Plan Review Details - Permit 01031191
Plan Review Stops For Permit 01031191
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-09 Cont ID  
Sent By jwitmer Date 2001-07-09 Time 16:58 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-13 Cont ID  
Sent By jwitmer Date 2001-04-13 Time 13:56 Rev Time 3.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-13 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01031191
 1714 DOUGLAS AV
 WEST PALM BEACH HOUSING
 AUTHORITY 655-3582 EX 11
  
 1)- CHANGE OF OCCUPANCY- PLANS WILL NEED
 TO BE SUBMITTED TO P B COUNTY FOR
 COUNTY IMPACT FEE REVIEW.
  
 2)- SBC 1013.1 WHERE CHANGES IN ELEVA-
 TION EXIST,ACCESS CORRIDORS, EXITS, AND
 EXIT DISCHARGES RAMPS WILL BE REQUIRED
 WHEN 12" OR LESS OCCURS. (BACK EGRESS)
  
 3)- SBC 306.1.2- INDICATE THEAGE OF
 THE OCCUPANTS TO USE THE BUILDING.
  
 4)- THE FREE STANDING CANOPY WILL RE-
 QUIRE A CERTIFICATE OF FLAME RESISTANCE
 (3103.1).
  
 5)- SSBC 905.1.1. A FIRE ALARM SYSTEM
 SHALL BE INSTALLED IN ACCORDANCE WITH
 NFPA 72 FOR GROUP E OCCUPANCY.
  
 6)- STORM SHUTTERS WILL REQUIRE THE FULL
 REPORT AND THE ASSOCIATED TECHNICAL
 DRAWINGS THAT ACCOMPANY THE REPORT. THE
 CITY ALSO REQUIRES A SHUTTER SCHEDULE,
 A COPY OF THE CITY POLICY IS ATTACHED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-08-08 Cont ID  
Sent By dpalmer Date 2001-08-08 Time 10:39 Rev Time 0.00
Received By dpalmer Date 2001-08-08 Time 10:39 Sent To  
Notes
2001-08-08 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ALL HANDWRITTEN
 CHANGES ON PLANS NEED TO BE DONE BY THE
 ARCH/ OF RECORD. PER FS/FAC 481.221
 THESE ARE CHANGES TO ORIGINAL SIGNED AND
 SEALED PLANS.
  
 PLEASE SUBMIT FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELELCTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-08 Cont ID  
Sent By dpalmer Date 2001-07-08 Time 12:34 Rev Time 0.00
Received By dpalmer Date 2001-07-08 Time 12:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-16 Cont ID  
Sent By dpalmer Date 2001-04-16 Time 12:15 Rev Time 0.00
Received By dpalmer Date 2001-04-16 Time 12:15 Sent To  
Notes
2001-04-16 00:00:00*****************UNSAT ***************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS. PLEASE CORRELATE WITH
 PANEL SCHEDULES THAT NEED TO BE
 SUBMITTED.
  
 2)NOTE: PLEASE NOTE THAT PER FS
 481.0221AND 471.025. ALL CHANGES ON
 PLANS THAT ARE SIGNED AND SEALED, NEED
 TO HAVE THOSE CHANGES DONE BY THAT
 ARCH/ENG OF RECORD
  
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 AIC RATING SHOWN FOR ONE MIAN DISCONNECT
 BUT NOT FOR OTHER OR PANELS.
  
 3)NOTE: PLEASE NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED. 215-5
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-04-03 Cont ID  
Sent By mamini Date 2001-04-03 Time 14:54 Rev Time 0.00
Received By mamini Date 2001-04-03 Time 14:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-06-26 Cont ID  
Sent By mcarsill Date 2001-06-26 Time 12:58 Rev Time 0.00
Received By mcarsill Date 2001-06-26 Time 12:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-04-05 Cont ID  
Sent By mcarsill Date 2001-04-05 Time 08:12 Rev Time 0.00
Received By mcarsill Date 2001-04-05 Time 08:12 Sent To  
Notes
2001-04-05 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 2) CODE ANALYSIS BOX INDICATES 1998
 EDITION OF THE LIFE SAFETY CODE. DO
 YOU MEAN 1997 OR 2000 EDITION.
 3) ANY CHANGES IN ELEVATION LESS THAN
 21 INCHES SHALL BE BY RAMPS. STAIRS IF
 PRESENT, SHOULD CONSIST OF THREE AT 7
 INCHES EACH.
 4) PLEASE INDICATE AGES OF CHILDREN AND
 PROPOSED HOURS OF OPERATION.
 5) NEW SHADE AWNING OVER PLAYGROUND IS
 TO BE FIRE RETARDANT IF PERSONS WILL
 BE UNDERNEATH IT.
 6) ON PAGE A001, SECTION K INDICATES
 NO PANIC HARDWARE. ON PAGE AE101, DOOR
 SCHEDULE, PANIC HARDWARE IS NOTED.
 PLEASE CLARIFY.
 7) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS WITH A PERMIT. CUT SHEETS,
 WIRING DIAGRAM AND BATTERY CALCULATIONS
 ARE TO BE PROVIDED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-28 Cont ID  
Sent By pkrauss Date 2001-06-28 Time 13:35 Rev Time 0.35
Received By pkrauss Date 2001-06-28 Time 13:28 Sent To  
Notes
2001-06-28 00:00:00CHANGED ENGINEER OF RECORD, JAMES R.
 HENRY MECHANICAL ENGINEER P.E.
 REPLACING HUGO LINARES.
  
 OUTSIDE AIR CALCULATIONS PER ENGINEER
 SIGNED, SEALED & DATED LETTER.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-04-12 Cont ID  
Sent By pkrauss Date 2001-04-11 Time 16:45 Rev Time 0.40
Received By pkrauss Date 2001-04-12 Time 12:52 Sent To  
Notes
2001-04-11 00:00:00 
  
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89 WITH MECHANICAL
 PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-07-07 Cont ID  
Sent By jleech Date 2001-07-07 Time 08:13 Rev Time 1.50
Received By jleech Date 2001-07-07 Time 08:13 Sent To  
Notes
2001-07-07 00:00:00PROVISO;
  
 AIR CHAMBERS SHALL COMPLY WITH 94 SPC
 607.8.2 AND 607.8.3.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-07 Cont ID  
Sent By pschmitz Date 2001-05-07 Time 15:40 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-07 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) SHT PL-100 GENERAL NOTES
 CODE REFERENCE STD PLBG CODE 1994
 HAND WRITTEN REFERENCE TO CPVC TO BE
 INCLUDED IN SPECIFICATIONS.
 (2) TWO WAY CO'S REQUIRED ON BLDG SEWER
 WITHIN 3' OF FOUNDATION WALL,SEC 710.4
 (3) SHTS PL-101,PL-901, NO MORE THAN 2
 FIXTURES ON 1/2" COLD WATER.
 NO MORE THAN 4 FIFTURES ON 1/2" HOT
 WATER, CNTY. WIDE AMEDMENTS TO THE 1994
 STD PLUMBING CODE.
 (4) MAXIM NUMBER OF FIXTURES UNITS ON
 BUILDING SEWERS AND BRANCHES,SEC 714.
 MIN SIZE FOR A WATER CLOSET DRAIN 3".
 NO MORE THAN 2 WATER CLOSETS ON 3"DRAIN.
 END OF COMMENTS. PAUL SCHMITZ
 QUESTIONS561-659-8096

Review Stop Z ZONING
Rev No 1 Status P Date 2001-04-03 Cont ID  
Sent By sgraham Date 2001-04-03 Time 09:22 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***