2001-10-16 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01030953
 204 MONROE DR
 CONT : W L SCHIELE
 TEL: 762-0511
  
 1)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 ALL GLAZED OPENINGS SHALL REQUIRE A
 PRODUCT APPROVAL TESTING REPORT INDICAT-
 ING THAT THE PRODUCT HAS MET THE LARGE
 MISSLE RESISTANCE TESTING.
 IF THEY PRODUCT HASN'T BEEN TESTED THEN
 STORM SHUTTERS SHALL BE REQUIRED THAT
 HAVE MET THIS CRITERIA. THE CITY ACCEPTS
 EITHER SBCCI OR DADE COUNTY PRODUCT
 TESTING REPORTS.
 A)- MISSING REPORT FOR THE FRENCH DOORS
 SINGLE AS WELL AS DOUBLE DOORS.
 B)- MISSINGTEST REPORT FOR MULLIONS
 C)- STORM SHUTTERS WILL BE REQUIRED,
 THE PRODUCT TESTING REPORT IS ONLY
 PART OF THE INFORMATION REQUIRED, A
 KEY PLAN AND FASTENING SCHEDULE FOR
 EACH OPENING, A SAMPLE IS ATTACHED.
 D)- A COPY OF CASEMENT WINDOWS IS STILL
 INCLUDED IN THE PERMIT PACKAGE, IS
 THIS PRODUCT STILL TO BE INSTALLED
 INTO THE ADDITION?
  
 2)- STATE STATUTE 61 G1.001ARCHITECTS
 SHALL IDENITY ALL PLANS, SPECIFICATIONS
 OR REPORTS PREPARED OR ISSUED BY HIM &
 FILED FOR PUBLIC RECORD. 8 1/2X11 ARE
 NOT SEALED, WHITE OUT NOT ACCEPTED, NOR
 IS THE CHANGE SIGNED BY THE ARCHITECT.
  
 3)-SBC 104.2.2 ADDITIONAL INFORMATION
 SHEET A-3,ELEVATIONS DO NOT CORRALATE
 WITH THE FLOOR PLAN. WEST/ EAST ELE.
  
 4)- SHEET A-5 VS A-6 WALL SECTION HAVE
 A DISCREPANCY FOR THE FIRST FLOOR, FLOOR
 SYSTEM. IS IT STEM WALL OR MONOLITHIC?
  
 5)-SHEET A-3 DETAIL OF FRENCH DOORS &
 TRANSOM ABOVE, WHAT TYPE OF SUPPORT IS
 BETWEEN THE FRENCH DOORS AND TRANSOM
 ABOVE? HOW ARE THE ENDS TIED BACK INTO
 THE CBS STRUCTURE? THE LINTEL SCHEDULE
 DOES NOT INDICATE IF THERE IS A DOUBLE
 LINTEL IN THIS AREA?
  
 6)- SH. A-5 INDICATES A DOUBLE 2X12
 HEADER AT THE FIRST FLOOR AND THE SECOND
 FLOOR LEVELS, THE ATTACHMENT OF THE ST.
 ANGLE AT THE OUTSIDE CORNER INDICATES
 A 3X3X8X5/16" STEEL ANGLE, WHAT IS THE
 SET BACK FOR THE HOLE ATTACHMENT INTO
 THE CMU, EDGE DISTANCE VS DERATING? WHAT
 IS TO BE CONSIDERED FOR UPLIFT?
  
 7)- SHEET A-6 :
 A) SBC 1804.1.3: REQUIRES 12" FOOTING
 MIN BELOW GRADE.
 B)- SIZING OF LEDGER NOT GIVEN, WOOD
 AGAINST MASONRY / PRESSURE TREATED
 C)- ROOF FRAMING DETAIL: DOESN'T INDI-
 CATE THE LEDGER SIZE? ANCHORS OR
 SPACING?
 D)- ROOF SHEATHING THICKNESS?
 E)- SBC 2305.1.4.1. FIRE STOPPING AT
 FLOOR/ CEILING LEVELS.
  
 8)- SBC 2405.2 SAFETY GLASS REQUIRED,
 AT THE SHOWEWR ENCLOSURE.
  
 9)- SBC 2309.6 ATTIC ACCESS
 SBC 2309.7 ATTIC VENTILATION
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412
  
 WHEN PLANS ARE READY TO PERMIT THE CON-
 TRACTOR IS TO TAAKE THE PLANS TO THE
 COUNTY BUILDING DEPARTMENT FOR IMPACT
 FEES. AT THIS TIME RADON FEES ARE PAID
 TO THE CITY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-31 Cont ID  
Sent By jwitmer Date 2001-03-31 Time 09:01 Rev Time 1.99
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-31 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01030953
 204 MONROE DR
 W. L. SCHIELE
 762-0511
  
 1)- ENERGY FORMS NEED TO BE SIGNED BY
 THE OWNER OR AGENT THE AREA IS HIGHLIGHT
 ED.
  
