Plan Review Details - Permit 01040043
Plan Review Stops For Permit 01040043
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-04-20 Cont ID  
Sent By mcarsill Date 2001-04-20 Time 12:38 Rev Time 0.00
Received By mcarsill Date 2001-04-20 Time 12:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-04-03 Cont ID  
Sent By mcarsill Date 2001-04-03 Time 11:22 Rev Time 0.00
Received By mcarsill Date 2001-04-03 Time 11:22 Sent To  
Notes
2001-04-03 00:00:001) PLEASE INDICATE WHAT THE TAPED
 MESSAGE OF THE VOICE EVACUATION
 SYSTEM WILL SAY. WHAT INSTRUCTIONS
 WILL BE GIVEN.
 2) SMOKE DETECTORS TO BE INSTALLED A
 MINIMUM OF THREE FROM AIR CONDITIONER
 DIFFUSERS.
 3) PLEASE INDICATE ON PLANS WHEN SMOKE
 EXHAUST FANS ARE TO ACTIVATE IN THE
 STAIRWELLS. DO THEY ACTIVATE ON ANY
 FIRE ALARM SIGNAL.
 4) PLEASE INDICATE ON PLANS THAT HEAT
 DETECTORS ASSOCIATED WITH ELEVATORS
 WILL NOT BE CONNECTED TO THE FIRE ALARM
 SYSTEM AND THAT THEY WILL ONLY SHUNT
 TRIP ELECTRIC AND OTHER ASSOCIATED
 DETAILS.
 5) FIRE ALARM LEGEND DOES NOT INDICATE
 WHAT THE DIAMONDS CONTAINING S
 REPRESENTS.
 6) FIRE ALARM SYSTEM TO BE MONITORED BY
 A UL LISTED CENTRAL STATION APPROVED BY
 THE FIRE RESCUE DEPARTMENT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910