| Plan Review Stops For Permit 01040211 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-05-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-26 |
Time |
09:48 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-04-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-16 |
Time |
07:50 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-16 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT# 01040211 | | | 222 LAKEVIEW / 4TH FL | | | CATALUMO CONST | | | (561) 694-3000 EX 256 | | | | | | 1)- SBC 104.2.2. ADDITIONAL INFO:TYPE OF | | | BUILDING, TYPE I CONSTRUCTION. | | | | | | 2)- SHEET A-1, A-2 BUCK DETAILS, SBC | | | 609.2.1. SUB BUCKS TO BE OF FIRE TREATED | | | RESISTANT WOOD. | | | | | | 3)- SBC TABLE803.3 MINIMUM INTERIOR | | | FINISH CLASSIFICATION NOT GIVEN. | | | | | | 4)- SBC FIRE SPRINKLERS 903.1 A LAYOUT | | | OF THE FIRE SPRINKLER PLAN AND EQUIPMENT | | | | | | 5)- SBC 905.1 MANUAL FIRE ALARM SYSTEM: | | | GROUP B REQUIRED FOR 100 PERSONS ABOVE | | | THE STREET FLOOR. | | | | | | 6)- SBC 104.2.2. ADITIONAL INFORMATION | | | DOOR # 1 FIRE RATED ROLL DOWN DOOR,ADD | | | INFORMATION REQUIRED. | | | | | | 7)- ROOM # 145 THE EXISTING DOOR DOESN'T | | | MEET THE FL ACCESSIBILITY MANEUVERING | | | CLEARENCES, FL ACC 4.13.6. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-09-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-10 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-10 |
Time |
13:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-05-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-21 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-21 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2001-05-21 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT ALL BRANCH | | | CIRCUIT #`S NEED TO BE SHOWN ON PLANS | | | AND SUBMIT PANEL SCHEDULES TO CORRELATE | | | W/#`S SHOWN. | | | | | | | | | PLEASE SUBMIT THE ABOVE IFFORMATION FOR' | | | REVIEW BEFORE FINAL ELECTRICAL INSPECT- | | | -ION IS CALLED IN. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-04-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-17 |
Time |
19:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-17 |
Time |
19:53 |
Sent To |
|
|
| Notes |
| 2001-04-17 00:00:00 | ******************* UNSAT ************ | | | | | | 1)NOTE: PLEASE PLACE BRANCH CIRCUIT #`S | | | ON PLANS THAT CORRELATE WITH A SUBMITTED | | | PANEL SCHEDULE. PLEASE NOTE THAT IF CIRC | | | UIT LAYOUT IS NOT SHOWN, WE SOMETIMES | | | FIND MORE LOAD THEN ALLOWED BY CODE. | | | PLEASE NOTE THAT PLAN SHOWS NUMEROUS NEW | | | LIGHTING FIXTURES. PLEASE NOTE THAT NO | | | LOAD CALCUALTIONS WERE SUBMITTED FOR | | | EXISTING AND NEW. 215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE NAY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-05-22 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-05-22 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-05-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-29 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-29 |
Time |
08:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-04-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-05 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-05 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2001-04-05 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | WITH PLANS. | | | 2) PLEASE INDICATE LOCATIONS OF FIRE | | | ALARM EQUIPMENT WITHIN TENANT SPACE. | | | 3) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-06-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-19 |
Time |
12:56 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-06-19 |
Time |
12:46 |
Sent To |
|
|
| Notes |
| 2001-06-19 00:00:00 | RESUB WAS NEVER REVIEWED BY MECHANICAL | | | APPROVED 6/19/01 PHK. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-04-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-17 |
Time |
13:32 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-04-17 |
Time |
12:31 |
Sent To |
|
|
| Notes |
| 2001-04-17 00:00:00 | *******************DENIED*************** | | | | | | 1.DRAWING M-1 IN THE KEY NOTES, #6. | | | HP-7 IS BEING REMOVED, IS IT BEING | | | REPLACED AS AN EXACT CHANGEOUT? | | | | | | 2.M-1 - KEY NOTE #11 INDICATES HP-D | | | WILL BE REPLACED WITH A LARGER UNIT | | | PLEASE INDICATE WHAT SIZE AND WHAT | | | LETTER/NUMBER IS ASSIGNED TO THE | | | NEW HEAT PUMP. | | | | | | PLEASE PROVIDE ABOVE INFORMATION WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | 3.PRIOR TO CONNECTING TO ANY EXISTING | | | DUCTWORK, CALL FOR AN INSPECTION. | | | | | | | | | MECHANICAL PLAN REVIEW | | | PATRICIA KRAUSS | | | (561) 659-8096 EXT. 8388 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-05-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-05-21 |
Time |
17:11 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-05-21 |
Time |
17:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-04-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-04-18 |
Time |
19:27 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-04-18 |
Time |
19:26 |
Sent To |
|
|
| Notes |
| 2001-04-18 00:00:00 | PLUMBING PLAN REVIEW. | | | DENIED: | | | SPC 1994 & FACBC 1997 | | | | | | (1)PAGE P-1 WATER HEATER DETAIL, | | | PAN DRAIN TO BE 1". | | | | | | (2)PAGE P-1 WATER HEATER DETAIL, | | | RELIEF AND PAN TO DRAIN | | | INTO FLOOR SINK NOT | | | FLOOR DRAIN. | | | | | | (3)PAGE P-1 RELIEF TO DISCHARGE TO | | | AN OBSERVABLE LOCATION. | | | | | | (4)PAGE P-1 NOTE # 12 - AIR CHAMBERS | | | TO BE ACCESSABLE AND | | | RECHARGABLE PER SPC 1994 | | | 607.8.2 & 607.8.3 | | | | | | (5)PAGE P-1 PLUMBING FIXTURE SCHED. | | | SINKS TO COMPLY WITH | | | FACBC 1997 4.24.2/4.24.3 | | | | | | QUESTION CALL KEN STEVENS | | | (561) 659-8096 X'S 8389/8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-05-22 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-05-22 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|