| Plan Review Stops For Permit 01031347 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-05-15 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-05-15 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-15 00:00:00 | APPROVED BY JIM WITMER ON 5/1/01LM |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-04-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-13 |
Time |
07:14 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-13 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01031347 | | | 444 24TH ST | | | L & L INTERIORS | | | 688-2844 | | | | | | 1)- SBC 1019.7.2. EACH DOOR IN A MEANS | | | OF EGRESS FROM AN AREA OF GROUP A OCCU- | | | PANCY MAY BE PROVIDED WITH A LATCH OR | | | LOCK ONLY IF IT IS PANIC HARDWARE OR | | | FIRE EXIT HARDWARE, WHICH RELEASES WHEN | | | NO MORE THAN 15LBS. PRESSURE IS APPLIED | | | TO THE RELEASING DEVICES IN THE DIREC- | | | TION OF THE EXIT TRAVEL. | | | | | | 2)- SBC 803.3 THE MINIMUM INTERIOR | | | FINISH CLASSIFICATION IS NOT INDICATED. | | | | | | 3)- SBC 1204.2 THE WALLS & FLOORS OF ALL | | | PUBLIC RESTROOMS SHALL BE LINED WITH | | | NONABSORBANT MATERIALS TO A HEIGTH OF | | | 4FT. ABOVE THE FLOOR. | | | | | | 4)- FL ACCESSIBILITY CODE 4.1.6 ALTERA- | | | TIONS CONTAINING A PRIMARY FUNCTION AREA | | | AN ACCESSIBILE ENTRENCE IS REQUIRED WITH | | | ONE RAMPED ENTRY. | | | | | | 5)- FL. ACCESIBILITY CODE 5.1 PROVIDE | | | AT LEAST 5% BUT LESS THAN ONE OF THE FIX | | | ED TABLES OR A PORTION OF THE COUNTER | | | SHALL BE ACCESSIBLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-04-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-09 |
Time |
18:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-09 |
Time |
18:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-04-25 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-04-25 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-04-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-27 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-27 |
Time |
09:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-04-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-05 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-05 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2001-04-05 00:00:00 | 1) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. PLEASE | | | INDICATE ON DRAWINGS WHERE THEY COULD | | | BE SEATED. | | | 2) PANIC HARDWARE REQUIRED ON ALL EXIT | | | DOORS WHERE 100 OR MORE PERSONS ARE | | | PRESENT. THE ONLY EXCEPTION IS THE | | | MAIN ENTRY DOOR(S) WHERE OCCUPANT LOADS | | | ARE LESS THAN 500 PERSONS AND SIGNS | | | ARE PLACED ON THE DOORS"THESE DOORS ARE | | | TO REMAIN UNLOCKED DURING BUSINESS | | | HOURS". | | | 3) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 4) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED ON PLANS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-05-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-21 |
Time |
09:42 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-05-21 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2001-05-21 00:00:00 | | | | | | | MECHANICAL PERMIT REQUIRED. | | | | | | ADDITIONAL PLANS AND PERMITS REQUIRED | | | FOR KITCHEN HOOD, FIRE SUPPRESSION | | | SYSTEM AND WALK-IN COOLERS. | | | | | | PRIOR TO CONNECTING TO ANY EXISTING | | | DUCT, CALL FOR AN INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2001-05-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-09 |
Time |
08:55 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-05-09 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2001-05-09 00:00:00 | ********************DENIED************** | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | WITH MECHANICAL PERMIT APPLICATION. | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | 2.AIR BALANCE SCHEDULE. | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHOULD UNIT HAVE THE CAPACITY | | | GREATER THAN 2,000 CFM. | | | | | | 4.WHEN UNIT CAPACITY IS GREATER THAN | | | 2,000 CFM & FAN SHUTDOWN APPLIES, | | | NOTIFICATION TO ALARM/STROBE AS PER | | | NFPA 4-4.4.3, WILL ALSO APPLY. | | | | | | 5.ADDITIONAL MECHANICAL PERMITS/PLANS | | | FOR