Plan Review Details - Permit 01040371
Plan Review Stops For Permit 01040371
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-26 Cont ID  
Sent By jwitmer Date 2001-04-26 Time 08:53 Rev Time 0.70
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-12 Cont ID  
Sent By jwitmer Date 2001-04-12 Time 12:44 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-12 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01040371
 915 S DIXIE HWY
 SUNCOAST AUTOBUILDERS
 (727) 561-0764
  
 1)- SBC 1004.2.2. A MINIMUM OF (2)
 APPROVED EXITS ARE REQUIRED FOR A
 BUSINESS OCCUPANY,PLEASE INDICATE THE
 SECOND MEANS OF EGRESS.
  
 2)- THE SITE PLAN INDICATES THAT THERE
 IS AN ELEVATOR TO THE SECOND FLOOR.THE
 FL ACCESSIBILITY CODE 4.13.6. HAS MAN-
 EUVERING CLEARENCES AT DOORWAYS TO BE
 CONSIDERED. THE COMPUTER ROOM & ENCLOSED
 OFFICE DO NOT MEET THE REQUIREMENTS OF
 THIS CODE SECTION, A COPY OF THE CODE
 SECTION IS ATTACHED.
  
 3)- SBC 1016.2.1. EMERGENCY LIGHTING IS
 NOT INDICATED ON THE PLAN.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2001-04-25 Cont ID  
Sent By dpalmer Date 2001-04-25 Time 19:18 Rev Time 0.00
Received By dpalmer Date 2001-04-25 Time 19:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-17 Cont ID  
Sent By dpalmer Date 2001-04-17 Time 20:34 Rev Time 0.00
Received By dpalmer Date 2001-04-17 Time 20:29 Sent To  
Notes
2001-04-17 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT NO BRANCH
 CIRCUIT #`S ARE SHOWN ON PLANS FOR
 LIGHTING AND NO SUBMITTED PANEL
 SCHEDULE TO CORRELATE #`S.
 ALSO PLEASE NOTE THAT OUTLETS ARE REQ`D
 BY NEC AND LOCAL CODE PER PALM BEACH
 COUNTY AND CITYWIDE AMENDMENTS FOR
 OFFICES 210-50. PLEASE NOTE THAT FIXED
 GLASS PANELS ARE CONSIDERED WALL SPACE
 BY NEC ART:210-52
  
  
 PLEASE SUBMIT MORE ELECTRICAL DEATIL
 FORREVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELETRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-04-26 Cont ID  
Sent By mcarsill Date 2001-04-26 Time 11:44 Rev Time 0.00
Received By mcarsill Date 2001-04-26 Time 11:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-04-10 Cont ID  
Sent By mcarsill Date 2001-04-10 Time 10:07 Rev Time 0.00
Received By mcarsill Date 2001-04-10 Time 10:07 Sent To  
Notes
2001-04-10 00:00:001) PLEASE INDICATE HOW THE REQUIRED
 SECOND MEANS OF EGRESS IS ACCOMPLISHED
 FROM THE SECOND FLOOR AREA THAT IS BEING
 REMODELED.
 2) PLEASE INDICATE ON THE PLANS WHERE
 THE EMERGENCY LIGHTING EQUIPMENT IS
 LOCATED.
  
 CAPTAIN MIKE CARSILLO
 659-8096 EXT 8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-04-17 Cont ID  
Sent By pkrauss Date 2001-04-17 Time 16:26 Rev Time 0.25
Received By pkrauss Date 2001-04-17 Time 16:26 Sent To  
Notes
2001-04-17 00:00:00******************DENIED****************
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.