Plan Review Details - Permit 01040196
Plan Review Stops For Permit 01040196
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-05-07 Cont ID  
Sent By hpiskura Date 2001-05-07 Time 11:33 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-13 Cont ID  
Sent By jwitmer Date 2001-04-13 Time 16:14 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-13 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01040196
 560 VILLAGE BLVD/ 250
 QUEST CONTRACTING
 691-9400
  
 1)- 1997 FL ACCESSIBILITY CODE 4.1.6.2.2
 ALTERATION TO AN AREA CONTAINING A
 PRIMARY FUNCTION: DISPROPORTIONATE COST
 IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO
 THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER:
 A)ACCESSIBLE ENTRY
 B)ACCESSIBLE ROUTE / ALTERED AREAS
 C)AT LEAST ONE ACCESSIBLE FOR EACH SEX
 OR A UNISEX RESTROOM. NEITHER RESTROOM
 1 OR 2 MEETS THE ACCESSIBILITY CODE.
  
 2)- SBC 903.1 AN APPROVED FIRE SPRINKLER
 LAY OUT( SHOP DRAWINGS) REQUIRED.
  
 3)- SBC TABLE 1004 REQUIRES A MINIMUM OF
 44" FOR CORRIDOR & ISLE WIDTH.
  
 4)- SBC 803.3 MISSING IS INFORMATION ON
 TABLE 803.3 FOR THE MINIMUM INTERIOR
 FINISH CLASSIFICATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-05-07 Cont ID  
Sent By dpalmer Date 2001-05-07 Time 13:10 Rev Time 0.00
Received By dpalmer Date 2001-05-07 Time 13:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-16 Cont ID  
Sent By dpalmer Date 2001-04-16 Time 22:20 Rev Time 0.00
Received By dpalmer Date 2001-04-16 Time 22:20 Sent To  
Notes
2001-04-16 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT TWO DIFFERENT
 SETS OF ELEC DRAWING WERE SUBMITTED AND
 ONE SET INCLUDED E-1,2,3 AND THE OTHER
 TWO SETS CONTAINED E-2,3? PLEASE
 SUBMIT FOR PROPER REVIEW.
  
 2)NOTE: PLEASE NOTE THAT IF PLANS
 SUBMITTED INCLUDENEW PANEL, THEN
 PLEASE SUBMIT LOAD CALCULATIONS PER
 215-5 FOR
 ADDED LOAD TO EXISTING HV PANEL. ECT
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-04-16 Cont ID  
Sent By lsmith Date 2001-04-16 Time 10:58 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-04-30 Cont ID  
Sent By mcarsill Date 2001-04-30 Time 14:36 Rev Time 0.00
Received By mcarsill Date 2001-04-30 Time 14:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-04-05 Cont ID  
Sent By mcarsill Date 2001-04-05 Time 13:54 Rev Time 0.00
Received By mcarsill Date 2001-04-05 Time 13:54 Sent To  
Notes
2001-04-05 00:00:001) FIRE DAMPERS NOT SHOWN WHERE AIR
 CONDITIONING PASSES THROUGH TENANT
 SEPARATION WALL.
 2) PROVIDE PERMIT AND SHOP DRAWINGS
 FOR FIRE SPRINKLER REMODEL.
 3) MINIMUM WIDTH OF CORRIDORS AND
 PASSAGEWAYS SHALL BE AT LEAST 44 INCHES
 WIDE.
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION.
 5) PLEASE INDICATE EMERGENCY LIGHT
 FIXTURE LOCATIONS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-05-09 Cont ID  
Sent By pkrauss Date 2001-05-09 Time 09:38 Rev Time 0.30
Received By pkrauss Date 2001-05-09 Time 09:38 Sent To  
Notes
2001-05-09 00:00:00NOTES ON MECH PERMIT 01040205

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-04-17 Cont ID  
Sent By pkrauss Date 2001-04-17 Time 12:21 Rev Time 0.35
Received By pkrauss Date 2001-04-17 Time 12:21 Sent To  
Notes
2001-04-17 00:00:00******************DENIED****************
  
 ALL EXISTING FIRE DAMPERS MUST BE
 INDICATED ON THE PLAN.
  
 PLEASE PROVIDE INFORMATION ON EXHAUST
 FAN TO BE INSTALLED.
  
 NO COMBUSTIBLES ABOVE THE CEILING IN THE
 RETURN AIR PLENUM, 1997 SMC 609.1.1.
  
  
 NOTE:PRIOR TO CONNECTING TO ANY
 EXISTING DUCTWORK, CALL FOR
 AN INSPECTION.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-05-14 Cont ID  
Sent By jleech Date 2001-05-14 Time 09:33 Rev Time 0.50
Received By jleech Date 2001-05-14 Time 09:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-05-06 Cont ID  
Sent By pschmitz Date 2001-05-06 Time 14:37 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-06 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) WASH ROOM #1 TOCOMPLY WITH FACBC
 SEC4.1.3(11) EACH PUBLIC AND COMMON USE
 TOILET RM,SHALL COMPLY WITH 4.22
 ACCESSIBLE TOILET TO BE ON AN ACCESIBLE
 ROUTE, CLEAR FLR SPACE,GRAB BARS.
 (2) IF CONFERENCE RM SINK, IS A BREAK
 RM SINK,THEN IT TOO WILL HAVE TO
 COMPLY WITH FACBC 4.24.2 SINK HEIGHT
 34" FF,WITH KNEE CLEARANCE 4.23.3
 END OF COMMENTPAUL SCHMITZ
 QUESTIONS561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-04-18 Cont ID  
Sent By kstevens Date 2001-04-18 Time 18:06 Rev Time 0.75
Received By kstevens Date 2001-04-18 Time 18:06 Sent To  
Notes
2001-04-18 00:00:00PLUMBING PLAN REVIEW.
 DENIED:
 NOT ENOUGH INFORMATION.
 RISER DIAGRAMS FOR SANITARY
 AND WATER ARE REQUIRED ECT:
  
 END OF COMMENTS.
  
 QUESTIONS CALL KEN STEVENS
 (561) 659-8096 X'S 8389/8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-04-16 Cont ID  
Sent By lsmith Date 2001-04-16 Time 10:58 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***