ANY HOOD, FIRE SUPPRESSION OR | | | WALK-IN COOLERS. | | | | | | 6.PRIOR TO CONNECTING TO ANY EXISTING | | | DUCTWORK, CALL FOR AN INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-04-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-10 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2001-04-10 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2001-04-10 00:00:00 | ******************DENIED**************** | | | | | | PRIOR TO CONNECTING OR RELOCATING OF | | | EXISTING DUCT, INSPECTION IS REQUIRED. | | | | | | NO COMBUSTIBLES ABOVE CEILING IF THIS | | | AREA IS USED AS A RETURN AIR PLENUM. | | | | | | PLEASE PROVIDE DETAIL ON THE ROOF CURB | | | ATTACHING TO THE ROOF. | | | | | | ADDITIONAL PERMIT REQUIRED FOR HOOD | | | GREASE DUCT AND SUPPLY AIR TO HOOD. | | | PLEASE PROVIDE PLANS AND ANY SUBMITTAL | | | DATA WITH PERMIT APPLICATION. | | | | | | ADDITIONAL PERMIT REQUIRED FOR WALK-IN | | | COOLER, PLEASE PROVIDE PLANS AND | | | SUBMITTAL DATA FOR THE COOLER AND | | | CONDENSER AT THE TIME OF PERMIT | | | APPLICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2001-05-15 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-05-15 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-15 00:00:00 | PLUMBINGREVIEW TO BE DONE UNDER | | | SEPERATE PERMIT, CONTRACTOR SHALL | | | SUBMIT ALL NEW PLUMBING INFORMATION AT | | | TIME OF PERMIT APPLICATION, | | | | | | | | | L.MARTINEZ |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-05-06 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-05-06 |
Time |
14:05 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-06 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | (1) SHT.A1 WOMENS REST RM, COMPLY WITH | | | FACBC 4.17.3 H/C W/C,LAV IN A STALL. | | | (2) SHT A2 GAS WATER HEATER, CALCULATION | | | FOR COMBUSTION AIR SGC 97 SEC 402.4 | | | (3) LETTER FROM WPB REG SEWER PLANT FOR | | | GREASE TRAP SIZE, R.COMPO 837- 4074 | | | (4) S/SEWER PUBLIC REST RM,NOT OVER 2 | | | W/C ON 3" WASTE LINE. | | | (5) AIR CHAMBER DETAIL:DOES NOT COMPLY | | | WITH SEC 607.8.3,ACCESSIBLE,RECHARGEABLE | | | (6) GREASE WASTE RISER: GREASE WASTE TO | | | COMPLY WITH SPC SEC 921.4,MAIN TRUNK 4" | | | ALL BRANCHES 3", VENTS ON EACH END. | | | (7)GAS PIPING UNDER SLAB DETAIL: TO | | | COMPLY WITH SGC 97 SEC 308.4.2(2) | | | CHANNEL FLR,LIGHT WEIGHT CONCRETE. | | | (8) GAS RISER: PLEASE COMPLY WITH GAS | | | PERMIT APPLICATION REQUIRMENTS, SGC 97 | | | SEC.104.1.2, NOTES 2,3,5,6,7,8,9. | | | SEE ATTACHED. | | | (9)EMERGENCY SOV BELOW CEILING (ESOV). | | | MANUAL SOV TO BE UP STREAM OF ESOV WITH | | | A UNION DOWN STREAM OF ESOV.SEC 103.5 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096- X 8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-04-16 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-04-16 |
Time |
13:40 |
Rev Time |
2.00 |
| Received By |
jleech |
Date |
2001-04-16 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2001-04-16 00:00:00 | DENIED; | | | | | | 1.PLANS MUST BE REVIEWED AND APPROVED BY | | | THE HOTEL BUISNESS REGULATIONS AT | | | 954-958-5520. | | | | | | 2.CONTACT THE CITY UTILITY DEPARTMENT. | | | RODNEY COMPO AT 837-4074 FOR APPROVAL | | | OF GREASE TRAP SIZE AND LOCATION. | | | | | | 3.1997 STANDARD GAS CODE TABLE 305.4A | | | SHALL BE USED TO SIZE GAS PIPE. | | | | | | 4.DELETE UNDER SLAB GAS PIPE DETAIL. NO | | | GAS PIPE IS SHOWN ON DRAWINGS UNDER | | | SLAB. | | | | | | 5.DISHWASHER TO DISHCHARGE INDIRECTLY | | | INTO SANITARY FLOOR SINK NOT GREASY | | | WASTE. CITY ORD. | | | | | | 6.AIR CHAMBERS SHALL BE ENGINEERED | | | MECHANICAL WATER HAMMER ARRESTERS AND | | | SIZED BY AN ENGINEER. PER 94 SPC | | | 607.8.2 AND 607.8.3. | | | | | | 7.GREASE TRAP DETAIL; TWO WAY CLEANOUTS | | | REQUIRED. | | | | | | 8.TWO COMPARTMENT SINK SHALL BE | | | INDIRECTLY WASTED. 804.1 | | | | | | 9.EMERGENCY SHUTOFF VALVE FOR GAS PIPING | | | SHALL BE INSTALLED BELOW THE CEILING. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT;8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-04-25 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-04-25 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|