Plan Review Details - Permit 01040211
Plan Review Stops For Permit 01040211
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-05-26 Cont ID  
Sent By jwitmer Date 2001-05-26 Time 09:48 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-16 Cont ID  
Sent By jwitmer Date 2001-04-16 Time 07:50 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-16 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01040211
 222 LAKEVIEW / 4TH FL
 CATALUMO CONST
 (561) 694-3000 EX 256
  
 1)- SBC 104.2.2. ADDITIONAL INFO:TYPE OF
 BUILDING, TYPE I CONSTRUCTION.
  
 2)- SHEET A-1, A-2 BUCK DETAILS, SBC
 609.2.1. SUB BUCKS TO BE OF FIRE TREATED
 RESISTANT WOOD.
  
 3)- SBC TABLE803.3 MINIMUM INTERIOR
 FINISH CLASSIFICATION NOT GIVEN.
  
 4)- SBC FIRE SPRINKLERS 903.1 A LAYOUT
 OF THE FIRE SPRINKLER PLAN AND EQUIPMENT
  
 5)- SBC 905.1 MANUAL FIRE ALARM SYSTEM:
 GROUP B REQUIRED FOR 100 PERSONS ABOVE
 THE STREET FLOOR.
  
 6)- SBC 104.2.2. ADITIONAL INFORMATION
 DOOR # 1 FIRE RATED ROLL DOWN DOOR,ADD
 INFORMATION REQUIRED.
  
 7)- ROOM # 145 THE EXISTING DOOR DOESN'T
 MEET THE FL ACCESSIBILITY MANEUVERING
 CLEARENCES, FL ACC 4.13.6.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-09-10 Cont ID  
Sent By dpalmer Date 2001-09-10 Time 13:40 Rev Time 0.00
Received By dpalmer Date 2001-09-10 Time 13:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-05-21 Cont ID  
Sent By dpalmer Date 2001-05-21 Time 13:52 Rev Time 0.00
Received By dpalmer Date 2001-05-21 Time 13:52 Sent To  
Notes
2001-05-21 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT ALL BRANCH
 CIRCUIT #`S NEED TO BE SHOWN ON PLANS
 AND SUBMIT PANEL SCHEDULES TO CORRELATE
 W/#`S SHOWN.
  
  
 PLEASE SUBMIT THE ABOVE IFFORMATION FOR'
 REVIEW BEFORE FINAL ELECTRICAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-17 Cont ID  
Sent By dpalmer Date 2001-04-17 Time 19:53 Rev Time 0.00
Received By dpalmer Date 2001-04-17 Time 19:53 Sent To  
Notes
2001-04-17 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE PLACE BRANCH CIRCUIT #`S
 ON PLANS THAT CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE. PLEASE NOTE THAT IF CIRC
 UIT LAYOUT IS NOT SHOWN, WE SOMETIMES
 FIND MORE LOAD THEN ALLOWED BY CODE.
 PLEASE NOTE THAT PLAN SHOWS NUMEROUS NEW
 LIGHTING FIXTURES. PLEASE NOTE THAT NO
 LOAD CALCUALTIONS WERE SUBMITTED FOR
 EXISTING AND NEW. 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-05-22 Cont ID  
Sent By lsmith Date 2001-05-22 Time 13:47 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-05-29 Cont ID  
Sent By mcarsill Date 2001-05-29 Time 08:27 Rev Time 0.00
Received By mcarsill Date 2001-05-29 Time 08:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-04-05 Cont ID  
Sent By mcarsill Date 2001-04-05 Time 14:45 Rev Time 0.00
Received By mcarsill Date 2001-04-05 Time 14:45 Sent To  
Notes
2001-04-05 00:00:001) NO FIRE SPRINKLER DRAWINGS INCLUDED
 WITH PLANS.
 2) PLEASE INDICATE LOCATIONS OF FIRE
 ALARM EQUIPMENT WITHIN TENANT SPACE.
 3) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-19 Cont ID  
Sent By pkrauss Date 2001-06-19 Time 12:56 Rev Time 0.40
Received By pkrauss Date 2001-06-19 Time 12:46 Sent To  
Notes
2001-06-19 00:00:00RESUB WAS NEVER REVIEWED BY MECHANICAL
 APPROVED 6/19/01 PHK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-04-17 Cont ID  
Sent By pkrauss Date 2001-04-17 Time 13:32 Rev Time 0.45
Received By pkrauss Date 2001-04-17 Time 12:31 Sent To  
Notes
2001-04-17 00:00:00*******************DENIED***************
  
 1.DRAWING M-1 IN THE KEY NOTES, #6.
 HP-7 IS BEING REMOVED, IS IT BEING
 REPLACED AS AN EXACT CHANGEOUT?
  
 2.M-1 - KEY NOTE #11 INDICATES HP-D
 WILL BE REPLACED WITH A LARGER UNIT
 PLEASE INDICATE WHAT SIZE AND WHAT
 LETTER/NUMBER IS ASSIGNED TO THE
 NEW HEAT PUMP.
  
 PLEASE PROVIDE ABOVE INFORMATION WITH
 MECHANICAL PERMIT APPLICATION.
  
 3.PRIOR TO CONNECTING TO ANY EXISTING
 DUCTWORK, CALL FOR AN INSPECTION.
  
  
 MECHANICAL PLAN REVIEW
 PATRICIA KRAUSS
 (561) 659-8096 EXT. 8388

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-05-21 Cont ID  
Sent By kstevens Date 2001-05-21 Time 17:11 Rev Time 0.33
Received By kstevens Date 2001-05-21 Time 17:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-04-18 Cont ID  
Sent By kstevens Date 2001-04-18 Time 19:27 Rev Time 1.00
Received By kstevens Date 2001-04-18 Time 19:26 Sent To  
Notes
2001-04-18 00:00:00PLUMBING PLAN REVIEW.
 DENIED:
 SPC 1994 & FACBC 1997
  
 (1)PAGE P-1 WATER HEATER DETAIL,
 PAN DRAIN TO BE 1".
  
 (2)PAGE P-1 WATER HEATER DETAIL,
 RELIEF AND PAN TO DRAIN
 INTO FLOOR SINK NOT
 FLOOR DRAIN.
  
 (3)PAGE P-1 RELIEF TO DISCHARGE TO
 AN OBSERVABLE LOCATION.
  
 (4)PAGE P-1 NOTE # 12 - AIR CHAMBERS
 TO BE ACCESSABLE AND
 RECHARGABLE PER SPC 1994
 607.8.2 & 607.8.3
  
 (5)PAGE P-1 PLUMBING FIXTURE SCHED.
 SINKS TO COMPLY WITH
 FACBC 1997 4.24.2/4.24.3
  
 QUESTION CALL KEN STEVENS
 (561) 659-8096 X'S 8389/8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-05-22 Cont ID  
Sent By lsmith Date 2001-05-22 Time 13:47 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***