| Plan Review Stops For Permit 01030614 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-09-19 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-09-19 |
Time |
07:41 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-19 00:00:00 | THERE IS A NEED FOR SOME CODE | | | STIPULATIONS: | | | 1)THE DESIGN INTENT IS TO HAVE 60 | | | TOWNHOUSE UNITS.SBC 202 DEFINES | | | TOWNHOUSE AS A SINGLE FAMILY DWELLING | | | CONSTRUCTED IN A SERIES OR GROUP OF | | | ATTACHED UNITS WITH PROPERTY LINES | | | SEPARATING EACH UNIT. | | | | | | THEREFORE THERE ARE 60 SEPARATE | | | BUILDINGS, NOT "BUILDINGS A THROUGH F" | | | | | | 2)FIRE SPRINKLERS.TO BE ACCREDITTED | | | FOR BUILDING CODE PURPOSES, A FIRE | | | SPRINKLER SYSTEM MUST BE DESIGNED TO | | | NFPA 13 - 96. 13R AND 13D ARE NOT | | | RECOGNIZED ALTERNATES.SEE SBC 903.2, | | | (THE LAST SENTENCE, PARTICULARLY) AND | | | TABLE 500 FOOTNOTE D. | | | | | | AS GROUP R3, (SINGLE FAMILY DWELLINGS) | | | THEY WILL REQUIRE A FULL 13 SYSTEM ONLY | | | IF THEY ARE 3 STORY AND TYPE VI OR V | | | UNPROTECTED, SEE FOOTNOTE H TABLE 500. | | | | | | INARGUABLY, THE 13D AND 13R SYSTEMS ARE | | | BENEFICIAL, HOWEVER IN NO WAY SHOULD | | | THEY BE CONSIDERED AN EQUAL AND | | | ALTERNATE FOR BUILDING CODE PURPOSES. | | | | | | PLEASE REFER TO THE EARLIER CODE | | | COMMENTS AS SOME OF THEM STILL PERTAIN | | | AND MUST BE COMPLIED WITH PRIOR TO | | | OBTAINING PERMITS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-08-23 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-23 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2001-08-23 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2001-08-23 00:00:00 | RE: 7/21/01 LETTER FROM R. KUPI.SEE | | | SBC 504 FOR BUILDINGS LOCATED ON THE | | | SAME PROPERTY AND THE REQUIREMENT FOR | | | ASSUMED PROPERTY LINES.NOTE YOUR | | | ASSUMED PROPERTY LINE AND THEN APPLY | | | TABLE 600 REQUIREMENTS. | | | | | | F102.2.5 IS APPLICABLE SINCE THE | | | TOWNHOUSE WALL IS EFFECTIVELY A ZERO | | | LOT LINE AND NOT 30'FURTHER THE 13D | | | SPRINKLER IS NOT CONSIDERED AS AN | | | EXCEPTION.SEE SBC 903.2. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-07-20 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-07-20 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-20 00:00:00 | REVIEW FOR TABLE 600 IS APPLIED TO EACH | | | BLDG, (TOWNHOUSE UNIT) ON A PER FLOOR | | | BASIS USING THE HEIGHT BETWEEN FLOOR | | | AND CEILING TO DETERMINE AREA. | | | | | | THE FIRST FLOOR GARAGE DOOR OPENINGS | | | WILL EXCEED THE ALLOWABLE 40% OPEN | | | AREA.SBC 705.1.1.2 REQUIRES OPENINGS | | | WITHIN 15' OF A PROPERTY LINE TO BE | | | PROTECTED.BUILDINGS C, D & F WILL BE | | | LOCATED WITHIN THE FIRE DISTRICT AND | | | MUST BE A MINIMUM TYPE V CONSTRUCTION | | | AND WILL NEED PROTECTED OPENINGS. | | | BUILDINGS A, B & E WILL FALL OUTSIDE | | | THE FIRE DISTRICT AND CAN BE VIEWED AS | | | TYPE VI AND HAVE NON FIRE RATED | | | OPENINGS.ALL MUST MEET THE PERCENTAGE | | | OF AREA ALLOWED. | | | | | | THE FIRE DISTRICT FOR THIS PROPERTY | | | FORMS A LINE APPROXIMATELY 140' EAST OF | | | THE CENTERLINE