Plan Review Details - Permit 01040035
Plan Review Stops For Permit 01040035
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-04-05 Cont ID  
Sent By mcarsill Date 2001-04-03 Time 14:40 Rev Time 0.00
Received By mcarsill Date 2001-04-03 Time 14:40 Sent To  
Notes
2001-04-03 00:00:001) USED HOOD IS TO BE IN GOOD CONDITION
 AND MEET THE REQUIREMENTS OF NFPA 96.
 2) PLEASE PROVIDE PRODUCT APPROVALS
 FOR 3M FIREMASTER WRAP MATERIAL SHOWN
 ON THE PLANS.
 3) HIGH-LIMIT CONTROLS REQUIRED FOR
 FRYERS.
 ON APRIL 5, 2001, WRITER RECEIVED
 PRODUCT APPROVAL INFORMATION FROM
 MECHANICAL PLAN REVIEWER PATTY KRAUSS.
 SHE RECEIVED THIS INFORMATION FROM THE
 CONTRACTOR. THIS INFORMATION HAS BEEN
 ATTACHED TO THE PLANS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-11 Cont ID  
Sent By pkrauss Date 2001-04-11 Time 14:33 Rev Time 0.25
Received By pkrauss Date 2001-04-11 Time 14:33 Sent To  
Notes
2001-04-11 00:00:00REVISION TO HOOD - HAD TO MODIFY THE WAY
 OF HANGING IT - ENGINEER APPROVED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-04-06 Cont ID  
Sent By pkrauss Date 2001-04-06 Time 09:42 Rev Time 0.40
Received By pkrauss Date 2001-04-06 Time 09:42 Sent To  
Notes
***NONE***