER ARRESTORS ARE USED THEY | | | WILL BE SIZED AND LOCATED PER MANUFACT- | | | URES INSTALLATION INSTRUCTIONS AND PER | | | WH-PDI 201. | | | 5) PAGE P-1 WATER RISER DIAGRAM TYPICAL. | | | MAXIMUM FIXTURES ON 1/2" COLD IS 2 FIX- | | | TURES. MODEL COUNTRWIDE AMENDMENTS TO | | | SPC-94 SEC 607.7 | | | 6) PAGE P-2, P/T #1 ON FLOOR PLAN SHOWS | | | 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS | | | A SINGLE RISER. TWO RISERS ARE REQUIRED. | | | SPC-94 SEC 507.8.2 & 507.8.4 | | | 7) PAGE A8.1 BACKING AT TUB TO BE 1'5" | | | NOT 1'2" AS SHOWN. FHA-98 REQUIREMENT 6. | | | PLEASE SHOW ALL BACKING WITH CORRECT | | | DISTANCE OFF FLOOR WITH CORRECT LENGTH | | | AND WIDTH SHOWN. | | | | | | REVIEW KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-09-22 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-09-22 |
Time |
10:01 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-22 00:00:00 | REVISION,PLUMBING FOUNDATION, ONLY. PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-05-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-05-16 |
Time |
18:28 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2001-05-17 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2001-05-16 00:00:00 | REVIEW NOTES: PASSED...PROVISO... | | | | | | 1) GENERAL NOTES #15 COPIES OF ALL DOC- | | | UMENTS TO BE FILED WITH THE DEPARTMENT | | | OF CONSTRUCTION SERVICES. CHANGE "L" TO | | | CITY OF WEST PALM BEACH. GNI 1 OF 1. | | | | | | 2) TYPICAL WATER RISER DIAGRAM - MAXIMUM | | | FIXTURES ON 1/2" COLD IS 2 FIXTURES. | | | MODEL COUNTYWIDE AMENDMENTS TO SPC-94 | | | 607.7 | | | | | | 3) AIR CHAMBERS TO COMPLY WITH SPC-94 | | | 607.8.2 & 607.8.3 | | | | | | 4) PAGE P-4, P/T #1 ON FLOOR PLAN SHOWS | | | 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS | | | A SINGLE RISER. TWO RISERS REQUIRED. | | | | | | 5) FAIR HOUSING ACT 1996 AMENDED 1998 | | | REQUIREMENT 7B REQUIRES THAT SPEC. A OR | | | B BE SHOWN ON PLAN. | | | | | | 6) PAGE A8.1 BACKING AT TUB TO BE 1'-5" | | | NOT 1'-2" AS SHOWN ON PLAN. FHA-96 | | | AMEND.-98 REQUIREMENT 6. | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-05-22 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-05-04 |
Time |
14:04 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-22 00:00:00 | APPROVED ANGELLA VANN | | 2001-05-04 00:00:00 | NEED MINOR AMENDENT |
|
|