Plan Review Details - Permit 01030614
Plan Review Stops For Permit 01030614
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-09-19 Cont ID  
Sent By hpiskura Date 2001-09-19 Time 07:41 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-09-19 00:00:00THERE IS A NEED FOR SOME CODE
 STIPULATIONS:
 1)THE DESIGN INTENT IS TO HAVE 60
 TOWNHOUSE UNITS.SBC 202 DEFINES
 TOWNHOUSE AS A SINGLE FAMILY DWELLING
 CONSTRUCTED IN A SERIES OR GROUP OF
 ATTACHED UNITS WITH PROPERTY LINES
 SEPARATING EACH UNIT.
  
 THEREFORE THERE ARE 60 SEPARATE
 BUILDINGS, NOT "BUILDINGS A THROUGH F"
  
 2)FIRE SPRINKLERS.TO BE ACCREDITTED
 FOR BUILDING CODE PURPOSES, A FIRE
 SPRINKLER SYSTEM MUST BE DESIGNED TO
 NFPA 13 - 96. 13R AND 13D ARE NOT
 RECOGNIZED ALTERNATES.SEE SBC 903.2,
 (THE LAST SENTENCE, PARTICULARLY) AND
 TABLE 500 FOOTNOTE D.
  
 AS GROUP R3, (SINGLE FAMILY DWELLINGS)
 THEY WILL REQUIRE A FULL 13 SYSTEM ONLY
 IF THEY ARE 3 STORY AND TYPE VI OR V
 UNPROTECTED, SEE FOOTNOTE H TABLE 500.
  
 INARGUABLY, THE 13D AND 13R SYSTEMS ARE
 BENEFICIAL, HOWEVER IN NO WAY SHOULD
 THEY BE CONSIDERED AN EQUAL AND
 ALTERNATE FOR BUILDING CODE PURPOSES.
  
 PLEASE REFER TO THE EARLIER CODE
 COMMENTS AS SOME OF THEM STILL PERTAIN
 AND MUST BE COMPLIED WITH PRIOR TO
 OBTAINING PERMITS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-08-23 Cont ID  
Sent By hpiskura Date 2001-08-23 Time 14:32 Rev Time 0.00
Received By hpiskura Date 2001-08-23 Time 13:42 Sent To  
Notes
2001-08-23 00:00:00RE: 7/21/01 LETTER FROM R. KUPI.SEE
 SBC 504 FOR BUILDINGS LOCATED ON THE
 SAME PROPERTY AND THE REQUIREMENT FOR
 ASSUMED PROPERTY LINES.NOTE YOUR
 ASSUMED PROPERTY LINE AND THEN APPLY
 TABLE 600 REQUIREMENTS.
  
 F102.2.5 IS APPLICABLE SINCE THE
 TOWNHOUSE WALL IS EFFECTIVELY A ZERO
 LOT LINE AND NOT 30'FURTHER THE 13D
 SPRINKLER IS NOT CONSIDERED AS AN
 EXCEPTION.SEE SBC 903.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-07-20 Cont ID  
Sent By hpiskura Date 2001-07-20 Time 11:02 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-07-20 00:00:00REVIEW FOR TABLE 600 IS APPLIED TO EACH
 BLDG, (TOWNHOUSE UNIT) ON A PER FLOOR
 BASIS USING THE HEIGHT BETWEEN FLOOR
 AND CEILING TO DETERMINE AREA.
  
 THE FIRST FLOOR GARAGE DOOR OPENINGS
 WILL EXCEED THE ALLOWABLE 40% OPEN
 AREA.SBC 705.1.1.2 REQUIRES OPENINGS
 WITHIN 15' OF A PROPERTY LINE TO BE
 PROTECTED.BUILDINGS C, D & F WILL BE
 LOCATED WITHIN THE FIRE DISTRICT AND
 MUST BE A MINIMUM TYPE V CONSTRUCTION
 AND WILL NEED PROTECTED OPENINGS.
 BUILDINGS A, B & E WILL FALL OUTSIDE
 THE FIRE DISTRICT AND CAN BE VIEWED AS
 TYPE VI AND HAVE NON FIRE RATED
 OPENINGS.ALL MUST MEET THE PERCENTAGE
 OF AREA ALLOWED.
  
