Plan Review Details - Permit 01040267
Plan Review Stops For Permit 01040267
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-04-20 Cont ID  
Sent By lsmith Date 2001-04-20 Time 12:58 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-05-10 Cont ID  
Sent By dpalmer Date 2001-05-10 Time 12:49 Rev Time 0.00
Received By dpalmer Date 2001-05-10 Time 12:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-09 Cont ID  
Sent By dpalmer Date 2001-04-09 Time 11:05 Rev Time 0.00
Received By dpalmer Date 2001-04-09 Time 11:05 Sent To  
Notes
2001-04-09 00:00:00**************** UNSAT *****************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW EQUIPMENT BEING INSTALLED. PER 110-9
 AND 215-5.
  
 2)NOTE: PLEASE NOTE THAT GROUNDING
 ELECTRODETO COLD WATER PIPE ALSO/
 PER 250-50SIZE CONDUCTOR PER 250-66.
  
 3)NOTE: PLEASE NOTE THAT NO PLAN WAS
 SUBMITTED FOR FLOOR PLAN OF HOUSE AND
 LAYOUT FOR ELECTRICAL. PLEASE SUBMIT
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-04-14 Cont ID  
Sent By kstevens Date 2001-04-14 Time 10:16 Rev Time 0.25
Received By kstevens Date 2001-04-14 Time 10:16 Sent To  
Notes
***NONE***