Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-04-10 Cont ID  
Sent By pkrauss Date 2001-04-10 Time 14:20 Rev Time 0.40
Received By pkrauss Date 2001-04-10 Time 14:12 Sent To  
Notes
2001-04-10 00:00:00******************PROVISO***************
  
 AS PER 1997 SMC 406.1, FAN SHUTDOWN BY
 DUCT SMOKE DETECTOR IN THE RETURN AIR
 STREAM PRIOR TO ANY EXHAUSTING FROM THE
 BUILDING OR MIXING WITH FRESH AIR
 MAKEUP, WITH NOTIFICATION TO
 ALARM/STROBE AS PER NFPA 4-4.4.3.