| Notes |
| 2001-04-12 00:00:00 | 1) HOOD, DUCT AND EXTINGUISHING SYSTEM | | | TO COMPLY WITH NFPA 96 AND NFPA 17A. | | | 2) THE DUCT IS TO BE INSPECTED PRIOR | | | TO DUCT WRAP APPLICATION. THE DUCT WHEN | | | WRAPPED IS TO BE INSPECTED. THE WHOLE | | | ASSEMBLY IS THEN TO BE INSPECTED AT THE | | | SITE PRIOR TO LOWERING IT INTO THE TWO | | | HOUR RATED SHAFT. | | | 3) EXHAUST DUCT TO BE A MINIMUM OF TEN | | | FEET FROM AIR INTAKES. | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE FIRE SUPPRESSION SYSTEM. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-04-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-09 |
Time |
10:30 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-04-12 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2001-04-09 00:00:00 | | | | | | | PLEASE PROVIDE DETAIL OF SUPPLY AIR | | | INTAKE, SUPPLY FAN AND SUPPLY TO HOODS. | | | | | | | | | NOTE - ADDITIONAL PERMIT REQUIRED FOR | | | FIRE SUPPRESSION, SUBMIT PLANS | | | WITH PERMIT APPLICATION. |
|
|
|