Plan Review Details - Permit 01030959
Plan Review Stops For Permit 01030959
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 18:23 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 18:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-06-24 Cont ID  
Sent By dpalmer Date 2001-06-24 Time 08:58 Rev Time 0.00
Received By dpalmer Date 2001-06-24 Time 08:58 Sent To  
Notes
2001-06-24 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT LOAD
 CALCUALTIONS THAT ARE SHOWN NEED TO BE
 DONE TO
 ART 220 OF THE 99 NEC. PLEASE LOAD
 CALCULATIONS PER ART 220.
  
 2)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 NEED TO SHOW EXISTING HOUSE SERVICE AS
 WELL. IS THERE A MAIN AT EXIST. PANEL?
 PLEASE SHOW GROUNDING AT MAIN HOUSE.
 YOU SHOW 3-#4`S COMING FROM A 200A
 DISC?YOU ARE SHOW #4 WITH 200A`S OF
 OCP.
  
 3) NOTE: PLEASE SHOW GROUNDING
 ELECTRODE GOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50. MISSING COLD WATER AT BOTH
 STRUCTURES.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT THESE PLANS THAT ARE
 BEING SUBMITTED ARE NOW SHOWING A NEW
 SERVICE AND THIS INFORMATION IS REQ`D.
  
 5) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF
 DISCONNECT AND PANEL(S). EQUIPMENT
 GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 6) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 THIS WAS ASKED FOR ON FIRST REVIEW.
  
 7)NOTE: PLEASE NOTE THAT ONLY ONE PANEL
 SCHEDULE WAS SUBMITTED AND LOAD
 CALCULATIONS NEED TO BE SHOWN FOR EACH
 PANEL. PLANS SHOW 60A FEED FOR MAIN
 HOUSE. ARE THERE ALL GAS APPLIANCES?
  
 8)NOTE: PLEASE NOTE THAT A/C EQUIPMNET
 IS MISSING FROM THE ELECTRICAL PLANS.
 NEED TO SHOW DISCONNECTS PER 440-11.
  
 9)NOTE: ,PLEASE NOTE THAT LOAD CALCS SHO
 W #12 AWG WITH 30A OCP? PLEASE CALRIFY.
 PLEASE CLARIFY SPECIAL EFFECT LIGHTING
 SHOWN W/ 2P50A AND #8?PLEASE SUBMIT
 ANY SPECS ON ANY SPECIAL LIGHTING
 EQUIPMENT BEING INSTALLED. PLANS DON'T
 SHOW ANY SPEC LIGHTING?
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-04 Cont ID  
Sent By dpalmer Date 2001-04-04 Time 19:20 Rev Time 0.00
Received By dpalmer Date 2001-04-04 Time 19:20 Sent To  
Notes
2001-04-04 00:00:00**************** UNSAT ***************
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 2)NOTE: PLEASE PROVIDE CLARIFICATION
 FORPOWER AND WHERE ITS COMING FROM.
 PLANS
 SHOW AN 100A PANEL AND NO OTHER DETAIL,
  
 3)NOTE: PLEASE NOTE, PLEASE SHOW ALL
 OUTLETS FOR GARAGE AS GFI/GFI PROTECTED
 PER 210-8.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5)NOTE: PLEASE PROVIDE CLARIFICATION ON
 GROUNDING/ AT DETACHED STRUCTURE.
  
 PLEASE PROVIDE THE ABOVE INFORMATION
 FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2001-09-19 Cont ID  
Sent By pkrauss Date 2001-09-19 Time 14:12 Rev Time 0.35
Received By pkrauss Date 2001-09-19 Time 14:12 Sent To  
Notes
2001-09-19 00:00:00MECHANICAL CONTRACTOR TO SUBMIT PLAN AND
 ENERGY CALCULATIONS WITH MECH PERMIT
 APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-08-23 Cont ID  
Sent By pkrauss Date 2001-08-23 Time 13:07 Rev Time 0.50
Received By pkrauss Date 2001-08-23 Time 13:07 Sent To  
Notes
2001-08-23 00:00:00*******************DENIED***************
  
  
 THE GARAGE SPACE SHALL NOT BE
 CONDITIONED WITH THE EQUIPMENT FROM THE
 REC ROOM.AS PER 1997 SMC 401.2, A
 SEPARATE AND INDIVIDUAL VENTILATION
 SYSTEM, WHICH IS NOT A PART OF ANY
 OTHER SYSTEM SHALL BE PROVIDED FOR
 VENTILATION OF EACH ROOM OR SPACE
 CONTAINING NOXIOUS GASES.
  
