Plan Review Details - Permit 01031317
Plan Review Stops For Permit 01031317
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-06-25 Cont ID  
Sent By jleahy Date 2001-06-25 Time 12:57 Rev Time 0.45
Received By jleahy Date 2001-06-25 Time 12:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-05-18 Cont ID  
Sent By dpalmer Date 2001-05-18 Time 09:01 Rev Time 0.00
Received By dpalmer Date 2001-05-18 Time 09:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-05-10 Cont ID  
Sent By dpalmer Date 2001-05-07 Time 15:05 Rev Time 0.00
Received By dpalmer Date 2001-05-07 Time 15:05 Sent To  
Notes
2001-05-10 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED TO
 BE SIGNED AND SEALED BY THE ARCH /
 ENGINEER OF RECORD. PER 481.221 AND
 471.025.
  
 PLEASE ADDRESS THGE ABOVE INFORMATION,
 IF THERE ARE ANY QUESTIONS, PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-04 Cont ID  
Sent By dpalmer Date 2001-04-04 Time 22:51 Rev Time 0.00
Received By dpalmer Date 2001-04-04 Time 22:51 Sent To  
Notes
2001-04-04 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 FRONT OUTLET
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-05 Cont ID  
Sent By pkrauss Date 2001-07-05 Time 13:02 Rev Time 0.25
Received By pkrauss Date 2001-07-05 Time 12:37 Sent To  
Notes
2001-07-05 00:00:00REVISION MECH PERMIT 01031332.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-04-04 Cont ID  
Sent By jleech Date 2001-04-04 Time 20:07 Rev Time 0.33
Received By jleech Date 2001-04-04 Time 20:07 Sent To  
Notes
2001-04-04 00:00:00PROVISO;R/A REQUIRED FROM M.B.
 X-FAN REQUIRED FROM MASTERBATH

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-06-23 Cont ID  
Sent By jleech Date 2001-06-23 Time 06:30 Rev Time 0.33
Received By jleech Date 2001-06-23 Time 06:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-05-25 Cont ID  
Sent By kstevens Date 2001-05-25 Time 15:40 Rev Time 0.25
Received By kstevens Date 2001-05-25 Time 15:40 Sent To  
Notes
2001-05-25 00:00:00REVIEW NOTESPASSED
  
 PROVISO
  
 SUBMIT SANITARY RISER DIAGRAM THAT
 REFLECTS INSTALLATION ON JOB.
  
 REVIEW BY KEN STEVENS
 561 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-04-04 Cont ID  
Sent By jleech Date 2001-04-04 Time 20:09 Rev Time 0.25
Received By jleech Date 2001-04-04 Time 20:09 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-05-25 Cont ID  
Sent By rmcdouga Date 2001-05-25 Time 16:41 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-05-10 Cont ID  
Sent By rmcdouga Date 2001-05-10 Time 16:10 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-05-10 00:00:00*************BUILDING UNSAT*************
  
 1) REVISED PLANS SUBMITTED MUST BE
 SIGNED AND SEALED BY THE ENGINEER.
 SBC 104.2.2
  
 2) NOTE: PLUMBING RISER ON REVISED PLANS
 HAS BEEN CHANGED AND DOES NOT CORRESPOND
 WITH THE FLOOR PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-04-17 Cont ID  
Sent By rmcdouga Date 2001-04-17 Time 09:30 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-04-17 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
 SBC 104.2.2
  
 2) STRUCTURE IS LOCATED IN AN A-ZONE,
 WHICH REQUIRES THAT A FLOOD ELEVATION
 CERTIFICATE BE SUBMITTED PRIOR TO
 RECEIVING A C.O.
  
 3) THE DESIGN PARAMETERS AND ASSUMPTIONS
 ON SHEET 1 LISTS BASIC VELOCITY PRESSURE
 OF 26 PSF AND MEAN ROOF HEIGHT OF 17 FT.
 THE ACTUAL MEAN ROOF HEIGHT IS 15FT.AND
 VELOCITY PRESSURE FROM TABLE 1606.2A IS
 24.7 PSF. TRUSS DRAWINGS ALSO LIST 15FT.
 AS MEAN ROOF HEIGHT. PLEASE CORRECT.
  
 4)RE: WALL ANCHOR DETAIL A/3 ON SHEET 3B
 REBENDING OF FLANGE ON GIRDER HANGER IS
 NOT ALLOWED BY MANUFACTURER. REBENDING
 CAN WEAKEN AND POSSIBLY FRACTURE THE
 METAL. ALSO, DUE TO THE PROXIMITY OF THE
 FASTENERS USED TO ANCHOR THE HANGER TO
 THE EDGE OF THE CONCRETE BEAM, THE
 CAPACITY OF THE HANGER NEEDS TO BE
 DERATED. PLEASE CORRECT.
  
 5) ON SHEET 2, THE INTERIOR BEARING WALL
 AT THE GARAGE IS NOT INDICATED WITH
 HATCH MARKS. PLEASE CORRECT.
  
 6) PROVIDE (2) COPIES OF KEY PLAN AND
 INSTALLATION SCHEDULE FOR STORM PANELS.
  
 7) PROVIDE THE COVER PAGES OF METRO-DADE
 PRODUCT APPROVAL FOR LAWSON SINGLE HUNG
 WINDOWS. ONLY THE APPROVED DRAWINGS WERE
 SUBMITTED.
  
 ************TRUSSES UNSAT***************
  
 1) THE WET SIGNATURE, DATE AND EMBOSSED
 SEAL OF THE ENGINEER IS REQUIRED ON EACH
 TRUSS DRAWING AND THE TRUSS LAYOUT, IN
 ADDITION TO HIS TITLE BLOCK.
 SIGNATURE STAMPS AND COPIES ARE NOT
 ACCEPTABLE. PLEASE CORRECT.
  
 2) GIRDER HANGER (GHP210HD) SPECIFIED
 FOR TRUSS FG1 IS RATED FOR UPLIFT OF
 1178#. TRUSS ENGINEERING INDICATES
 UPLIFTS OF 1500# AND 1300#. PLEASE
 CORRECT.
  
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-04-17 Cont ID  
Sent By rmcdouga Date 2001-04-17 Time 09:28 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-04-17 00:00:00OK PER SHIRLEY GRAHAM 4-2-01 RM