| Plan Review Stops For Permit 01040054 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-04-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-03 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-03 |
Time |
12:46 |
Sent To |
|
|
| Notes |
| 2001-04-03 00:00:00 | 1) DUCT SMOKE DETECTORS ARE REQUIRED TO | | | BE CONNECTED TO FIRE ALARM SYSTEM. WHEN | | | ACTIVATED, THEY ARE TO ACTIVATE THE | | | FIRE ALARM SYSTEM AND CAUSE THE AIR | | | HANDLING UNITS TO SHUT DOWN. | | | 2) SMOKE DETECTORS TO BE INSTALLED A | | | MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 3) FIRE ALARM AND FIRE SPRINKLER SYSTEM | | | TO BE SUPERVISED BY A LICENSED UL LISTED | | | CENTRAL STATION APPROVED BY THE FIRE | | | RESCUE DEPARTMENT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|