Plan Review Details - Permit 01040278
Plan Review Stops For Permit 01040278
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-04-12 Cont ID  
Sent By mcarsill Date 2001-04-12 Time 10:33 Rev Time 0.00
Received By mcarsill Date 2001-04-12 Time 10:33 Sent To  
Notes
2001-04-12 00:00:001) HOOD, DUCT AND EXTINGUISHING SYSTEM
 TO COMPLY WITH NFPA 96 AND NFPA 17A.
 2) THE DUCT IS TO BE INSPECTED PRIOR
 TO DUCT WRAP APPLICATION. THE DUCT WHEN
 WRAPPED IS TO BE INSPECTED. THE WHOLE
 ASSEMBLY IS THEN TO BE INSPECTED AT THE
 SITE PRIOR TO LOWERING IT INTO THE TWO
 HOUR RATED SHAFT.
 3) EXHAUST DUCT TO BE A MINIMUM OF TEN
 FEET FROM AIR INTAKES.
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE SUPPRESSION SYSTEM.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-04-12 Cont ID  
Sent By pkrauss Date 2001-04-09 Time 10:30 Rev Time 0.45
Received By pkrauss Date 2001-04-12 Time 11:12 Sent To  
Notes
2001-04-09 00:00:00 
  
 PLEASE PROVIDE DETAIL OF SUPPLY AIR
 INTAKE, SUPPLY FAN AND SUPPLY TO HOODS.
  
  
 NOTE - ADDITIONAL PERMIT REQUIRED FOR
 FIRE SUPPRESSION, SUBMIT PLANS
 WITH PERMIT APPLICATION.