 2)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 MISSING PRODUCT APPROVAL REPORTS OR
 ADDTIONAL INFORMATION REQUIRED FOR THE
 REPORTS ON HAND.
 A)- REPORT MISSING FOR THE AWNING TYPE
 WINDOW 2ND FL BATH.
 B)- FRENCH STYLE DOORS SINGLE AS WELL
 AS THE DOUBLE.
 C)- FIXED TRANSOM
 D)- MULLION FOR THE SINGLE HUNG WINDOW
 E)- ROOF TILE REPORT, SHEET A-3 NOTE
 MATCH EXISTING ROOF TILE.
 F)- STORM SHUTTER W.P.B. POLICY RE-
 QUIRES A KEY DIAGRAM AND A FASTEN-
 ING SCHEDULE FORSTORM SHUTTTERS,
 ATTACHED IS A COPY OF POLICY.
  
 3)- SBC 104.2.2 ADDITIONAL INFORMATION:
 SHEET A-3 ELEVATIONS ARE WRONG ACCORDING
 TO THE SURVEY. A-3 ARE ALSO MISSING THE
 SCUPPERS, DOWNSPOUTS & OVERFLOWS. A-1
 INDICATES THAT THE DOWNSPOUT WILL BE
 RELOCATED? WILL THE SCUPPER ALLOW THE
 WATER TO FLOW ONTO THE NEW ROOF, IS
 THERE A EXISTING OVERFLOW ALSO TO CONSID
 ER?
  
 4)- SHEET A-5 DISCREPANCY FIRST FLOOR
 FRAMING PLAN VS. A-6 WALL SECTION DEPICT
 ING A MONOLITHIC SLAB FOR THE FIRST
 FLOOR?
  
 5)- SH. A-5 DBL. 2X12 HEADER AT THE
 FIRST FLOOR AND SECOND FLOOR FL. THE
 ATTACHMENT AT THE OUTSIDE CORNER INDI-
 CATES 3X3X8X5/16 ST. ANGLE, THIS APPLICA
 TION WILL REQUIRE FLAT STEEL, ALSO INDI-
 CATE THE SETBACK FOR THE HOLE ATTACHMENT
 INTO THE CMU, EDGE DISTANCE VS. DERATING
  
 6)- SHEET A-6 :
 A) SBC 1804.1.3: REQUIRES 12" BELOW
 GRADE NOT 10".
 B) SIZING OF LEDGER NOT GIVEN, WOOD
 AGAINST CMU TO BE PRESSURE TREATED.
 C) ROOF FRAMING DETAIL: DOESN'T INDI-
 CATE THE LEDGER SIZE, ANCHORS OR
 SPACING.
 D) ROOF SHEATHING THICKNESS NOT INDI-
 CATED.
 E) SBC 2305.1.4.1. FIRESTOPPING AT
 FLOOR/ CEILING LEVELS.
  
 7)- SBC 2405.2 SAFETY GLASS REQUIRED
 AT THE SHOWER ENCLOSURE.
  
 8)- SBC 2309.6 ATTIC ACCESS
  
 9)- SBC 2309.7 ATTIC VENTILATION
  
 BUILDING PLAN REVIEW
 JIN WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-03-29 Cont ID  
Sent By dpalmer Date 2001-03-29 Time 20:22 Rev Time 0.00
Received By dpalmer Date 2001-03-29 Time 20:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-03-27 Cont ID  
Sent By jleech Date 2001-03-27 Time 07:13 Rev Time 0.00
Received By jleech Date   Time   Sent To  
Notes
2001-03-27 00:00:00NO A/C PLANS.A/C PLAN WITH APPLICATION.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-03-06 Cont ID  
Sent By kstevens Date 2002-03-06 Time 15:09 Rev Time 0.50
Received By kstevens Date 2002-03-06 Time 15:08 Sent To  
Notes
2002-03-06 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) ANY REVISIONS TO A SIGNED AND SEALED
 SET OF PLANS SHALL ALSO BE SIGNED AND
 SEALED BY ARCHITECT OF RECORD.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-03-27 Cont ID  
Sent By jleech Date 2001-03-27 Time 07:14 Rev Time 0.25
Received By jleech Date 2001-03-27 Time 07:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-03-23 Cont ID  
Sent By sgraham Date 2001-03-23 Time 13:21 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved