Plan Review Details - Permit 01031299
| Plan Review Stops For Permit 01031299 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-04-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-03 |
Time |
14:09 |
Rev Time |
3.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-03 00:00:00 | PROVISO: | | | PHASE 1 | | | GEE & JENSEN | | | 1)- SHEET 4 DETAIL B/C INDICATES FENCE | | | POST BUT NOT CLEAR AS TO FENCING MATER- | | | IAL. GAURDRAILS ARE REQUIRED(SBC 1022.4) | | | | | | PHASE II | | | MOCK . ROOS | | | 1)- PUMP STATION: STRUCTURAL CONTROL | | | HOUSE, STANDARD BUILDING CODE 1997, | | | CORRECT DATEON : DESIGNED TO MEET | | | ASCE 7-95.WALL & ROOF WINDSPEED 110 MPH. | | | A)- FABRICATED BUILDINGS REQUIRE | | | SIGNED & SEALED ENGINEER DRAWINGS | | | ARE REQUIRED FOR FABRICATED BUILD | | | INGS. | | | B)- FOUNDATION DETAILS? | | | | | | 2)- CHEMICAL STORAGE BUILDING: | | | PLANS INDICATE THAT A PREFABRICATED | | | METAL BUILDING WILL BE REQUIRED. | | | PREFABRICATED METAL STRUCTURES WILL | | | REQUIRE SIGNED & SEALED ENGINEERED | | | DRAWINGS BEFORE PEMITTING. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-04-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-02 |
Time |
21:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-02 |
Time |
21:40 |
Sent To |
|
|
| Notes |
| 2001-04-02 00:00:00 | ************** PROVISO *************** | | | | | | 1)NOTE: PLEASE CLARIFY GFI PROTECTION | | | FOR MAIN SERVICE PER 230-95. | | | | | | 2)NOTE: PLEASE NOTE THAT PLANS ARE | | | SHOWING FUTURE ATS AND GENERATOR. | | | PLEASE NOTE THAT PER 225-31 A | | | DISCONNECT IS REQ`D. 230-72, | | | 230,76,230-79.THIS A JUST A NOTE BECAUSE | | | IT MIGHT END UP CHANGING LAYOUT OF | | | ROOM. PLEASE CALL FOR ANY CLARIFICATION. | | | | | | 3)NOTE: PLEASE NOTE GROUNDING ELECTRODE | | | TO COLD WATER PIPE PER 250-50. | | | | | | PLEASE SUBMIT CLARIFICATION ON THE ABOVE | | | NOTES. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2001-04-02 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-04-02 |
Time |
09:51 |
Rev Time |
4.00 |
| Received By |
mamini |
Date |
2001-04-02 |
Time |
09:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-04-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-03 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-03 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2001-04-03 00:00:00 | 1) A PLAN AND PERMIT IS REQUIRED PRIOR | | | TO THE INSTALLATION OF THE EMERGENCY | | | GENERATOR AND FUEL STORAGE. THIS AREA | | | COULD BE LOCATED IN THE FIRE LIMITS | | | WHICH LIMITS THE AMOUNT OF FUEL THAT | | | CAN BE STORED ABOVEGROUND. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-04-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-03 |
Time |
15:01 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-04-03 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2001-04-04 00:00:00 | ******************PROVISO*************** | | | | | | DRAWING NO. 43-43-28-40 (SHEET 26 OF | | | 42), PLEASE PROVIDE INFORMATION ON | | | VENTILATION FOR PREFABRICATED METAL | | | STRUCTURE THAT HOUSES CHEMICAL STORAGE | | | AND FEED SYSTEMS. | | 2001-04-03 00:00:00 | NO HVAC PLANS SUBMITTED. SUBMIT PLANS | | | WITH MECHANICAL PERMIT APPLICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-04-03 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-04-03 |
Time |
15:38 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-03 00:00:00 | PROVISO: FOR BACK FLOW, DOMESTIC H20. | | 2001-04-01 00:00:00 | PLUMBING PLAN REVIEW, | | | BACK FLOW PROTECTION ON ALL POTABLE | | | WATER CONNECTIONS.PES |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-06-05 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-06-05 |
Time |
11:18 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|