 THE FIRE DISTRICT FOR THIS PROPERTY
 FORMS A LINE APPROXIMATELY 140' EAST OF
 THE CENTERLINE OF DIXIE AND 140' NORTH
 OF TH
 E CENTERLINE OF FLAMINGO.
  
 SOME OF THE PRODUCT REPORTS PROVIDED ARE
 ILLEGIBLE OR EXPIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-17 Cont ID  
Sent By hpiskura Date 2001-04-17 Time 13:42 Rev Time 0.00
Received By hpiskura Date 2001-04-12 Time 10:43 Sent To  
Notes
2001-04-17 00:00:001 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY.CALL 233-5025 FOR MORE
 INFORMATION.
  
 2A RESIDENT INSPECTOR IS REQUIRED FOR
 THIS TYPE OF PROJECT.CALL DON NEELY
 FOR MORE INFORMATION.659-8096 X 8333.
  
 3 THE CITY USES THE 1997 STANDARD CODES
 TH THE EXCEPTION OF THE 1994 PLUMBING
 CODE.
  
 4SHOW THE FREE AREA OF THE 1 INCH
 SCREEN FOR THE SOFFIT VENT CALCULATIONS
 SHOWN ON SHEET A3.
  
 5THE TWO HOUR PARTY WALLS MUST PROJECT
 18" BEYOND THE COMBUSTIBLE VENER ON THE
 EXTERIOR WALSS.SEE SBC 704.5.1.2.
  
 6PLEASE PROVIDE THE TEST DATA FOR THE
 WINDOWS, DOORS AND ROOF COVERINGS.SEE
 SBC 104.2.
  
 7SHOW HOW THE GLAZED OPENINGS WILL
 COMPLY WITH THE CITY'S HURRICANE
 MISSILE IMPACT RESISTANCE POLICY.
  
 8SHOW THE TERMITE TREATMENT
 SPECIFICATION FOR THE SOIL UNDER THE
 BUILDINGS.SBC 2304.
  
 9THE BUILDINGS FACING EACH OTHER MUST
 COMPLY WITH SBC TABLE 600 AS TO THE
 PERCENTAGE OF WALL AREA THAT MAY HAVE
 OPENINGS.
  
 10THE FIRE SPRINKLER DEWSIGN MUST BE
 INCLUDED WITH THE PERMIT PLANS.FS
 553.79(2).

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-03-21 Cont ID  
Sent By btrobaug Date 2003-03-21 Time 09:28 Rev Time 0.75
Received By btrobaug Date 2003-03-21 Time 09:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-31 Cont ID  
Sent By dpalmer Date 2001-07-31 Time 19:37 Rev Time 0.00
Received By dpalmer Date 2001-07-31 Time 19:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-05 Cont ID  
Sent By dpalmer Date 2001-04-06 Time 21:47 Rev Time 0.00
Received By dpalmer Date 2001-04-05 Time 21:47 Sent To  
Notes
2001-04-06 00:00:00****************UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PLANS SHOW NO
 MAINS FOR PANELS OF EACH UNIT? SHOWS
 MLOMAINS REQ`D PER 225-31
  
 2)NOTE: PLEASE NOTE MISSING OUTLETS IN
 SOME UNITS REQ`D BY 210-52
  
 3)NOTE: PLEASE NOTE THE EQUIPMENT
 GROUNDING CONDUCTOR SHOWN BETWEEN
 METERCAN AND PANEL. EQUIPMENT GROUND IS
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT. INSTALLATION SHOWS NEUTRAL
 BEING PARALLED.
  
