Plan Review Details - Permit 01040436
Plan Review Stops For Permit 01040436
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-06-24 Cont ID  
Sent By dpalmer Date 2001-06-24 Time 14:17 Rev Time 0.00
Received By dpalmer Date 2001-06-24 Time 14:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-04-25 Cont ID  
Sent By dpalmer Date 2001-04-25 Time 14:13 Rev Time 0.00
Received By dpalmer Date 2001-04-25 Time 14:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-04-25 Cont ID  
Sent By pkrauss Date 2001-04-25 Time 14:04 Rev Time 0.30
Received By pkrauss Date 2001-04-25 Time 14:04 Sent To  
Notes
2001-04-25 00:00:00MECH PERMIT 01040441

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-25 Cont ID  
Sent By kstevens Date 2001-06-25 Time 09:55 Rev Time 0.25
Received By kstevens Date 2001-06-25 Time 09:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-04-23 Cont ID  
Sent By kstevens Date 2001-04-23 Time 18:44 Rev Time 0.33
Received By kstevens Date 2001-04-23 Time 18:43 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2001-09-04 Cont ID  
Sent By jgomez Date 2001-09-04 Time 11:14 Rev Time 2.00
Received By jgomez Date 2001-09-04 Time 11:14 Sent To  
Notes
2001-09-04 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOOR WITH SIDELITE ASSEMBLY AS
 SHOWN ON REVISED PLANS.
 B)FRENCH DOOR BY CABANA.
 C)SLIDING GLASS DOORS WITH TRANSOM ABOVE
 ASSEMBLY AS SHOWN ON PLANS.
 D)BUTT GLAZING SYSTEM AS SHOWN ON PLANS.
  
 2-REVISE ANCHOR SCHEDULE AS REQUIRED.
 SEE COMMENTS ON ANCHOR SCHEDULE
 SPACING ACCORDING TO THE PANEL SPAN.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-06-27 Cont ID  
Sent By jgomez Date 2001-06-27 Time 11:56 Rev Time 2.50
Received By jgomez Date 2001-06-27 Time 11:56 Sent To  
Notes
2001-06-27 00:00:00SECOND CHECKLIST:
 1-MISSING ORIGINAL PERMIT APPLICATION.
 2-ENTRY DOOR TO HAVE 32" MIN. CLEAR
 OPENING. TABLE 1004 SBC 1997.
 REAR DOOR BY CABANA IS NOT THE MAIN
 EGRESS.
 3-SPECIFY SAFETY GLASS WHERE REQUIRED BY
 SEC 2405.2 SBC/97. NEW EGRESS WINDOW
 4-ARCHITECT TO CLEARLY SPECIFY ON DWGS
 THAT GLASS BLOCK @ ZERO LOT LINE NEEDS
 TO BE ONE HOUR FIRE RATED. TABLE 600.
 5-ARCHITECT TO UPDATE SHEET C-1. SEE
 COMMENTS.
 6-REVISE STORM PANEL INSTALLATION SCHED:
 A)SEE MASONRY OPENINGS SPECIFIED BY THE
 ARCHITECT AND REVISE ACCORDINGLY.
 B)INSTALLATION SCHEDULE ANCHOR SPACING
 DOESN'T MATCH THE SPACING SCHEDULE AS
 SHOWN ON SHEETS 5 & 6 OF APPROVED DWGS
 C)CLEARLY WRITE THE ANCHOR SPACING
 ACCORDING TO THE TYPE OF STRUCTURE TO
 BE ATTACHED TO: CONC. OR CONC. BLOCK.
 7-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS (DRAWINGS NOT LEGIBLE).
 B)ARCHITECT TO REVISE DWGS IF TRANSOM
 ABOVE CABANA DOOR IS DELETED. PROVIDE
 PRODUCT APPROVAL FOR DOOR ONLY.
 C)SLIDING GLASS DOORS W/ TRANSOM ABOVE
 SINGLE ASSEMBLY. MULLION PRODUCT
 APPROVAL IS FOR WINDOWS ONLY.
 D)MISSING DWGS FOR 16'-0" GARAGE DOOR.
 E)DRAWINGS FOR GLASS BLOCK PRODUCT
 APPROVAL ARE NOT LEGIBLE.
 -PROVIDE DETAILS AND SPECS FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY.
 F)FIXED WINDOWS WITH SIZES AS SHOWN ON
 ARCHITECT'S EXTERIOR ELEVATIONS.
 G)BUTT GLAZING AND FIXED WINDOW BY
 BREAKFAST AREA.
 -NOTE: SITE SPECIFIC ENGINEERING USE
 CITY SAMPLE FORM, ATTACHED, AND NEEDS
 TO BE SIGNED, SEALED BY THE MANUFACT'R
 ENGINEER AND BY THE PROFESSIONAL OF
 RECORD (REMAINDER: INCLUDE ALL THE
 INFORMATION REQUIRED BY CHAPTER 471 &
 481 OF FLORIDA STATUTES WHEN
 PROFESSIONALS ARE SUBMITTING INFO. FOR
 PUBLIC RECORDS).
 H)PGT ENGINEER, ROBERT L. CLARK PE, TO
 SIGN, SEAL AND DATE LETTER AS REQUIRED
 BY CHAPTER 471 OF FLORIDA STATUTES.
 8-PROVIDE DETAIL AND SPECIFICATIONS FOR
 2X STRUCTURAL BUCK AS REQUIRED FOR
 EXTERIOR DOORS. SEE PRODUCT APPROVAL.
  
