Plan Review Details - Permit 01030937
Plan Review Stops For Permit 01030937
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-27 Cont ID  
Sent By pkrauss Date 2001-04-27 Time 13:31 Rev Time 0.40
Received By pkrauss Date 2001-04-27 Time 13:31 Sent To  
Notes
2001-04-27 00:00:00*******************PROVISO**************
  
 AS PER AMENDED 1997 SMC 304.4.2,
 CONDENSER UNIT STAND SHALL BE A MINIMUM
 OF 18 INCHES FROM THE ROOF SURFACE TO
 THE BOTTOM OF SUPPORT RAIL TO
 CONDENSING UNIT.
  
 MINIMUM OF 10' BETWEENAIR INTAKE AND
 EXHAUST.1997 SMC 506.1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-28 Cont ID  
Sent By pkrauss Date 2001-03-27 Time 09:26 Rev Time 0.35
Received By pkrauss Date 2001-03-27 Time 09:26 Sent To  
Notes
2001-03-27 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE INFORMATION ON ROUTING OF
 PIPE TO CONDENSERS, LOCATION OF CONDENS
 ERS AND MANUFACTURER SPECIFICATIONS OF C
 ONDENER/WALK-IN COOLER.