Plan Review Details - Permit 01031347
Plan Review Stops For Permit 01031347
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-05-15 Cont ID  
Sent By lmartine Date 2001-05-15 Time 16:25 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-05-15 00:00:00APPROVED BY JIM WITMER ON 5/1/01LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-13 Cont ID  
Sent By jwitmer Date 2001-04-13 Time 07:14 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-13 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01031347
 444 24TH ST
 L & L INTERIORS
 688-2844
  
 1)- SBC 1019.7.2. EACH DOOR IN A MEANS
 OF EGRESS FROM AN AREA OF GROUP A OCCU-
 PANCY MAY BE PROVIDED WITH A LATCH OR
 LOCK ONLY IF IT IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE, WHICH RELEASES WHEN
 NO MORE THAN 15LBS. PRESSURE IS APPLIED
 TO THE RELEASING DEVICES IN THE DIREC-
 TION OF THE EXIT TRAVEL.
  
 2)- SBC 803.3 THE MINIMUM INTERIOR
 FINISH CLASSIFICATION IS NOT INDICATED.
  
 3)- SBC 1204.2 THE WALLS & FLOORS OF ALL
 PUBLIC RESTROOMS SHALL BE LINED WITH
 NONABSORBANT MATERIALS TO A HEIGTH OF
 4FT. ABOVE THE FLOOR.
  
 4)- FL ACCESSIBILITY CODE 4.1.6 ALTERA-
 TIONS CONTAINING A PRIMARY FUNCTION AREA
 AN ACCESSIBILE ENTRENCE IS REQUIRED WITH
 ONE RAMPED ENTRY.
  
 5)- FL. ACCESIBILITY CODE 5.1 PROVIDE
 AT LEAST 5% BUT LESS THAN ONE OF THE FIX
 ED TABLES OR A PORTION OF THE COUNTER
 SHALL BE ACCESSIBLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-04-09 Cont ID  
Sent By dpalmer Date 2001-04-09 Time 18:45 Rev Time 0.00
Received By dpalmer Date 2001-04-09 Time 18:45 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-04-25 Cont ID  
Sent By lsmith Date 2001-04-25 Time 10:43 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-04-27 Cont ID  
Sent By mcarsill Date 2001-04-27 Time 09:41 Rev Time 0.00
Received By mcarsill Date 2001-04-27 Time 09:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-04-05 Cont ID  
Sent By mcarsill Date 2001-04-05 Time 09:44 Rev Time 0.00
Received By mcarsill Date 2001-04-05 Time 09:44 Sent To  
Notes
2001-04-05 00:00:001) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS. PLEASE
 INDICATE ON DRAWINGS WHERE THEY COULD
 BE SEATED.
 2) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS WHERE 100 OR MORE PERSONS ARE
 PRESENT. THE ONLY EXCEPTION IS THE
 MAIN ENTRY DOOR(S) WHERE OCCUPANT LOADS
 ARE LESS THAN 500 PERSONS AND SIGNS
 ARE PLACED ON THE DOORS"THESE DOORS ARE
 TO REMAIN UNLOCKED DURING BUSINESS
 HOURS".
 3) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 4) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION PROVIDED ON PLANS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-05-21 Cont ID  
Sent By pkrauss Date 2001-05-21 Time 09:42 Rev Time 0.40
Received By pkrauss Date 2001-05-21 Time 09:40 Sent To  
Notes
2001-05-21 00:00:00 
  
 MECHANICAL PERMIT REQUIRED.
  
 ADDITIONAL PLANS AND PERMITS REQUIRED
 FOR KITCHEN HOOD, FIRE SUPPRESSION
 SYSTEM AND WALK-IN COOLERS.
  
 PRIOR TO CONNECTING TO ANY EXISTING
 DUCT, CALL FOR AN INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-05-09 Cont ID  
Sent By pkrauss Date 2001-05-09 Time 08:55 Rev Time 0.30
Received By pkrauss Date 2001-05-09 Time 08:55 Sent To  
Notes
2001-05-09 00:00:00********************DENIED**************
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.AIR BALANCE SCHEDULE.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHOULD UNIT HAVE THE CAPACITY
 GREATER THAN 2,000 CFM.
  
 4.WHEN UNIT CAPACITY IS GREATER THAN
 2,000 CFM & FAN SHUTDOWN APPLIES,
 NOTIFICATION TO ALARM/STROBE AS PER
 NFPA 4-4.4.3, WILL ALSO APPLY.
  
 5.ADDITIONAL MECHANICAL PERMITS/PLANS
 FOR ANY HOOD, FIRE SUPPRESSION OR
 WALK-IN COOLERS.
  
 6.PRIOR TO CONNECTING TO ANY EXISTING
 DUCTWORK, CALL FOR AN INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-04-10 Cont ID  
Sent By pkrauss Date 2001-04-10 Time 16:36 Rev Time 0.00
Received By pkrauss Date 2001-04-10 Time 16:11 Sent To  
Notes
2001-04-10 00:00:00******************DENIED****************
  
 PRIOR TO CONNECTING OR RELOCATING OF
 EXISTING DUCT, INSPECTION IS REQUIRED.
  
 NO COMBUSTIBLES ABOVE CEILING IF THIS
 AREA IS USED AS A RETURN AIR PLENUM.
  
 PLEASE PROVIDE DETAIL ON THE ROOF CURB
 ATTACHING TO THE ROOF.
  
 ADDITIONAL PERMIT REQUIRED FOR HOOD
 GREASE DUCT AND SUPPLY AIR TO HOOD.
 PLEASE PROVIDE PLANS AND ANY SUBMITTAL
 DATA WITH PERMIT APPLICATION.
  
 ADDITIONAL PERMIT REQUIRED FOR WALK-IN
 COOLER, PLEASE PROVIDE PLANS AND
 SUBMITTAL DATA FOR THE COOLER AND
 CONDENSER AT THE TIME OF PERMIT
 APPLICATION.

Review Stop P PLUMBING
Rev No 3 Status N Date 2001-05-15 Cont ID  
Sent By lmartine Date 2001-05-15 Time 16:36 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-05-15 00:00:00PLUMBINGREVIEW TO BE DONE UNDER
 SEPERATE PERMIT, CONTRACTOR SHALL
 SUBMIT ALL NEW PLUMBING INFORMATION AT
 TIME OF PERMIT APPLICATION,
  
  
 L.MARTINEZ

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-05-06 Cont ID  
Sent By pschmitz Date 2001-05-06 Time 14:05 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-06 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) SHT.A1 WOMENS REST RM, COMPLY WITH
 FACBC 4.17.3 H/C W/C,LAV IN A STALL.
 (2) SHT A2 GAS WATER HEATER, CALCULATION
 FOR COMBUSTION AIR SGC 97 SEC 402.4
 (3) LETTER FROM WPB REG SEWER PLANT FOR
 GREASE TRAP SIZE, R.COMPO 837- 4074
 (4) S/SEWER PUBLIC REST RM,NOT OVER 2
 W/C ON 3" WASTE LINE.
 (5) AIR CHAMBER DETAIL:DOES NOT COMPLY
 WITH SEC 607.8.3,ACCESSIBLE,RECHARGEABLE
 (6) GREASE WASTE RISER: GREASE WASTE TO
 COMPLY WITH SPC SEC 921.4,MAIN TRUNK 4"
 ALL BRANCHES 3", VENTS ON EACH END.
 (7)GAS PIPING UNDER SLAB DETAIL: TO
 COMPLY WITH SGC 97 SEC 308.4.2(2)
 CHANNEL FLR,LIGHT WEIGHT CONCRETE.
 (8) GAS RISER: PLEASE COMPLY WITH GAS
 PERMIT APPLICATION REQUIRMENTS, SGC 97
 SEC.104.1.2, NOTES 2,3,5,6,7,8,9.
 SEE ATTACHED.
 (9)EMERGENCY SOV BELOW CEILING (ESOV).
 MANUAL SOV TO BE UP STREAM OF ESOV WITH
 A UNION DOWN STREAM OF ESOV.SEC 103.5
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096- X 8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-04-16 Cont ID  
Sent By jleech Date 2001-04-16 Time 13:40 Rev Time 2.00
Received By jleech Date 2001-04-16 Time 13:40 Sent To  
Notes
2001-04-16 00:00:00DENIED;
  
 1.PLANS MUST BE REVIEWED AND APPROVED BY
 THE HOTEL BUISNESS REGULATIONS AT
 954-958-5520.
  
 2.CONTACT THE CITY UTILITY DEPARTMENT.
 RODNEY COMPO AT 837-4074 FOR APPROVAL
 OF GREASE TRAP SIZE AND LOCATION.
  
 3.1997 STANDARD GAS CODE TABLE 305.4A
 SHALL BE USED TO SIZE GAS PIPE.
  
 4.DELETE UNDER SLAB GAS PIPE DETAIL. NO
 GAS PIPE IS SHOWN ON DRAWINGS UNDER
 SLAB.
  
 5.DISHWASHER TO DISHCHARGE INDIRECTLY
 INTO SANITARY FLOOR SINK NOT GREASY
 WASTE. CITY ORD.
  
 6.AIR CHAMBERS SHALL BE ENGINEERED
 MECHANICAL WATER HAMMER ARRESTERS AND
 SIZED BY AN ENGINEER. PER 94 SPC
 607.8.2 AND 607.8.3.
  
 7.GREASE TRAP DETAIL; TWO WAY CLEANOUTS
 REQUIRED.
  
 8.TWO COMPARTMENT SINK SHALL BE
 INDIRECTLY WASTED. 804.1
  
 9.EMERGENCY SHUTOFF VALVE FOR GAS PIPING
 SHALL BE INSTALLED BELOW THE CEILING.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT;8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-04-25 Cont ID  
Sent By lsmith Date 2001-04-25 Time 10:43 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***