| Plan Review Stops For Permit 01031191 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-07-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-09 |
Time |
16:58 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-04-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-13 |
Time |
13:56 |
Rev Time |
3.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-13 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01031191 | | | 1714 DOUGLAS AV | | | WEST PALM BEACH HOUSING | | | AUTHORITY 655-3582 EX 11 | | | | | | 1)- CHANGE OF OCCUPANCY- PLANS WILL NEED | | | TO BE SUBMITTED TO P B COUNTY FOR | | | COUNTY IMPACT FEE REVIEW. | | | | | | 2)- SBC 1013.1 WHERE CHANGES IN ELEVA- | | | TION EXIST,ACCESS CORRIDORS, EXITS, AND | | | EXIT DISCHARGES RAMPS WILL BE REQUIRED | | | WHEN 12" OR LESS OCCURS. (BACK EGRESS) | | | | | | 3)- SBC 306.1.2- INDICATE THEAGE OF | | | THE OCCUPANTS TO USE THE BUILDING. | | | | | | 4)- THE FREE STANDING CANOPY WILL RE- | | | QUIRE A CERTIFICATE OF FLAME RESISTANCE | | | (3103.1). | | | | | | 5)- SSBC 905.1.1. A FIRE ALARM SYSTEM | | | SHALL BE INSTALLED IN ACCORDANCE WITH | | | NFPA 72 FOR GROUP E OCCUPANCY. | | | | | | 6)- STORM SHUTTERS WILL REQUIRE THE FULL | | | REPORT AND THE ASSOCIATED TECHNICAL | | | DRAWINGS THAT ACCOMPANY THE REPORT. THE | | | CITY ALSO REQUIRES A SHUTTER SCHEDULE, | | | A COPY OF THE CITY POLICY IS ATTACHED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-08-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-08 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-08 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2001-08-08 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT ALL HANDWRITTEN | | | CHANGES ON PLANS NEED TO BE DONE BY THE | | | ARCH/ OF RECORD. PER FS/FAC 481.221 | | | THESE ARE CHANGES TO ORIGINAL SIGNED AND | | | SEALED PLANS. | | | | | | PLEASE SUBMIT FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELELCTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-07-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-08 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-08 |
Time |
12:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-04-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-16 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-16 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2001-04-16 00:00:00 | *****************UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | #`S ON PLANS. PLEASE CORRELATE WITH | | | PANEL SCHEDULES THAT NEED TO BE | | | SUBMITTED. | | | | | | 2)NOTE: PLEASE NOTE THAT PER FS | | | 481.0221AND 471.025. ALL CHANGES ON | | | PLANS THAT ARE SIGNED AND SEALED, NEED | | | TO HAVE THOSE CHANGES DONE BY THAT | | | ARCH/ENG OF RECORD | | | | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | AIC RATING SHOWN FOR ONE MIAN DISCONNECT | | | BUT NOT FOR OTHER OR PANELS. | | | | | | 3)NOTE: PLEASE NOTE THAT NO LOAD | | | CALCULATIONS WERE SUBMITTED. 215-5 | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-04-03 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-04-03 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
2001-04-03 |
Time |
14:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-06-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-06-26 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-06-26 |
Time |
12:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-04-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-05 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-05 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2001-04-05 00:00:00 | 1) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | | COMPLY WITH CITY CODE REQUIREMENTS. | | | 2) CODE ANALYSIS BOX INDICATES 1998 | | | EDITION OF THE LIFE SAFETY CODE. DO | | | YOU MEAN 1997 OR 2000 EDITION. | | | 3) ANY CHANGES IN ELEVATION LESS THAN | | | 21 INCHES SHALL BE BY RAMPS. STAIRS IF | | | PRESENT, SHOULD CONSIST OF THREE AT 7 | | | INCHES EACH. | | | 4) PLEASE INDICATE AGES OF CHILDREN AND | | | PROPOSED HOURS OF OPERATION. | | | 5) NEW SHADE AWNING OVER PLAYGROUND IS | | | TO BE FIRE RETARDANT IF PERSONS WILL | | | BE UNDERNEATH IT. | | | 6) ON PAGE A001, SECTION K INDICATES | | | NO PANIC HARDWARE. ON PAGE AE101, DOOR | | | SCHEDULE, PANIC HARDWARE IS NOTED. | | | PLEASE CLARIFY. | | | 7) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS WITH A PERMIT. CUT SHEETS, | | | WIRING DIAGRAM AND BATTERY CALCULATIONS | | | ARE TO BE PROVIDED. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-06-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-28 |
Time |
13:35 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-06-28 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2001-06-28 00:00:00 | CHANGED ENGINEER OF RECORD, JAMES R. | | | HENRY MECHANICAL ENGINEER P.E. | | | REPLACING HUGO LINARES. | | | | | | OUTSIDE AIR CALCULATIONS PER ENGINEER | | | SIGNED, SEALED & DATED LETTER. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-04-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-11 |
Time |
16:45 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-04-12 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2001-04-11 00:00:00 | | | | | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER ASHRAE 62-89 WITH MECHANICAL | | | PERMIT APPLICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-07-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-07 |
Time |
08:13 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2001-07-07 |
Time |
08:13 |
Sent To |
|
|
| Notes |
| 2001-07-07 00:00:00 | PROVISO; | | | | | | AIR CHAMBERS SHALL COMPLY WITH 94 SPC | | | 607.8.2 AND 607.8.3. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-05-07 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-05-07 |
Time |
15:40 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-07 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | (1) SHT PL-100 GENERAL NOTES | | | CODE REFERENCE STD PLBG CODE 1994 | | | HAND WRITTEN REFERENCE TO CPVC TO BE | | | INCLUDED IN SPECIFICATIONS. | | | (2) TWO WAY CO'S REQUIRED ON BLDG SEWER | | | WITHIN 3' OF FOUNDATION WALL,SEC 710.4 | | | (3) SHTS PL-101,PL-901, NO MORE THAN 2 | | | FIXTURES ON 1/2" COLD WATER. | | | NO MORE THAN 4 FIFTURES ON 1/2" HOT | | | WATER, CNTY. WIDE AMEDMENTS TO THE 1994 | | | STD PLUMBING CODE. | | | (4) MAXIM NUMBER OF FIXTURES UNITS ON | | | BUILDING SEWERS AND BRANCHES,SEC 714. | | | MIN SIZE FOR A WATER CLOSET DRAIN 3". | | | NO MORE THAN 2 WATER CLOSETS ON 3"DRAIN. | | | END OF COMMENTS. PAUL SCHMITZ | | | QUESTIONS561-659-8096 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-04-03 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-04-03 |
Time |
09:22 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|