OF DIXIE AND 140' NORTH | | | OF TH | | | E CENTERLINE OF FLAMINGO. | | | | | | SOME OF THE PRODUCT REPORTS PROVIDED ARE | | | ILLEGIBLE OR EXPIRED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-04-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-04-17 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2001-04-12 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2001-04-17 00:00:00 | 1 IMPACT FEES MUST BE PAID TO PALM BEACH | | | COUNTY.CALL 233-5025 FOR MORE | | | INFORMATION. | | | | | | 2A RESIDENT INSPECTOR IS REQUIRED FOR | | | THIS TYPE OF PROJECT.CALL DON NEELY | | | FOR MORE INFORMATION.659-8096 X 8333. | | | | | | 3 THE CITY USES THE 1997 STANDARD CODES | | | TH THE EXCEPTION OF THE 1994 PLUMBING | | | CODE. | | | | | | 4SHOW THE FREE AREA OF THE 1 INCH | | | SCREEN FOR THE SOFFIT VENT CALCULATIONS | | | SHOWN ON SHEET A3. | | | | | | 5THE TWO HOUR PARTY WALLS MUST PROJECT | | | 18" BEYOND THE COMBUSTIBLE VENER ON THE | | | EXTERIOR WALSS.SEE SBC 704.5.1.2. | | | | | | 6PLEASE PROVIDE THE TEST DATA FOR THE | | | WINDOWS, DOORS AND ROOF COVERINGS.SEE | | | SBC 104.2. | | | | | | 7SHOW HOW THE GLAZED OPENINGS WILL | | | COMPLY WITH THE CITY'S HURRICANE | | | MISSILE IMPACT RESISTANCE POLICY. | | | | | | 8SHOW THE TERMITE TREATMENT | | | SPECIFICATION FOR THE SOIL UNDER THE | | | BUILDINGS.SBC 2304. | | | | | | 9THE BUILDINGS FACING EACH OTHER MUST | | | COMPLY WITH SBC TABLE 600 AS TO THE | | | PERCENTAGE OF WALL AREA THAT MAY HAVE | | | OPENINGS. | | | | | | 10THE FIRE SPRINKLER DEWSIGN MUST BE | | | INCLUDED WITH THE PERMIT PLANS.FS | | | 553.79(2). |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-03-21 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-03-21 |
Time |
09:28 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2003-03-21 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-07-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-31 |
Time |
19:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-31 |
Time |
19:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-04-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-06 |
Time |
21:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-05 |
Time |
21:47 |
Sent To |
|
|
| Notes |
| 2001-04-06 00:00:00 | ****************UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS SHOW NO | | | MAINS FOR PANELS OF EACH UNIT? SHOWS | | | MLOMAINS REQ`D PER 225-31 | | | | | | 2)NOTE: PLEASE NOTE MISSING OUTLETS IN | | | SOME UNITS REQ`D BY 210-52 | | | | | | 3)NOTE: PLEASE NOTE THE EQUIPMENT | | | GROUNDING CONDUCTOR SHOWN BETWEEN | | | METERCAN AND PANEL. EQUIPMENT GROUND IS | | | ONLY INSTALLED AFTER THE FIRST MEANS OF | | | DISCONNECT. INSTALLATION SHOWS NEUTRAL | | | BEING PARALLED. | | | | | | 4)NOTE: PLANS ARE MISSING DETAIL FOR | | | FEEDS TO ALL HOUSE PANELS. WIRE,METERS | | | CONDUITS,,,ETC. PLEASE SHOW LOCATIONS | | | OF ALL ON PLAN. GROUNDING DETAIL PER | | | 250-50 | | | | | | 5)NOTE: PLEASE NOTE THAT ALL THE HEIGHT | | | REQUIREMENTS FOR DEVICES NEED TO BE | | | SHOWN ON PLANS PER F.H.A.R. 24CFR | | | 100.205 | | | PLEASE MAKE NOTE ON EACH SHEET FOR | | | SEPARATE UNITS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS , | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-07-11 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-07-11 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
