Plan Review Details - Permit 01030589
Plan Review Stops For Permit 01030589
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-05-11 Cont ID  
Sent By jwitmer Date 2001-05-11 Time 16:08 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-05-09 Cont ID  
Sent By jwitmer Date 2001-05-09 Time 08:34 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-05-09 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01030589
 1041 OLD OKEECHOBEE RD
 ROY DUNWORTH
 (561) 485-5210
  
 1)- ENERGY CALCULATIONS REQUIRED,
 FL. ENERGY CODE 400.1
  
 2)- 1606.2.6.2 COMPONENTS & CLADDING:
 MISSING PRODUCT APPROVAL REPORT FOR THE
 FRENCH DOORS & FRONT DOOR.
  
 3)- FLOOR TRUSS SYSTEM: MISSING LEDGER
 DETAIL.
  
 4)- FLOOR TRUSS SYSTEM: MEZZANINE, THE
 LIVE LOAD FOR THE FLOOR TRUSSES IS TO BE
 125 PSF NOT 40 PSF!!!!!!!!!!RE-ENGINEER
  
 5)- CANOPY CHANGED FROM CANVAS TO A
 WOOD FRAME STRUCTURE WITH TRUSSES, NO
 LEDGER DETAILS.
  
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-03 Cont ID  
Sent By jwitmer Date 2001-04-03 Time 18:39 Rev Time 2.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-03 00:00:00BUILDING PLAN REVIEW
 PERMMIT# 01030589
 1041 OLD OKEECHOBEE ROAD
 ROY D. DUNWORTH CONT
 (561) 485-5210
  
 1)- PLOT PLAN DEPECTS THE PROPOSED BUILD
 ING SITUATED ON THE NORTH & WEST PROPER-
 TY LINES.THE FOOTING NOR THE DOOR SHOWN
 ON THE WEST ELEVATION CAN ENCROACH OVER
 THE PROPERTY LINE.
  
 2)_ENERGY CALCULATIONS REQUIRED, FL.
 ENERGY CODE 400.1.
  
 3)- STRUCTURAL NOTES S-1 ASSUMED SOIL
 BEARING VALUE OF 2000PSF SOILS REPORT
 REQUIRES 2500 PSF.
  
 4)- SHEET A-2 SEC. 4:
 A)- SHUTTER DETAIL NOTE "SEE ROLL-
 ADEN PRODUCT APPROVAL DWGS" FOR
 DIMENSIONS & INSTALLATION DETAIL
 THE UPPER BUCK ATTACHES TO WHAT?
 WAS THE WINDOW AND SHUTTER TEST-
 ED THIS WAY?
 B)- STEEL STAIRS: RISE & RUN, SHOP
 DRAWINGS REQUIRED, SHOW ATTACH-
 MENT TO LANDING, COLUMNS AND
 FLOOR.
 C)- SBC 104.2.2: ADD INFO, SHOW DE-
 TAIL FOR DROPPED BEAM UNDER
 STAIR STRINGER?
 D)- LINTEL SCHEDULE LIST OPENINGS
 FOR THE FIRST FLOOR BUT NOT THE
 WINDOWS OVER THE MEZANINE NOR
 THE CIRCULAR WINDOW.
  
 5)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 A)- SBC 1707.4 ALL GLAZED OPENINGS
 REQUIRE TESTING FORWIND PRESSURE
 A 10 SEC. LOAD EQUAL TO 1.5
 TIMES THE DESIGN LOADS.
 B)- SBC GLAZED OPENINGS REQUIRE
 LARGE MISSLE IMPACT TESTING OR
 SHUTTERS THAT HAVE PRODUCT AP-
 PROVAL, DADE COUNTY OR SBCCI RE-
 PORTS ARE ACCEPTABLE.CITY POLICY
 FOR STORM SHUTTERS REQUIRES A
 INSTALLATION PLAN & SCHEDULE.
 C)- ALL DOORS ALSO REQUIRE PRODUCT
 TESTING SBC 1606.2.6.2 (SWING &
 OVERHEAD DOORS).
 D)- 1503.3.2/1503.4.1.2: ALL ROOF
 ASSEMBLIES REQUIRE PRODUCT TEST-
 ING FOR 110 MPH.
  
