| Plan Review Stops For Permit 01040464 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-07-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-03 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2001-07-03 |
Time |
08:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-04-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-24 |
Time |
08:34 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-04-24 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2001-04-24 00:00:00 | ********************DENIED************** | | | | | | | | | PLEASE PROVIDE O.A. CALCULATION AS PER | | | ASHRAE 62-89. | | | | | | PLEASE CLARIFY "REMOTE STATUS INDICATOR" | | | FOR DUCT SMOKE DETECTOR.WILL THIS BE | | | TIED TO A CONSTANTLY ATTENDED LOCATION? | | | (NFPA 90A 4-4.4.2) | | | | | | | | | | | | NOTE:CONDENSER WATER PIPING WITH TYPE | | | "K" COPPER SHALL BE BRAZED AS | | | PER 1997 SMC TABLE 1205. |
|
|
|