Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-03-20 Cont ID  
Sent By pkrauss Date 2001-03-20 Time 08:41 Rev Time 0.30
Received By pkrauss Date 2001-03-19 Time 08:48 Sent To  
Notes
2001-03-20 00:00:00***************PROVISO******************
  
 ATTIC ACCESS MUST COMPLY WITH 1997 SMC
 304.4.1,SIZE OF OPENING, AND SHALL BE
 NOT MORE THAN 20' (UNOBSTRUCTED) FROM
 THE CENTER LINE OF THE OPENING TO THE
 EQUIPMENT.
  
 AHU SHALL ALSO HAVE AN AUXILARY DRAIN
 PAN WITH OVER FLOW PROTECTION.