 6)- A-2/ A-3 MEZANINE DECK NEEDS A
 ATTACHMENT DETAIL FOR THE FLOOR TRUSSES
 ON THE EXTERIOR WALL, TRUSS FLOOR LOAD-
 ING AS PER TABLE 1604.1 LIVE LOADS FOR
 STORAGE, LIGHT 125 PSF
 HEAVY 150 PSF
 SBC 413.4.5.2 POSTING STORAGE LOAD SIGNS
 TRUSS PLAN LAYOUT FOR MEZANINE AND ROOF.
 THE PLANS DON'T INDICATE IF THERE IS TO
 BE FLOOR TRUSSES OVER THE KITCHEN AREA,
 IF THERE IS , ISTHE NORTH KITCHEN WALL
 BEARING? IS A GIRDER REQUIREDALSO?
  
 7)- THE METAL FRAME CANOPY WILL REQUIRE
 A SEPERATE PERMIT.
  
 8)- ROOF TRUSSES: THE GABLE END MISSING
 DETAILS, DROPPED GABLE, RAKED BEAM, DE-
 TAILS ON THE ATTACHMENT OF THE GABLE
 TRUSS TO THE BEAM.
  
 9)_ MISSING ACCESS PANEL FOR THE FIRST
 FLOOR A/C UNIT.
  
 10)- MEZANINE USAGE REQUIRED, IF NOT
 USED FOR STORAGE FL. VERTICAL ACCESSI-
 BILITY BECOMES A ISSUE.
  
 11)- PLANS ARE REQUIRED TO RECEIVE
 COUNTY IMPACT FEE STAMPS BEFORE ISSUANCE
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-02-05 Cont ID  
Sent By dpalmer Date 2002-02-05 Time 19:51 Rev Time 0.00
Received By dpalmer Date 2002-02-05 Time 19:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-05-09 Cont ID  
Sent By dpalmer Date 2001-05-09 Time 11:09 Rev Time 0.00
Received By dpalmer Date 2001-05-09 Time 11:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-02 Cont ID  
Sent By dpalmer Date 2001-04-02 Time 07:50 Rev Time 0.00
Received By dpalmer Date 2001-04-02 Time 07:50 Sent To  
Notes
2001-04-02 00:00:00***************** UNSAT ***************
  
 1)NOTE: BRANCH CIRCUIT #`S ARE NOT SHOWN
 ON PLANS. PLEASE SUBMIT A PANEL
 SCHEDULE TO CORRELATEWITH BRANCH
 CIRUCIT #`S.
  
 2)NOTE:PLEASE CLARIFY WHERE CONTINUOUS
 LOADS ARE SHOWN AT 125%. CALCS SHOW
 CONTINUOUS LOAD BUT, NOT AT 125%.
  
 3)NOTE: PLEASE "J" BOX SHOWN IN STORAGE
 AREA. NEEDS LIGHT FIXTURE SHOWN.
  
 4)NOTE: PLEASE NOTE THAT DISCONNECTS
 NEED TO BE SHOWN FOR A/C EQUIPMENT PER
 440-11.
  
 5)NOTE: PLEASE NOTE THAT NO SERVICE
 RISERDIAGRAM WAS SUBMITTED.
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO SHOWN FOR TRACK LIGHTING PER
 220-12.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-02-06 Cont ID  
Sent By mcarsill Date 2002-02-06 Time 09:12 Rev Time 0.00
Received By mcarsill Date 2002-02-06 Time 09:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-03-30 Cont ID  
Sent By mcarsill Date 2001-03-30 Time 09:14 Rev Time 0.00
Received By mcarsill Date 2001-03-30 Time 09:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-02-07 Cont ID  
Sent By pkrauss Date 2002-02-07 Time 12:30 Rev Time 0.35
Received By pkrauss Date 2002-02-07 Time 12:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-25 Cont ID  
Sent By hmoser Date 2001-08-25 Time 13:10 Rev Time 0.50
Received By hmoser Date 2001-08-25 Time 13:10 Sent To  
Notes
2001-08-25 00:00:00REVISON OK CALLED ROY LEFT MESSAGE FOR
 PICKUP PLANS IN BOX A 08/25/01
 H.M.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-03-23 Cont ID  
Sent By pkrauss Date 2001-03-23 Time 13:04 Rev Time 0.35
Received By pkrauss Date 2001-03-23 Time 11:49 Sent To  
Notes
2001-03-23 00:00:00******************PROVISO***************
  
