| Plan Review Stops For Permit 01040035 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-04-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-03 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-03 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2001-04-03 00:00:00 | 1) USED HOOD IS TO BE IN GOOD CONDITION | | | AND MEET THE REQUIREMENTS OF NFPA 96. | | | 2) PLEASE PROVIDE PRODUCT APPROVALS | | | FOR 3M FIREMASTER WRAP MATERIAL SHOWN | | | ON THE PLANS. | | | 3) HIGH-LIMIT CONTROLS REQUIRED FOR | | | FRYERS. | | | ON APRIL 5, 2001, WRITER RECEIVED | | | PRODUCT APPROVAL INFORMATION FROM | | | MECHANICAL PLAN REVIEWER PATTY KRAUSS. | | | SHE RECEIVED THIS INFORMATION FROM THE | | | CONTRACTOR. THIS INFORMATION HAS BEEN | | | ATTACHED TO THE PLANS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-04-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-11 |
Time |
14:33 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2001-04-11 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2001-04-11 00:00:00 | REVISION TO HOOD - HAD TO MODIFY THE WAY | | | OF HANGING IT - ENGINEER APPROVED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-04-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-06 |
Time |
09:42 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-04-06 |
Time |
09:42 |
Sent To |
|
|
| Notes |
|
|
|