 4)NOTE: PLANS ARE MISSING DETAIL FOR
 FEEDS TO ALL HOUSE PANELS. WIRE,METERS
 CONDUITS,,,ETC. PLEASE SHOW LOCATIONS
 OF ALL ON PLAN. GROUNDING DETAIL PER
 250-50
  
 5)NOTE: PLEASE NOTE THAT ALL THE HEIGHT
 REQUIREMENTS FOR DEVICES NEED TO BE
 SHOWN ON PLANS PER F.H.A.R. 24CFR
 100.205
 PLEASE MAKE NOTE ON EACH SHEET FOR
 SEPARATE UNITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS ,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-07-11 Cont ID  
Sent By mamini Date 2001-07-11 Time 08:03 Rev Time 0.00
Received By mamini Date 2001-07-11 Time 08:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-09-13 Cont ID  
Sent By mcarsill Date 2001-09-13 Time 08:40 Rev Time 0.00
Received By mcarsill Date 2001-09-13 Time 08:40 Sent To  
Notes
2001-09-13 00:00:001) FIRE UNDERGROUND LINE PLAN DISPLAYS
 BUILDING FIRE DEPARTMENT CONNECTIONS
 BUT THE NOTES ON THE SAME PAGE STATES
 THAT A SINGLE 1/2 FDC SHALL BE PROVIDED
 AT EACH UNIT. PLEASE CORRELATE
 INFORMATION. ALSO ONLY SINGLE 2 1/2
 CONNECTIONS WILL BE ALLOWED.
 2) ACCORDING TO DOCUMENTS, EACH UNIT
 WILL HAVE A SECURITY SYSTEM THAT WILL
 BE TIED INTO THE FLOW AND TAMPER
 SWITCHES. HOW DOES THIS WORK AND THERE
 APPEARS TO BE SOME CONFUSION REGARDING
 THIS MATTER. THE FIRE SPRINKLER SYSTEMS
 ARE REQUIRED SO THIS MEANS THAT THE
 FIRE SPRINKLER MONITORING IS THEREFORE
 REQUIRED. WHAT HAPPENS IF A TENANTS
 SECURITY IS OUT OF SERVICE OR THE
 SECURITY SYSTEM IS DISCONTINUED. WHAT
 CODE PROVISIONS ALLOWS THIS ARRANGEMENT
 AND HOW DOES IF AFFECT LISTING OF
 EQUIPMENT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-07-05 Cont ID  
Sent By mcarsill Date 2001-07-05 Time 17:17 Rev Time 0.00
Received By mcarsill Date 2001-07-05 Time 17:17 Sent To  
Notes
2001-07-05 00:00:00IT APPEARS THAT ALL PREVIOUS COMMENTS
 BY THE FIRE RESCUE DEPARTMENT HAS
 BEEN MITIGATED.
  
 1) PLEASE CLARIFY IN WRITING TO THIS
 OFFICE IF INDIVIDUAL FIRE DEPARTMENT
 CONNECTIONS WILL BE PROVIDED. PLANS
 SEEM TO SUGGEST INDIVIDUAL ONES AND
 COMMON ONES FOR THE BUILDINGS OR UNITS.
 2) COULD NOT LOCATE FIRE SPRINKLER
 MONITORING DEVICES FOR EACH BUILDING.
 3) PLEASE BE ADVISED THAT CITY CODE
 SECTION 11-4 REQUIRES THAT NO DEVICES
 BE PLACED WITHIN 18 FEET OF FIRE
 HYDRANTS.
 4) ALSO PLEASE BE ADVISED THAT THE
 PROPERTY APPEARS TO BE LOCATED IN THE
 CITY FIRE LIMITS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-03-27 Cont ID  
Sent By mcarsill Date 2001-03-27 Time 12:09 Rev Time 0.00
Received By mcarsill Date 2001-03-27 Time 12:09 Sent To  
Notes
2001-03-27 00:00:001) WRONG BUILDING CODE EDITION
 REFERENCED. SHOULD READ 1997 EDITION
 INSTEAD OF 1994.
 2) FIRE HYDRANTS NOT SHOWN ON SITE PLAN.
 3) BUILDING ADDRESSES NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESSES
 TO COMPLY WITH CITY CODE REQUIREMENTS.
 4) HOW IS COMBUSTIBLE LINT REMOVED FROM
 THE INDIVIDUAL DRYER VENT PIPES.
 5) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 DRAWINGS. PLEASE BE ADVISED THAT FS
 553.895 (2) REQUIRES ALL NEW BUILDINGS
 THREE OR MORE STORIES IN HEIGHT
 REGARDLESS OF OCCUPANCY TO BE PROTECTED
 BY AN AUTOMATIC FIRE SPRINKLER SYSTEM.
 6) THE REQUIRED FIRE SPRINKLER SYSTEM(S)
 ARE TO BE MONITORED BY A LICENSED UL
 LISTED CENTRAL STATION APPROVED BY THE
 FIRE RESCUE DEPARTMENT. THE MONITORING
 REQUIREMENT IS BOTH BY BUILDING AND FIRE
 CODE REGULATIONS.
 7) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR UNITS.
 8) PLEASE PROVIDE FLAME SPREAD
 INFORMATION FOR CEDAR SHAKES PLANNED FOR
 USE.
 9) EACH INDIVIDUAL UNIT TO COMPLY WITH
 ONE AND TWO FAMILY DWELLINGS PER THE
 LIFE SAFETY CODE 1985 EDITION IF THEY
 PLATTED INDIVIDUALLY. IF THEY ARE NOT
 PLATTED INDIVIDUALLY, THEN THE
 REQUIREMENTS FOR NEW APARTMENTS PER THE
 LIFE SAFETY CODE 1985 EDITION ARE
 APPLICABLE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-23 Cont ID  
Sent By pkrauss Date 2001-07-23 Time 14:45 Rev Time 1.30
Received By pkrauss Date 2001-07-23 Time 13:45 Sent To  
Notes
2001-07-23 00:00:00*******************PROVISO**************
  
