| Plan Review Stops For Permit 01040422 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-04-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-10 |
Time |
14:20 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-04-10 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2001-04-10 00:00:00 | ******************PROVISO*************** | | | | | | AS PER 1997 SMC 406.1, FAN SHUTDOWN BY | | | DUCT SMOKE DETECTOR IN THE RETURN AIR | | | STREAM PRIOR TO ANY EXHAUSTING FROM THE | | | BUILDING OR MIXING WITH FRESH AIR | | | MAKEUP, WITH NOTIFICATION TO | | | ALARM/STROBE AS PER NFPA 4-4.4.3. |
|
|
|