Plan Review Details - Permit 01040038
Plan Review Stops For Permit 01040038
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-05-15 Cont ID  
Sent By lmartine Date 2001-05-15 Time 09:22 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-05-24 Cont ID  
Sent By dpalmer Date 2001-05-24 Time 08:19 Rev Time 0.00
Received By dpalmer Date 2001-05-24 Time 08:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-05-17 Cont ID  
Sent By dpalmer Date 2001-05-17 Time 10:53 Rev Time 0.00
Received By dpalmer Date 2001-05-17 Time 10:53 Sent To  
Notes
2001-05-17 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT AN ELECTRICAL
 RISER DIAGRAM AND LOAD CALCULATIONS
 WERE DROPPED OF BY ELECTRICAL CONTRACTOR
 ON 5/17/01 10:45AM.
 PANEL SCHEDULE AND LOAD CALCS DO NOT
 CORRELATE WITH PLANS. PLANS NEEDED TO
 BE PICKED AND AND NOTES NEEDED TO BE
 GONE OVER FROM PREVIOUS REVIEW.
 PLEASE ADDRESS THE NOTES ATTACHED FROM
 PREVIOUS REVIEW.
 PLEASE ALSO NOTE THAT A $50 RE-SUB FEE
 WILL NOW BE DUE ON NEXT RE-SUB.
  
 PLEASE CALL IF THERE ARE ANY QUESTIONS,
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-05-10 Cont ID  
Sent By dpalmer Date 2001-05-10 Time 07:39 Rev Time 0.00
Received By dpalmer Date 2001-05-10 Time 07:39 Sent To  
Notes
2001-05-10 00:00:00***************** UNSAT ***************
  
 1)NOTE:PLEASE NOTE THAT RESUBMITTAL
 SHEET SAYS THAT YOUR ELECTRICAL HAS
 CALLED ME AND SPOKEN WITH ME.??
 I DON'T RECALL SPEAKING TO ANYONE ABOUT
 THIS PLAN?
  
 2)NOTE: ALSO PLEASE NOTE THAT THE NOTE
 THAT I GAVE OUTFRONTFOR REVIEW OF
 ELECTRICAL IS STILL NOT DRAWN UP ON
 PLAN CORRECTLY.PLEASE SEE THE FOLLOWING
 NOTES.
  
  
 3)NOTE: PLEASE SUBMIT A RISER DIAGRAM
 SHOWING THE RISER FROM EXISTING TO NEW
 SERVICE BEING INSTALLED ON THE COTTAGE.
  
 PLEASE INCLUDE AIC RATINGS FOR ANY NEW
 EQUIPMENT BEING INSTALLED.110-9/215-5
 PLEASE SHOW ALL CONDUIT AND WIRE SIZES.
 PLEASE SHOW GROUNDING FROM MAIN HOUSE
 TOCOTTAGE AND GROUNDING AT COTTAGE.
 250-24AND 250-32
 PLEASE SUBMIT LOAD CALCUALTIONS FOR NEW
 LOADS BEING ADDED TO EXISTING LOAD.
 PLEASE SHOW COMBINED TOTAL LOAD. ART
 220AND 215-5.
 PLEASE INDICATE PANEL AT DETACHED
 STRUCTURE AS MCB.
  
 4)NOTE: PLEASE NOTE THAT THE PLAN SHOWS
 A TANKLESS WATER HEATER SYSTEM AND LOAD
 AT 4800W. PLEASE VERIFY THIS LOAD.
 AS MOST HAVE A HIGHER KW RATING.
  
 5)NOTE: PLEASE HAVE PLANS REPRINTED
 TO CLEAR UP ALL HAND WRITTEN ITEMS ON
 PLANS PER COUNTYWIDE AND CITY-WIDE
 ADMINISTRATIVE CODE. 104.2/ 104.2.7
  
 PLEASE SUBMIT ALL OF THE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-06 Cont ID  
Sent By dpalmer Date 2001-04-06 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2001-05-10 Time 07:38 Sent To  
Notes
2001-04-06 00:00:00FAILED DUE TO ZONING. PLEASE SEE
 NOTES HANDWRITTEN ON PLAN BY SG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-05-11 Cont ID  
Sent By pkrauss Date 2001-05-11 Time 07:22 Rev Time 0.25
Received By pkrauss Date 2001-05-11 Time 07:22 Sent To  
Notes
2001-05-11 00:00:00MECHANICAL PERMIT 01040040.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-12 Cont ID  
Sent By kstevens Date 2001-05-12 Time 08:24 Rev Time 1.00
Received By kstevens Date 2001-05-12 Time 08:24 Sent To  
Notes
2001-05-12 00:00:00REVIEW NOTES....PASSED....
  
 ....PROVISO...
  
 PLUMBING NOTES:
  
 #5 HO-HUM PIPE AND FITTINGS NOT
 APPROVED.
  
 # 16 AIR CHAMBERS SHALL COMPLY WITH
 SPC-94 - 607.8.2 & 607.8.3
  
 # 19 SANITARY PIPE SHALL HAVE 1/4" PITCH
 PER SPC-94 705.2
  
 REVIEW KSTEVENS

Review Stop Z ZONING
Rev No 2 Status P Date 2001-05-24 Cont ID  
Sent By dpalmer Date 2001-05-24 Time 08:22 Rev Time 0.00
Received By dpalmer Date 2001-05-24 Time 08:22 Sent To  
Notes
2001-05-24 00:00:00ZONING APPROVED BY ANGELA JONES.
 NO MEANS OF COOKING ALLOWED. NO STOVE.

Review Stop Z ZONING
Rev No 1 Status F Date 2001-04-06 Cont ID  
Sent By dpalmer Date 2001-04-06 Time 12:54 Rev Time 0.00
Received By dpalmer Date 2001-04-06 Time 12:54 Sent To  
Notes
2001-04-06 00:00:00PER SHIRLEY GRAHAM.