  
 FIRE DAMPERS SHALL COMPLY WITH UL 555
 AND SHALL BEAR THE LABEL OF ANY
 APPROVED TESTING AGENCY.
  
 NOTE:PLANS DO NOT INDICATE MEANS OF
 VENTILATION FOR THE CABANAS AT
 THE POOL.PLEASE SUBMIT EXHAUST
 FANS AND HOW AIR MAKE-UP WILL BE
 MAINTAINED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-04-19 Cont ID  
Sent By pkrauss Date 2001-04-19 Time 12:13 Rev Time 2.30
Received By pkrauss Date 2001-04-19 Time 10:37 Sent To  
Notes
2001-04-19 00:00:00*******************DENIED***************
  
  
 APARTMENTS:
  
 1.DRYER VENTS SHALL NOT EXCEED 25'
 FROM DRYER LOCATION TO WALL OR CAP.
 THERE WILL BE A 2 1/2 FT DEDUCTION
 FOR EVERY 45 DEGREE OFFSET & A 5 FT
 DEDUCTION FOR EVERY 90 DEGREE OFF-
 SET.1997 SMC 509.3.
  
 2.EXHAUST DUCTS FOR DRYERS SHALL
 COMPLY WITH 1997 SMC 509.1, FOR
 THE ASSEMBLY/CONTRUCTION OF EXHAUST
 DUCT.PLEASE INDICATE ANY ACCESS
 DOORS OR METHOD USED TO CLEAN LINT
 FROM DUCT.
  
 3.PLEASE INDICATE ON PLAN WHICH A/C
 UNIT GOES TO WHICH APARTMENT.
  
 4.PLAN INDICATES A SUPPLY DUCT
 DROPING INTO GARAGE AREA TO SUPPLY
 THE FIRST FLOOR. WHERE THE DUCT
 PENETRATES THE WALL FROM THE GARAGE
 INTO THE BATHROOM WILL REQUIRE A
 FIRE DAMPER IF THIS IS A RATED WALL
 (SEE DRAWING A.9 & AC.1, 1ST FLOOR)
 PLEASE PROVIDE MANUFACTURE SPECS
 AND MOUNTING DETAILS FOR ANY FIRE
 DAMPERS.FIRE DAMPERS MUST BE
 IDENTIFIED ON PLAN.
  
 5.DRAWING AC.10, DETAIL FOR SUSPENDED
 A/C UNIT & AUX. DRAIN PAN DETAIL,
 SPECIFY WHERE THE AUXILIARY DRAIN
 WILL TERMINATE.SHALL COMPLY WITH
 1997 SMC 304.8.6.1, SEPERATE DRAIN
 SHALL BE EXTENDED FROM PAN AND
 TERMINATING AT A CONSPICUOUS POINT
 TO SERVE AS AN ALARM THAT REGULAR
 DRAIN IS RESTRICTED. A FLOAT SWITCH
 IN LIEU OF DRAIN LINE MAY BE USED.
  
