Plan Review Details - Permit 01030667
Plan Review Stops For Permit 01030667
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-25 Cont ID  
Sent By jwitmer Date 2001-04-25 Time 15:32 Rev Time 0.01
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-29 Cont ID  
Sent By jwitmer Date 2001-03-29 Time 16:49 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-29 00:00:00PERMIT # 01030667
 415 SUNSET RD
 MARION CONSTRUCTION
 659-5292
  
 1)- SBC 104.2.2: ADDITIONAL INFORMATION,
 MISSING COLUMN AND BEAM SCHEDULE, VERTIC
 AL DOWN RODS, SIZE & FREQUENCY, THE BEAM
 SIZE STEEL AND HOOP PLACEMENT OVER THE
 GARAGE DOOR AS WELL AS THE OPEN PORCH.
  
 2)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 SBC 1707.4 EXTERIOR WINDOWS & DOORS;
 GLAZED OPENINGS SHALL BE TESTED FOR A
 PERIOD OF TIME OF 10 SECONDS AT A LOAD
 OF 1.5 TIMES THE DESIGN PRESSURE. THIS
 ALSO INCLUDES GARAGE DOORS.SBCCI OR
 DADE COUNTY PRODUCT APPROVAL REPORTS
 ARE ACCEPTTED.
  
 3)- SBC 1707.4.1: GLAZED OPENINGS RE-
 QUIRE TESTING FOR LARGE MISSLE IMPACT
 TESTING, IF THE OPENINGS HAVEN'T
 RECEIVED TESTING STORM SHUTTERS WILL BE
 REQUIRED, CITY POLICY ALSO REQUIRES A
 SCHEDULE FOR INSTALATION.
  
 4)- SBC 104.2.2 MISSING INFORMATION ON
 THE TRUSS LAYOUT.
  
 5)- COUNTY IMPACT FEES NEED TO BE PAID
 AT THE COUNTY BUILDING DEPARTMENT.
  
 6)- STATE RADON FEES $12.00 TO BE PAID
 TO THE CITY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-19 Cont ID  
Sent By dpalmer Date 2001-04-19 Time 19:59 Rev Time 0.00
Received By dpalmer Date 2001-04-19 Time 19:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-23 Cont ID  
Sent By dpalmer Date 2001-03-23 Time 13:56 Rev Time 0.00
Received By dpalmer Date 2001-03-23 Time 13:56 Sent To  
Notes
2001-03-23 00:00:00*************** UNSAT ****************
  
 1) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC. GRADE LEVEL
 ACCESS FROM GARAGE.
  
 2) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF
 DISCONNECTAND PANEL AT DETACHED GARAGE.
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 3) NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50 AT DEATCHED GARAGE.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE AREANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-03-20 Cont ID  
Sent By jleech Date 2001-03-20 Time 18:52 Rev Time 0.00
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-03-20 Cont ID  
Sent By jleech Date 2001-03-20 Time 18:50 Rev Time 0.33
Received By jleech Date 2001-03-20 Time 18:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-03-19 Cont ID  
Sent By sgraham Date 2001-03-19 Time 11:19 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***