Plan Review Details - Permit 01040372
| Plan Review Stops For Permit 01040372 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-04-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-26 |
Time |
10:16 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-04-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-11 |
Time |
18:45 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-11 00:00:00 | BUILDING PLAN REVIEW | | | SUNCOAST AUTO BUILDERS | | | (727) 561-0764 | | | 915 S DIXIE HWY | | | 01040372 | | | | | | 1)- SHEET A -8.3 SECTION 2, THIS DETAIL | | | DEPICTS A FOOTER WITH DOWEL @ 48" EXTEND | | | ING OUT OF THE FOOTER, NO VERTICAL STEEL | | | NOR IS THERE INFORMATION HOW THE WALL | | | WILL BE SUPPORTED OR STABALIZED FOR | | | LATERAL BRACING AT THE TOP OF THE WALL, | | | IS THERE A BEAM DOWELS WILL BE SECURRED | | | TO? | | | | | | 2)- HEAD & JAMB DETAIL, INFORMATION ON | | | THE DOOR BUCK FASTENING NOR IS THERE ANY | | | INFORMATION ON THE JAMB FASTENING? | | | | | | 3)- EXTERIOR DOOR REQUIRES PRODUCT INFOR | | | MATION FOR TESTING FOR WIND, SBC 1707.4 | | | TESTING IS TO INDICATE A 10 SEC.TEST AT | | | 1 1/2 TIMES THE DESIGN PRESSURE. DADE | | | COUNTY OR SBCCI REPORTS ARE ACCEPTED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2001-04-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-25 |
Time |
19:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-25 |
Time |
19:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-04-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-17 |
Time |
20:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-17 |
Time |
20:16 |
Sent To |
|
|
| Notes |
| 2001-04-17 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: NOT ENOUGH INFORMATION SUBMITTED | | | FOR AN ELECTRICAL REVIEW. | | | PLAN ONLY SHOW A REFLECTED CEILING | | | LAYOUT. | | | PLEASE SUBMIT MORE INFORMATION IF | | | ELECTRICAL WORK IS BEING DONE. PLEASE | | | NOTE THAT BRANCH CIRCUIT #`S NEED TO BE | | | ON PLANS FOR ALL REQ`D OUTLETS PER NEC | | | AND LOCAL CODE. ALSO FOR ALL LIGHTING | | | AND HOW THEY ARE CONTROLLED. PLEASE | | | SUBMIT PANEL | | | SCHEDULE(S) THAT CORRELATE WITH BRANCH | | | CIRCUIT #`S. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-04-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-26 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-26 |
Time |
11:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-04-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-17 |
Time |
16:42 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2001-04-17 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2001-04-17 00:00:00 | ******************DENIED**************** | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW.PLEASE SUBMIT PLANS WITH | | | MECHANICAL PERMIT APPLICATION. |
|
|
|