 6.AHU'S SHALL COMPLY WITH 1997 SMC
 304.4.2, IN ATTIC A LIGHT SHALL BE
 ON THE SERVICE SIDE OF EQUIPMENT
 WHICH IS CONTROLLED BY A SWITCH
 LOCATED AT THE ACCESS OPENING.
  
 7.CONDENSER UNITS SHALL COMPLY WITH
 1997 SMC 304.7.2, A MINIMUM OF 30"
 OF CLEAR SPACE ON THE SERVICE SIDE
 FOR INSPECTION AND SERVICING.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-08-18 Cont ID  
Sent By kstevens Date 2001-08-18 Time 11:06 Rev Time 0.00
Received By kstevens Date 2001-08-18 Time 11:06 Sent To  
Notes
2001-08-18 00:00:00PASSED/PROVISO
  
 1) PER LETTER DATED AUGUST 6, 2001,
 SEPARATE PERMIT TO BE SUBMITTED FOR POOL
 CABANA REST ROOMS. PALM BEACH COUNTY
 HEALTH DEPT. PLAN REVIEW AND COMMENTS
 PRIOR TO PLUMBING PLAN REVIEW.
  
 2) FULL IRRIGATION PLANS TO BE SUBMITTED
 FOR IRRIGATION PERMIT APPLICATION.
 SEPARATE PERMIT FOR BACKFLOWS. TO BE
 INSTALLED BY PLUMBING CONTRACTOR.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-07-19 Cont ID  
Sent By pschmitz Date 2001-07-19 Time 08:23 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-07-19 00:00:00PLUMBING PLAN REVIEW,DENIED.
 (1) PREVIOUS COMMENTS DATED 04-26-01,
 SHT P-1 NOTE (14) AND P-2 THRU P-10,
 WATER HAMMER ARRESTORS TO BE INSTALLED
 AS PER MANFACTURE INSTRUTIONS,NOT AT THE
 HIGH POINT.USE WATER HAMMER ARRESTOR
 STD PDI-201 FOR SIZE AND PLACEMENT.
 (2A) SHT A-62, CABANA REST RM'S,PALM BCH
 CNTY HEALTH DEPT, PLAN REVEIEW AND
 COMMMENTS PRIOR TO PLUMBING PLAN REVIEW.
 (2B) COMPLY W/FACBC SEC 4.1.2(2) ACCESS-
 IBLE SITE AND EXTERIOR FACILITIES.
 SEC 4.2.2.1 DOOR'S, CLEAR FLR SPACE,W/C.
 (3) IRRIGATION PLANS & LOCATION OF BACK
 FLOW PREVENTER.
 END OF COMMENTS PAUL CHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-04-26 Cont ID  
Sent By kstevens Date 2001-04-26 Time 18:05 Rev Time 2.50
Received By pschmitz Date 2001-04-26 Time 18:04 Sent To  
Notes
2001-04-26 00:00:00PLUMBING PLAN REVIEW. SPC-94
  
 FAILED
  
 (1) TYPICAL WATER RISER DIAGRAMS. AIR-
 CHAMBERS TO COMPLY WITH 607.8.3 AND
 BE ACCESSABLE AND RECHARGEABLE.
  
 (2) PAGE P.2 WHERE DOES THE VENT FROM
 THE POWDER ROOM TERMINATE?
  
 (3) CIVIL PLANS WITH SITE SEWER, WATER,
 ECT. NOT INCLUDED WITH PLANS AS
 INDICATED ON SHEET SCHEDULE.
  
 REVIEW BY KEN STEVENS. (561) 659-8096
 EXT. 8377

Review Stop Z ZONING
Rev No 2 Status N Date 2003-09-15 Cont ID  
Sent By mmclean Date 2003-09-15 Time 09:08 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-09-15 00:00:009/15/03 IT'S IN BIN FOR PICKUP

Review Stop Z ZONING
Rev No 1 Status F Date 2001-08-01 Cont ID  
Sent By sgraham Date 2001-08-01 Time 08:26 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-08-01 00:00:00NEED RECORDED PLATS