| Plan Review Stops For Permit 01030937 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-04-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-27 |
Time |
13:31 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-04-27 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2001-04-27 00:00:00 | *******************PROVISO************** | | | | | | AS PER AMENDED 1997 SMC 304.4.2, | | | CONDENSER UNIT STAND SHALL BE A MINIMUM | | | OF 18 INCHES FROM THE ROOF SURFACE TO | | | THE BOTTOM OF SUPPORT RAIL TO | | | CONDENSING UNIT. | | | | | | MINIMUM OF 10' BETWEENAIR INTAKE AND | | | EXHAUST.1997 SMC 506.1. |
|
|