| Plan Review Stops For Permit 01030776 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-04-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-25 |
Time |
15:10 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-04-25 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2001-04-25 00:00:00 | PROVISO NOTES WRITTEN ON PLANS. | | | | | | AUXILIARY DRAIN PAN W/OVERFLOW PROTECT. | | | ACCESSIBILITY FOR SERVICE 97 SMC | | | 304.4.1CONVENIENCE OULET & LIGHT | | | REQUIRED FOR | | | ATTIC INSTALLATION AMENDED 97 SMC 304.4. | | | 2. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-03-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-20 |
Time |
15:22 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-03-20 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2001-03-20 00:00:00 | ******************DENIED**************** | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW.MUST SUBMIT AHU AND CONDENSING | | | UNIT EQUIPMENT I.E., MANUFACTURER, SIZE, | | | SEER, HEAT STRIP, ETC..NEED LOCATION | | | OF AHU AND ACCESS TO AHU.DESIGNATE | | | DUCT SIZE, GRILLES, CFM BEING | | | DISTRIBUTED, AND LOCATION OF RETURN AIR | | | GRILLE AS WELL AS CONDENSASTE DRAIN. |
|
|
|