 GARAGE MAY HAVE A SEPARATE SYSTEM AND
 SHALL BE CONTOLLED BY A HUMIDISTAT.
 (FLORIDA ENERGY CODE).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-25 Cont ID  
Sent By pkrauss Date 2001-06-25 Time 14:34 Rev Time 0.35
Received By pkrauss Date 2001-06-25 Time 14:34 Sent To  
Notes
2001-06-25 00:00:00*******************DENIED***************
  
  
 THERE WILL BE NO MIXING OF AIR BETWEEN
 THE GARAGE AND THE REC ROOM / BATHROOM
 AREAS.THIS HAS POTENTIAL FOR CARBON
 MONOXIDE POISONING.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-03-22 Cont ID  
Sent By jleech Date 2001-03-22 Time 19:53 Rev Time 0.33
Received By jleech Date 2001-03-22 Time 19:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-07-09 Cont ID  
Sent By hpiskura Date 2001-07-09 Time 09:23 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-04-09 Cont ID  
Sent By jgomez Date 2001-04-09 Time 18:07 Rev Time 1.50
Received By jgomez Date 2001-04-09 Time 18:07 Sent To  
Notes
2001-04-09 00:00:00CHECKLIST:
 1-ONE AND TWO FAMILY DWELLINGS MAY NOT
 REQUIRE AN ARCHITECT OR ENGINEER
 PROVIDED THAT ENTIRE DWELLING CONFORMS
 TO A PRESCRIPTIVE STANDARD ADOPTED BY
 THE CITY: SSTD 10-97. THEREFORE,
 DESIGNER SHALL USE THIS BOOK TO
 DESIGN THE STRUCTURE.
 SECTION 104.2.3 OF CITY AMENDMENTS.
 2-DESIGNER TO PROVIDE HIS/HER NAME AND
 SIGNATURE ON ALL DRAWINGS AS REQUIRED
 BY SECTION 104.2.1 OF CITY AMENDMENTS.
 3-BRING DRAWINGS TO PALM BEACH COUNTY TO
 VERIFY IF NEED TO PAY IMPACT FEES.
 BRING COUNTY STAMPED DRAWINGS AND
 RECEIPT AS REQUIRED.
 4-DOOR FROM GARAGE TO BEDROOM IS NOT
 ALLOWED. SECTION 411.2.8 SBC 1997.
 5-CLEARLY SPECIFY WINDOW TYPES AND SIZES
 -SPECIFY DOOR SIZES.
 6-PROVIDE PRODUCT APPROVAL FOR:
 -EXTERIOR DOORS AND WINDOWS.
 -GARAGE DOORS WITH SIZES AS SHOWN ON
 PLANS AND ELEVATIONS.
 -FLAT ROOF SYSTEM TO BE USED.
 7-STORM PANELS:
 -PROVIDE PRODUCT APPROVAL.
 -PROVIDE KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE AS PER CITY
 SAMPLE ATTACHED.
 -CLEARLY INDICATE ON STORM PANEL
 DRAWINGS THE SPECIFIC MOUNTING
 CONDITIONS, ANCHOR TYPE AND SPACING TO
 BE USED ACCORDING TO THE MEAN ROOF
 HEIGHT, DESIGN PRESSURES, PANEL SPAN,
 EDGE DISTANCE, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (CONCRETE
 BLOCK).
 8-PROVIDE COMPLETE STRUCTURAL BUCK
 DETAILS FOR GARAGE DOORS, WINDOWS AND
 EXTERIOR DOORS.
 SECTION 104.2.2 OF CITY AMENDMENTS.
 9-PROVIDE ENERGY CALCS. AS REQUIRED BY
 THE FLORIDA ENERGY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.
 10-CLEARLY SPECIFY ON PLANS HOW THE
 OPENINGS FOR DOORS AND WINDOWS ARE
 REINFORCED.
 -SPECIFY HOW ARE BUILDING CORNERS
 REINFORCED.
 -PROVIDE BEAM AND LINTEL SCHEDULE.
 -CLARIFY IF ROOF IS GOING TO HAVE
 PARAPET WALLS OR NOT. AND HOW IS THE
 WATER GOING TO RUN OFF.
 11-PROVIDE A COMPLETE HURRICANE ANCHOR
 SCHEDULE FOR ROOF FRAMING. AND SPECIFY
 UPLIFT LOADS AS CALCULATED ACCORDING
 TO THE PRESCRIPTIVE METHOD SSTD 10-97.
 12-SPECIFY TYPE AND GRADE OF STRUCTURAL
 LUMBER TO BE USED.
 13-SPECIFY HOW THE ROOF IS GOING TO BE
 VENTILATED AS REQUIRED BY SECTION
 2309.7 OF SBC 1997.
 14-SPECIFY SAFETY GLASS (TEMPERED GLASS)
 FOR WINDOWS WITHIN 24" RADIOUS OF
 SWING DOORS AS REQUIRED BY SECTION
 2405.2 SBC 1997.
 15-ROOF SHEATHING TO BE 19/32" MIN. NOT
 1/2". ALSO, SPECIFY NAIL TYPE AND
 SPACING AS REQUIRED BY SECTION 2306 OF
 CITY AMENDMENTS TO SBC 1997.
 16-FLAT ROOF TO HAVE A MINIMUM SLOPE OF
 1/4" PER FT. SEC. 1503.1.2.3 SBC 1997.
 17-TOILET ROOM TO HAVE WINDOW WITH MIN.
 3 SQ. FT. OF OPEN AREA OR PROVIDE
 MECHANICAL VENTILATION AS REQUIRED BY
 SECTION 1203.4.2 OF SBC 1997.
 18-FILE NOTICE OF COMENCEMENT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-03-29 Cont ID  
Sent By sgraham Date 2001-03-29 Time 07:40 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-03-29 00:00:00SLEEPING ROOM NOT ALLOWED IN GARAGE IN
 SF7