Plan Review Details - Permit 01040372
Plan Review Stops For Permit 01040372
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-26 Cont ID  
Sent By jwitmer Date 2001-04-26 Time 10:16 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-11 Cont ID  
Sent By jwitmer Date 2001-04-11 Time 18:45 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-11 00:00:00BUILDING PLAN REVIEW
 SUNCOAST AUTO BUILDERS
 (727) 561-0764
 915 S DIXIE HWY
 01040372
  
 1)- SHEET A -8.3 SECTION 2, THIS DETAIL
 DEPICTS A FOOTER WITH DOWEL @ 48" EXTEND
 ING OUT OF THE FOOTER, NO VERTICAL STEEL
 NOR IS THERE INFORMATION HOW THE WALL
 WILL BE SUPPORTED OR STABALIZED FOR
 LATERAL BRACING AT THE TOP OF THE WALL,
 IS THERE A BEAM DOWELS WILL BE SECURRED
 TO?
  
 2)- HEAD & JAMB DETAIL, INFORMATION ON
 THE DOOR BUCK FASTENING NOR IS THERE ANY
 INFORMATION ON THE JAMB FASTENING?
  
 3)- EXTERIOR DOOR REQUIRES PRODUCT INFOR
 MATION FOR TESTING FOR WIND, SBC 1707.4
 TESTING IS TO INDICATE A 10 SEC.TEST AT
 1 1/2 TIMES THE DESIGN PRESSURE. DADE
 COUNTY OR SBCCI REPORTS ARE ACCEPTED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2001-04-25 Cont ID  
Sent By dpalmer Date 2001-04-25 Time 19:19 Rev Time 0.00
Received By dpalmer Date 2001-04-25 Time 19:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-17 Cont ID  
Sent By dpalmer Date 2001-04-17 Time 20:16 Rev Time 0.00
Received By dpalmer Date 2001-04-17 Time 20:16 Sent To  
Notes
2001-04-17 00:00:00****************** UNSAT *************
  
 1)NOTE: NOT ENOUGH INFORMATION SUBMITTED
 FOR AN ELECTRICAL REVIEW.
 PLAN ONLY SHOW A REFLECTED CEILING
 LAYOUT.
 PLEASE SUBMIT MORE INFORMATION IF
 ELECTRICAL WORK IS BEING DONE. PLEASE
 NOTE THAT BRANCH CIRCUIT #`S NEED TO BE
 ON PLANS FOR ALL REQ`D OUTLETS PER NEC
 AND LOCAL CODE. ALSO FOR ALL LIGHTING
 AND HOW THEY ARE CONTROLLED. PLEASE
 SUBMIT PANEL
 SCHEDULE(S) THAT CORRELATE WITH BRANCH
 CIRCUIT #`S.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-04-26 Cont ID  
Sent By mcarsill Date 2001-04-26 Time 11:37 Rev Time 0.00
Received By mcarsill Date 2001-04-26 Time 11:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-04-17 Cont ID  
Sent By pkrauss Date 2001-04-17 Time 16:42 Rev Time 0.25
Received By pkrauss Date 2001-04-17 Time 16:41 Sent To  
Notes
2001-04-17 00:00:00******************DENIED****************
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE SUBMIT PLANS WITH
 MECHANICAL PERMIT APPLICATION.