| Plan Review Stops For Permit 01031095 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-03-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-28 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-28 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2001-03-28 00:00:00 | 1) A SEPARATE FIRE ALARM CONTROL PANEL | | | INSTALLATION WILL NOT BE ACCEPTED. | | | 2) DUCT SMOKE DETECTORS WHEN ACTIVATED | | | ARE TO SHUT DOWN THE AIR HANDLING | | | EQUIPMENT AND CAUSE THE FIRE ALARM | | | SYSTEM TO ACTIVATE. ACCORDING TO THE | | | NOTES DUCT SMOKE DETECTORS WILL ONLY | | | CAUSE A SUPERVISORY SIGNAL. | | | 3) SMOKE DETECTORS WHEN INSTALLED ARE TO | | | BE A MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 4) SYSTEM TO BE CLASS A OR FULLY | | | ADDRESSABLE. | | | 5) AN AS-BUILT SET OF PLANS ARE TO BE | | | SUBMITTED WITHOUT THE FIRE ALARM PANEL | | | SHOWN. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|