  
  
 NOTE:
 PLEASE RETURN REVIEWED SET OF DRAWINGS
 AFTER CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS IN ORDER TO EXPEDITE THE REVIEW
 PROCESS. THIS WAS NOT DONE FOR THIS SUB-
 MITTAL, THEREFORE, I HAD TO RE-REVIEW
 THE ALL SET AGAIN.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-05-10 Cont ID  
Sent By jgomez Date 2001-05-10 Time 09:07 Rev Time 0.50
Received By jgomez Date 2001-05-10 Time 09:07 Sent To  
Notes
2001-05-10 00:00:00RESPONSE TO ARCHITECT REGARDING THE NEED
 FOR SECONDARY EGRESS FROM THE LIBRARY
 ROOM:
  
 THIS IS A LIFE SAFETY ISSUE AND EVEN
 THOUGH THE ROOM IS CALLED "LIBRARY" WE
 ARE CONCERNED ABOUT THE USAGE OF THIS
 ROOM AS A BEDROOM AS WELL.
 BEDROOM,ACCORDING TO WEBSTER'S NINTH NEW
 COLLEGIATE DICTIONARY (SECTION 201.3 OF
 SBC 1997) IS "A ROOM FURNISHED WITH A
 BED AND INTENDED PRIMARILY FOR SLEEPING"
  
 THIS ROOM MAY BE VERY WELL FURNISHED W/
 A BED AND BECOME A "BEDROOM".
  
 IN ADDITION, CHAPTER 22 OF LIFE SAFETY
 CODE (1985) REGARDING ONE AND TWO FAMILY
 DWELLINGS REQUIRES THAT "EVERY BEDROOM
 AND LIVING AREA SHALL HAVE AT LEAST TWO
 MEANS OF ESCAPE OR ALTERNATE PROTECTION"
 (SEC 22-2.1.1)
  
 THIS ISSUE WAS ALSO BROUGHT TO THE
 ATTENTION OF THE BUILDING OFFICIAL AND
 HIS INTERPRETATION IS THAT THE ROOM
 NEEDS TO PROVIDE A SECONDARY MEANS OF
 EGRESS FOR LIFE SAFETY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT 659-8096
 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-05-04 Cont ID  
Sent By jgomez Date 2001-05-04 Time 10:37 Rev Time 3.00
Received By jgomez Date 2001-05-04 Time 10:37 Sent To  
Notes
2001-05-04 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 2-NEED NOTICE OF COMMENCEMENT.
 3-ENTRY DOORS TO HAVE 32" MIN. CLEAR
 OPENING PER LEAF. TABLE 1004 SBC 1997.
 4-SPECIFY SAFETY GLASS AS REQUIRED BY
 SEC 2405.2 SBC 1997. SEE PLANS.
 5-MASTER BATH GLASS BLOCK TO BE ONE HOUR
 FIRE RATED. TABLE 600 SBC 1997.
 6-UPDATE SHEET C-1: GENERAL NOTES. SEE
 COMMENTS ON THIS SHEET.
 7-PROVIDE EGRESS WINDOW AT LIBRARY ROOM.
 THIS MAY BE CONSIDERED AS A BEDROOM.
 8-ENERGY CALCULATIONS:
 A)REVISE UNDER ATTIC AREA CALCULATED.
 SEC. 602.1.ABC.1.2 FLORIDA ENERGY
 EFFICIENCY CODE, 1997 EDITION.
 B)COMPLETE ADDRESS ON TOP OF FORM
 C)MISSING CALCULATIONS FOR ADJACENT WALL
 D)OWNER/AGENT TO DATE FORM AT THE BOTTOM
 9-REVISE STORM PANELS INSTALLATION SCHED
 AND KEY PLAN TO MATCH ARCHITECT'S PLAN
 10-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS.
 B)FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 C)SLIDING GLASS DOORS WITH TRANSOM ABOVE
 SINGLE ASSEMBLY AS SHOWN ON PLANS.
 D)WINDOW MULLIONS(ONE SUBMITTED EXPIRED)
 E)GARAGE DOORS. 8' AND 16'. DADE COUNTY
 OR SBCCI NOT BROWARD COUNTY.
 F)ONE HOUR FIRE RATED GLASS BLOCK.
 G)FIXED WINDOWS AS SHOWN ON ARCHITECT'S
 EXTERIOR ELEVATIONS.
 H)ROUND WINDOW.
 11-SEE PLANS FOR ADDITIONAL COMMENTS.
  
 NOTE: PLEASE RETURN REVIEWED SET OF
 DRAWINGS AFTER CORRECTIONS ARE
 DONE TO ORIGINAL DRAWINGS IN ORDER
 TO EXPEDITE THE REVIEW PROCESS.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-04-17 Cont ID  
Sent By sgraham Date 2001-04-17 Time 10:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***