Plan Review Details - Permit 01031299
Plan Review Stops For Permit 01031299
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-04-03 Cont ID  
Sent By jwitmer Date 2001-04-03 Time 14:09 Rev Time 3.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-03 00:00:00PROVISO:
 PHASE 1
 GEE & JENSEN
 1)- SHEET 4 DETAIL B/C INDICATES FENCE
 POST BUT NOT CLEAR AS TO FENCING MATER-
 IAL. GAURDRAILS ARE REQUIRED(SBC 1022.4)
  
 PHASE II
 MOCK . ROOS
 1)- PUMP STATION: STRUCTURAL CONTROL
 HOUSE, STANDARD BUILDING CODE 1997,
 CORRECT DATEON : DESIGNED TO MEET
 ASCE 7-95.WALL & ROOF WINDSPEED 110 MPH.
 A)- FABRICATED BUILDINGS REQUIRE
 SIGNED & SEALED ENGINEER DRAWINGS
 ARE REQUIRED FOR FABRICATED BUILD
 INGS.
 B)- FOUNDATION DETAILS?
  
 2)- CHEMICAL STORAGE BUILDING:
 PLANS INDICATE THAT A PREFABRICATED
 METAL BUILDING WILL BE REQUIRED.
 PREFABRICATED METAL STRUCTURES WILL
 REQUIRE SIGNED & SEALED ENGINEERED
 DRAWINGS BEFORE PEMITTING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-04-02 Cont ID  
Sent By dpalmer Date 2001-04-02 Time 21:40 Rev Time 0.00
Received By dpalmer Date 2001-04-02 Time 21:40 Sent To  
Notes
2001-04-02 00:00:00************** PROVISO ***************
  
 1)NOTE: PLEASE CLARIFY GFI PROTECTION
 FOR MAIN SERVICE PER 230-95.
  
 2)NOTE: PLEASE NOTE THAT PLANS ARE
 SHOWING FUTURE ATS AND GENERATOR.
 PLEASE NOTE THAT PER 225-31 A
 DISCONNECT IS REQ`D. 230-72,
 230,76,230-79.THIS A JUST A NOTE BECAUSE
 IT MIGHT END UP CHANGING LAYOUT OF
 ROOM. PLEASE CALL FOR ANY CLARIFICATION.
  
 3)NOTE: PLEASE NOTE GROUNDING ELECTRODE
 TO COLD WATER PIPE PER 250-50.
  
 PLEASE SUBMIT CLARIFICATION ON THE ABOVE
 NOTES. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-04-02 Cont ID  
Sent By mamini Date 2001-04-02 Time 09:51 Rev Time 4.00
Received By mamini Date 2001-04-02 Time 09:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-04-03 Cont ID  
Sent By mcarsill Date 2001-04-03 Time 13:34 Rev Time 0.00
Received By mcarsill Date 2001-04-03 Time 13:34 Sent To  
Notes
2001-04-03 00:00:001) A PLAN AND PERMIT IS REQUIRED PRIOR
 TO THE INSTALLATION OF THE EMERGENCY
 GENERATOR AND FUEL STORAGE. THIS AREA
 COULD BE LOCATED IN THE FIRE LIMITS
 WHICH LIMITS THE AMOUNT OF FUEL THAT
 CAN BE STORED ABOVEGROUND.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-04-04 Cont ID  
Sent By pkrauss Date 2001-04-03 Time 15:01 Rev Time 0.40
Received By pkrauss Date 2001-04-03 Time 15:01 Sent To  
Notes
2001-04-04 00:00:00******************PROVISO***************
  
 DRAWING NO. 43-43-28-40 (SHEET 26 OF
 42), PLEASE PROVIDE INFORMATION ON
 VENTILATION FOR PREFABRICATED METAL
 STRUCTURE THAT HOUSES CHEMICAL STORAGE
 AND FEED SYSTEMS.
2001-04-03 00:00:00NO HVAC PLANS SUBMITTED. SUBMIT PLANS
 WITH MECHANICAL PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-04-03 Cont ID  
Sent By pschmitz Date 2001-04-03 Time 15:38 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-04-03 00:00:00PROVISO: FOR BACK FLOW, DOMESTIC H20.
2001-04-01 00:00:00PLUMBING PLAN REVIEW,
 BACK FLOW PROTECTION ON ALL POTABLE
 WATER CONNECTIONS.PES

Review Stop Z ZONING
Rev No 1 Status P Date 2001-06-05 Cont ID  
Sent By sgraham Date 2001-06-05 Time 11:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***