2001-07-11 |
Time |
08:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2001-09-13 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-13 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-13 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2001-09-13 00:00:00 | 1) FIRE UNDERGROUND LINE PLAN DISPLAYS | | | BUILDING FIRE DEPARTMENT CONNECTIONS | | | BUT THE NOTES ON THE SAME PAGE STATES | | | THAT A SINGLE 1/2 FDC SHALL BE PROVIDED | | | AT EACH UNIT. PLEASE CORRELATE | | | INFORMATION. ALSO ONLY SINGLE 2 1/2 | | | CONNECTIONS WILL BE ALLOWED. | | | 2) ACCORDING TO DOCUMENTS, EACH UNIT | | | WILL HAVE A SECURITY SYSTEM THAT WILL | | | BE TIED INTO THE FLOW AND TAMPER | | | SWITCHES. HOW DOES THIS WORK AND THERE | | | APPEARS TO BE SOME CONFUSION REGARDING | | | THIS MATTER. THE FIRE SPRINKLER SYSTEMS | | | ARE REQUIRED SO THIS MEANS THAT THE | | | FIRE SPRINKLER MONITORING IS THEREFORE | | | REQUIRED. WHAT HAPPENS IF A TENANTS | | | SECURITY IS OUT OF SERVICE OR THE | | | SECURITY SYSTEM IS DISCONTINUED. WHAT | | | CODE PROVISIONS ALLOWS THIS ARRANGEMENT | | | AND HOW DOES IF AFFECT LISTING OF | | | EQUIPMENT. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-07-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-05 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-05 |
Time |
17:17 |
Sent To |
|
|
| Notes |
| 2001-07-05 00:00:00 | IT APPEARS THAT ALL PREVIOUS COMMENTS | | | BY THE FIRE RESCUE DEPARTMENT HAS | | | BEEN MITIGATED. | | | | | | 1) PLEASE CLARIFY IN WRITING TO THIS | | | OFFICE IF INDIVIDUAL FIRE DEPARTMENT | | | CONNECTIONS WILL BE PROVIDED. PLANS | | | SEEM TO SUGGEST INDIVIDUAL ONES AND | | | COMMON ONES FOR THE BUILDINGS OR UNITS. | | | 2) COULD NOT LOCATE FIRE SPRINKLER | | | MONITORING DEVICES FOR EACH BUILDING. | | | 3) PLEASE BE ADVISED THAT CITY CODE | | | SECTION 11-4 REQUIRES THAT NO DEVICES | | | BE PLACED WITHIN 18 FEET OF FIRE | | | HYDRANTS. | | | 4) ALSO PLEASE BE ADVISED THAT THE | | | PROPERTY APPEARS TO BE LOCATED IN THE | | | CITY FIRE LIMITS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-03-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-27 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-27 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2001-03-27 00:00:00 | 1) WRONG BUILDING CODE EDITION | | | REFERENCED. SHOULD READ 1997 EDITION | | | INSTEAD OF 1994. | | | 2) FIRE HYDRANTS NOT SHOWN ON SITE PLAN. | | | 3) BUILDING ADDRESSES NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESSES | | | TO COMPLY WITH CITY CODE REQUIREMENTS. | | | 4) HOW IS COMBUSTIBLE LINT REMOVED FROM | | | THE INDIVIDUAL DRYER VENT PIPES. | | | 5) NO FIRE SPRINKLER DRAWINGS OR | | | HYDRAULIC CALCULATIONS PROVIDED WITH | | | DRAWINGS. PLEASE BE ADVISED THAT FS | | | 553.895 (2) REQUIRES ALL NEW BUILDINGS | | | THREE OR MORE STORIES IN HEIGHT | | | REGARDLESS OF OCCUPANCY TO BE PROTECTED | | | BY AN AUTOMATIC FIRE SPRINKLER SYSTEM. | | | 6) THE REQUIRED FIRE SPRINKLER SYSTEM(S) | | | ARE TO BE MONITORED BY A LICENSED UL | | | LISTED CENTRAL STATION APPROVED BY THE | | | FIRE RESCUE DEPARTMENT. THE MONITORING | | | REQUIREMENT IS BOTH BY BUILDING AND FIRE | | | CODE REGULATIONS. | | | 7) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR UNITS. | | | 8) PLEASE PROVIDE FLAME SPREAD | | | INFORMATION FOR CEDAR SHAKES PLANNED FOR | | | USE. | | | 9) EACH INDIVIDUAL UNIT TO COMPLY WITH | | | ONE AND TWO FAMILY DWELLINGS PER THE | | | LIFE SAFETY CODE 1985 EDITION IF THEY | | | PLATTED INDIVIDUALLY. IF THEY ARE NOT | | | PLATTED INDIVIDUALLY, THEN THE | | | REQUIREMENTS FOR NEW APARTMENTS PER THE | | | LIFE SAFETY CODE 1985 EDITION ARE | | | APPLICABLE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-07-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-23 |
Time |
14:45 |
Rev Time |
1.30 |
| Received By |
pkrauss |
Date |
2001-07-23 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2001-07-23 00:00:00 | *******************PROVISO************** | | | | | | | | | FIRE DAMPERS SHALL COMPLY WITH UL 555 | | | AND SHALL BEAR THE LABEL OF ANY | | | APPROVED TESTING AGENCY. | | | | | | NOTE:PLANS DO NOT INDICATE MEANS OF | | | VENTILATION FOR THE CABANAS AT | | | THE POOL.PLEASE SUBMIT EXHAUST | | | FANS AND HOW AIR MAKE-UP WILL BE | | | MAINTAINED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-04-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-19 |
Time |
12:13 |
Rev Time |
2.30 |
| Received By |
pkrauss |
Date |
2001-04-19 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2001-04-19 00:00:00 | *******************DENIED*************** | | | | | | | | | APARTMENTS: | | | | | | 1.DRYER VENTS SHALL NOT EXCEED 25' | | | FROM DRYER LOCATION TO WALL OR CAP. | | | THERE WILL BE A 2 1/2 FT DEDUCTION | | | FOR EVERY 45 DEGREE OFFSET & A 5 FT | | | DEDUCTION FOR EVERY 90 DEGREE OFF- | | | SET.1997 SMC 509.3. | | | | | | 2.EXHAUST DUCTS FOR DRYERS SHALL | | | COMPLY WITH 1997 SMC 509.1, FOR | | | THE ASSEMBLY/CONTRUCTION OF EXHAUST | | | DUCT.PLEASE INDICATE ANY ACCESS | | | DOORS OR METHOD USED TO CLEAN LINT | | | FROM DUCT. | | | | | | 3.PLEASE INDICATE ON PLAN WHICH A/C | | | UNIT GOES TO WHICH APARTMENT. | | | | | | 4.PLAN INDICATES A SUPPLY DUCT | | | DROPING INTO GARAGE AREA TO SUPPLY | | | THE FIRST FLOOR. WHERE THE DUCT | | | PENETRATES THE WALL FROM THE GARAGE | | | INTO THE BATHROOM WILL REQUIRE A | | | FIRE DAMPER IF THIS IS A RATED WALL | | | (SEE DRAWING A.9 & AC.1, 1ST FLOOR) | | | PLEASE PROVIDE MANUFACTURE SPECS | | | AND MOUNTING DETAILS FOR ANY FIRE | | | DAMPERS.FIRE DAMPERS MUST BE | | | IDENTIFIED ON PLAN. | | | | | | 5.DRAWING AC.10, DETAIL FOR SUSPENDED | | | A/C UNIT & AUX. DRAIN PAN DETAIL, | | | SPECIFY WHERE THE AUXILIARY DRAIN | | | WILL TERMINATE.SHALL COMPLY WITH | | | 1997 SMC 304.8.6.1, SEPERATE DRAIN | | | SHALL BE EXTENDED FROM PAN AND | | | TERMINATING AT A CONSPICUOUS POINT | | | TO SERVE AS AN ALARM THAT REGULAR | | | DRAIN IS RESTRICTED. A FLOAT SWITCH | | | IN LIEU OF DRAIN LINE MAY BE USED. | | | | | | 6.AHU'S SHALL COMPLY WITH 1997 SMC | | | 304.4.2, IN ATTIC A LIGHT SHALL BE | | | ON THE SERVICE SIDE OF EQUIPMENT | | | WHICH IS CONTROLLED BY A SWITCH | | | LOCATED AT THE ACCESS OPENING. | | | | | | 7.CONDENSER UNITS SHALL COMPLY WITH | | | 1997 SMC 304.7.2, A MINIMUM OF 30" | | | OF CLEAR SPACE ON THE SERVICE SIDE | | | FOR INSPECTION AND SERVICING. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-08-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-18 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2001-08-18 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2001-08-18 00:00:00 | PASSED/PROVISO | | | | | | 1) PER LETTER DATED AUGUST 6, 2001, | | | SEPARATE PERMIT TO BE SUBMITTED FOR POOL | | | CABANA REST ROOMS. PALM BEACH COUNTY | | | HEALTH DEPT. PLAN REVIEW AND COMMENTS | | | PRIOR TO PLUMBING PLAN REVIEW. | | | | | | 2) FULL IRRIGATION PLANS TO BE SUBMITTED | | | FOR IRRIGATION PERMIT APPLICATION. | | | SEPARATE PERMIT FOR BACKFLOWS. TO BE | | | INSTALLED BY PLUMBING CONTRACTOR. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-07-19 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-07-19 |
Time |
08:23 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-19 00:00:00 | PLUMBING PLAN REVIEW,DENIED. | | | (1) PREVIOUS COMMENTS DATED 04-26-01, | | | SHT P-1 NOTE (14) AND P-2 THRU P-10, | | | WATER HAMMER ARRESTORS TO BE INSTALLED | | | AS PER MANFACTURE INSTRUTIONS,NOT AT THE | | | HIGH POINT.USE WATER HAMMER ARRESTOR | | | STD PDI-201 FOR SIZE AND PLACEMENT. | | | (2A) SHT A-62, CABANA REST RM'S,PALM BCH | | | CNTY HEALTH DEPT, PLAN REVEIEW AND | | | COMMMENTS PRIOR TO PLUMBING PLAN REVIEW. | | | (2B) COMPLY W/FACBC SEC 4.1.2(2) ACCESS- | | | IBLE SITE AND EXTERIOR FACILITIES. | | | SEC 4.2.2.1 DOOR'S, CLEAR FLR SPACE,W/C. | | | (3) IRRIGATION PLANS & LOCATION OF BACK | | | FLOW PREVENTER. | | | END OF COMMENTS PAUL CHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-04-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-04-26 |
Time |
18:05 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
2001-04-26 |
Time |
18:04 |
Sent To |
|
|
| Notes |
| 2001-04-26 00:00:00 | PLUMBING PLAN REVIEW. SPC-94 | | | | | | FAILED | | | | | | (1) TYPICAL WATER RISER DIAGRAMS. AIR- | | | CHAMBERS TO COMPLY WITH 607.8.3 AND | | | BE ACCESSABLE AND RECHARGEABLE. | | | | | | (2) PAGE P.2 WHERE DOES THE VENT FROM | | | THE POWDER ROOM TERMINATE? | | | | | | (3) CIVIL PLANS WITH SITE SEWER, WATER, | | | ECT. NOT INCLUDED WITH PLANS AS | | | INDICATED ON SHEET SCHEDULE. | | | | | | REVIEW BY KEN STEVENS. (561) 659-8096 | | | EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
N |
Date |
2003-09-15 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2003-09-15 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-09-15 00:00:00 | 9/15/03 IT'S IN BIN FOR PICKUP |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2001-08-01 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-08-01 |
Time |
08:26 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-01 00:00:00 | NEED RECORDED PLATS |
|
|