 NO CONDENSATE TRAP DETAIL SHOWN ON
 DRAWING M.
  
 SHALL COMPLY WITH 1997 SMC 304.8.3 -
  
 1.UNITS LARGER THAN 3 TONS (10.6KW)
 NOMINAL CAPACITY SHALL DRAIN THROUGH
 STORM DRAIN OR AN APPROVED DRY WELL.

Review Stop P PLUMBING
Rev No 5 Status N Date 2002-02-11 Cont ID  
Sent By kstevens Date 2002-02-11 Time 18:09 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
2002-02-11 00:00:00WITHDREW REVISION - SUBMITTED IN ERROR
 REVISION SUBMITTED PREVIOUS KS

Review Stop P PLUMBING
Rev No 4 Status F Date 2002-02-11 Cont ID  
Sent By kstevens Date 2002-02-11 Time 11:43 Rev Time 0.50
Received By kstevens Date 2002-02-11 Time 11:43 Sent To  
Notes
2002-02-11 00:00:00REVISION - DENIED
 SHT P-1
 1) SERVICE SINK NOT SHOWN ON RISER DIA-
 GRAM.
 2) FLOOR DRAIN IN WAREHOUSE NOT VENTED.
 3) FLOOR DRAIN IN TOILET ROOM NOT VENTED
 PROPERLY.
 4) DRINKING FOUNTAIN NOT VENTED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-05-30 Cont ID  
Sent By pschmitz Date 2001-05-30 Time 15:07 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-30 00:00:00PLUMBING PLAN REVIEW REVISION AS BUILT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-05-10 Cont ID  
Sent By jleech Date 2001-05-10 Time 10:10 Rev Time 1.00
Received By jleech Date 2001-05-10 Time 10:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-04-02 Cont ID  
Sent By jleech Date 2001-04-02 Time 16:16 Rev Time 1.00
Received By jleech Date 2001-04-02 Time 16:15 Sent To  
Notes
2001-04-02 00:00:00DENIED;
  
 1.PAGE A1 TOILET ROOM MEASUREMENTS ARE
 NOT CORRECT. FLOOR PLAN, SAME PAGE,
 BATHROOM SIZE IS 7'X7'.
  
 2.SHOW ON PLANS COMPLIANCE TO 94 SPC
 TABLE 407 MINIMUM PLUMBING FIXTURES
 REQUIRED. (NUMBER OF PEOPLE PER SHIFT)
  
 3.ONE DRINKING FOUNTAIN IS REQUIRED PER.
 TABLE 407. DRINKING FOUNTAIN SHALL
 COMPLY WITH FACBC 4.1.3(10) AND 4.15.
 PROVISIONS SHALL BE MADE FOR PEOPLE
 WHO HAVE TROUBLE BENDING OR STOOPING.
  
 4.PAGE P (RISER DIAGRAM) URINAL IS UN-
 VENTED.
  
 5.FLOOR DRAIN;
 A.WHAT WILL DRAIN INTO FLOOR DRAIN
 B.SHOULD HAVE A DEEP SEAL.
 C.IS NOT VENTED SEE TABLE 908.1.
  
 6.PAGE A-2 (CABINET DETAIL) SINK TO
 COMPLY WITH FACBC 4.24.2 THRU 4.24.7.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-14 Cont ID  
Sent By sgraham Date 2001-05-14 Time 14:32 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***