| Plan Review Stops For Permit 01031144 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-03-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-28 |
Time |
08:52 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-03-28 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2001-03-28 00:00:00 | NOTE:BATHROOMS SHALL HAVE WINDOWS WITH | | | NO LESS THAN 3 SQ. FT. OF OPEN | | | SPACE OR SHALL BE MECHANICALLY | | | EXHAUSTED, AS PER 97 SMC 503.3.1. | | | | | | ACCESS FOR AHU SHALL COMPLY WITH | | | 97 SMC 304.4.1, ACCESSIBLE BY AN | | | OPENING AS THE LARGEST PIECE OF | | | EQUIPMENT AND IN NO CASE LESS | | | THAN22" X 36" CONTINUOUS | | | OPENING TO THE EQUIPMENT AND ITS | | | CONTROLS. | | | | | | AIR HANDLER IN ATTIC REQUIRES AN | | | AUXILLLIARY DRAIN PAN WITH OVER- | | | FLOW PROTECTION BY MEANS OF A | | | FLOAT SWITCH OR DRAIN LINE IS | | | REQUIRED AS PER 97 SMC 304.8.6.1. |
|
|
|