Plan Review Details - Permit 01030713
Plan Review Stops For Permit 01030713
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-27 Cont ID  
Sent By jwitmer Date 2001-04-27 Time 09:42 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-02 Cont ID  
Sent By jwitmer Date 2001-04-02 Time 12:46 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-02 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01030713
 1011 UPLAND RD.
 KAISER CONSTRUCTION INC.
 439-0113
  
 1)- SBC 2304.1.1.3. EXISTING HEADER
 JOIST TO BE REPLACED WITH PRESSURE TREAT
 ED LUMBER, WOOD BEING SUBJECT TO DECAY &
 TERMITES.
  
 2)- SBC 1804.6.2.1. OPENING VENTILATION,
 INDICATE STEM WALL VENTING TO REPLACE
 THE VENTING CLOSED OFF BY THE SLAB ON
 GRADE CONSTRUCTION, ALSO IS THE ACCESS
 OR SCUTTLE HOLE STILL AVAILABLE (1804.6.
 2.2).
  
 3)- SBC 2308.1 MISSING HEADER INFORMA-
 TION FOR WINDOWS.
  
 4)- SBC 104.2.2. ADDITIONAL INFO., THE
 TYPICAL WALL SECTION SHOWS THE CEILING
 JOIST & RAFTERS ATTACHED TO A LEDGER
 WITH 3" LONG TAP CONS. THE PT LEDGER
 WIDTH IS 1 1/2" STUCCO 5/8 "LEAVES 7/8"
 EMBEDMENT? TAP CON ALSO DOESN'T MAKE A
 3" CONCRETE SCREW?
  
 5)- SBC 104.2.2 ADDITIONAL INFO., ARE
 THE WINDOWS BEING INSTALLED FLUSH WITH
 THE EXTERIOR SHEATHING OR ARE THEY GOING
 TO BE INSET ON BUCKS?
  
 6)- MISSING THE TOP & BOTTOM PLATE
 STRAPPING TO STUD?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-26 Cont ID  
Sent By dpalmer Date 2001-04-26 Time 18:19 Rev Time 0.00
Received By dpalmer Date 2001-04-26 Time 18:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-21 Cont ID  
Sent By dpalmer Date 2001-03-21 Time 20:31 Rev Time 0.00
Received By dpalmer Date 2001-03-21 Time 20:31 Sent To  
Notes
2001-03-21 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PER F.A.C.
 F.S. 61G15-23.002 PLANS THAT ARE SIGNED
 AND SEALED BY AN ENGINEER MUST CONATIN
 A TITLE BLOCK W/ INFORMATION REQ`D BY
 THAT STATUE.
  
 2) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC. PLEASE NOTE THAT
 YOU SHOW"J" FOR LIGHTING REQ`D FOR
 EGRESS. ONLY ONE IS REQ`D FOR BATH, SO
 ONLY ONE NEEDS TO BE SHOWN AS A LIGHT.
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 KITCHEN WALL.
  
 4)NOTE: PLEASE NOTE THAT AS PER SCALE
 OF DRAWING. ELEC PANEL IN CLOSET DOES
 NOTMEET 110-26/384-7. ELECTRCIAL
 CLEARENCE MUST BE MET AND MAINTAINED.
 PLEASE PLACE NOTE ON PLAN THAT THE AREA
 REQ`D BY 110-26 IS DEDICATED ELECTRICAL
 SPACE.
  
 5)NOTE: PLEASE MAKE NOTE THAT IS WAS RED
 LINED ON PLAN THAT THE OUTLET ON BATH OR
 CIRCUIT FOR BATH MUST BE 20A AND #12 AWG
 PLEASE SEE 210-11-C-3 FOR SPECIFIC
 REQ`MENTS.
  
 PLEASE MAKE THE CORRECTIONS FOR NOTES
 1-4 AND NOTE #5 CAN BE ADDED TO PLAN
 OR CAN BE RELINED ON NEXT REVIEW.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-03-19 Cont ID  
Sent By jleech Date 2001-03-19 Time 19:46 Rev Time 0.00
Received By jleech Date   Time   Sent To  
Notes
2001-03-19 00:00:00NO A/C DRAWINGS

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-03-19 Cont ID  
Sent By jleech Date 2001-03-19 Time 19:48 Rev Time 0.25
Received By jleech Date 2001-03-19 Time 19:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-04-30 Cont ID  
Sent By sgraham Date 2001-04-30 Time 10:44 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***