Plan Review Details - Permit 01031095
Plan Review Stops For Permit 01031095
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-03-28 Cont ID  
Sent By mcarsill Date 2001-03-28 Time 12:37 Rev Time 0.00
Received By mcarsill Date 2001-03-28 Time 12:37 Sent To  
Notes
2001-03-28 00:00:001) A SEPARATE FIRE ALARM CONTROL PANEL
 INSTALLATION WILL NOT BE ACCEPTED.
 2) DUCT SMOKE DETECTORS WHEN ACTIVATED
 ARE TO SHUT DOWN THE AIR HANDLING
 EQUIPMENT AND CAUSE THE FIRE ALARM
 SYSTEM TO ACTIVATE. ACCORDING TO THE
 NOTES DUCT SMOKE DETECTORS WILL ONLY
 CAUSE A SUPERVISORY SIGNAL.
 3) SMOKE DETECTORS WHEN INSTALLED ARE TO
 BE A MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
 4) SYSTEM TO BE CLASS A OR FULLY
 ADDRESSABLE.
 5) AN AS-BUILT SET OF PLANS ARE TO BE
 SUBMITTED WITHOUT THE FIRE ALARM PANEL
 SHOWN.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910