Plan Review Details - Permit 01030582
Plan Review Stops For Permit 01030582
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2002-12-12 Cont ID  
Sent By jwitmer Date 2002-12-12 Time 07:21 Rev Time 0.75
Received By jwitmer Date 2002-12-12 Time 07:20 Sent To  
Notes
2002-12-12 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 01030582
 ADD: 4325 N HAVERHILL
 CONT: UNITED ENG. CORP.
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 SUBMITTAL 12-03-02DENIED
  
 AS THE PROVISO FOR ISSUANCE OF PERMIT
 THE ENGINEERING FOR THE STRUCTURE SHALL
 BE SIGNED & SEALED:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 2) TWO (2) COPIES OF ALL SUBMITTAL ARE
 REQUIRED, 1 FOR OFFICE RECORD, 1 FOR
 THE FIELD SET OF PLANS.
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-06-15 Cont ID  
Sent By jwitmer Date 2001-06-15 Time 07:34 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-15 00:00:00BUILDING PLAN REVIEW:
 4325 N HAVERHILL
 CITY OF WEST PALM BEACH
 RECLAIMED WATER PRODUCTION FACILITY
 PERMIT # 01030582
  
 BUILDING PROVISO:
 1)- THIS PROVISO HAS (2) ELEMENTS THAT
 WILL HAVE TO BE SATISFIED TO RECEIVE
 A CERTIFICATE OF OCCUPANCY.
 A)- THAT THERE WILL BE A AUTOMATIC
 FIRE SPRINKLER DEVISE,AN APPROVED FIRE
 SUPRESSION SYSTEM, AT TTHE METHANAL
 STORAGE FACILITY.
 B)- THAT TTHE CONTRACTOR WILL PROVIDE
 THE SIGNED & SEALED ENGINEERED DRAWINGS
 FOR THE METAL BUILDING.
  
 BUILDING PLAAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-06-06 Cont ID  
Sent By jwitmer Date 2001-06-06 Time 06:52 Rev Time 6.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-06 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01030582
 4325 N HAVERHILL RD
 WASTE WATER TREATMENT PLANT
 UNITED ENGINEERING CORP.
 PHONE #(305)994-7360
 CAMP DRESSER & MC KEE
 PHONE #(561)689-3336
  
 1)- SBC 308.1 HAZARDOUS OCCUPANCY
 SUB-CLASSIFICATION :
 H-2; METHANOL MSDS METYAL ALCOHOL
 FLASH POINT: 12C
 H-4; CAUSTIC MSDS CAUSTIC SODA/
 SODIUM HYDROXIDE
 2)- SBC TABLE 308.B LIMITS TO 60 GAL.
 NOT SPRINKLERED FOR A CLASS 1A
 FLAMMABLELIQUID (METHAL ALCOHOL)
 FLAMMABLE & COMBUSTIBLE LIQUIDS IN OPEN
 CONTAINERS OR
 PRESSURIZED AT MORE THAN 15 PSIG.
 SBCTABLE 308.D CORROSIVES UNPROTECTED
 BY SPRINKLERS OR CABINET FOR SOLIDS
 5,000LBS. LIQUIDS 500 GAL. IS THIS TYPE
 OF USAGE A SOLID OR LIQUID?
 3)- SBC INDOOR STORAGE AREAS, STORAAGE
 BUILDINGS, AND AREAS OR ROOMS IN WHICH
 HAZARDOUS MATERIALS ARE DISPENSED OR
 USED SHALL BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM. HIGHER AUTOMATIC
 SPRINKLER DISCHARGE DENSITY MAY BE
 REQUIRED
 THAN REQUIRED THAN ARE SUPPLIED BY
 ORDINARY HAZARD, GROUP 2 TO ADEQUUATELY
 PRO- TECT MANY TYPES OF HAZARDOUS
 MATERIALS. NFPA 13, 1-1 INDICATES THAT
 THE PROTEC-
 TION OF MANY OF THESE MATERIALS IS BE-
 YOND THE SCOPE OF THE STANDARD. THERE-
 FORE, OTHER NFPA STANDARDS OR TEST DATA
 MAYBE SUBSTANTIATE SPRINKLER DESIGN
 DETAILS.
 4)- SBC 407.2.1- STORAGE & DISPENSING
 AREAS- THIS DIVISION SHALL APPLY TO THE
 STORAGE AND DISPENSING OF HAZARDOUS MATE
 RIALS IN EXCESS OF THE EXEMPT AMOUNTS
 SPECIFIED IN TABLES 308.2A THROUGH
 308.2D.
 5)- SBC 407 2.3.4(3) SECONDARY CONTAIN-
 MENT SHALL BE DESIGNED TO RETAIN THE
 SPILL FROM THE LARGEST SINGLE CONTAINER
 PLUS THE DESIGN FLOW RATE OF THE AUTOMA-
 TIC FIRE EXTINGUISHING SYSTEM FOR THE
 AREA OF THE ROOM OR AREA IN WHICH THE
 STORAGE, WHICHEVER IS SMALLER. THE
 CONTAINMENT CAPACITY SHALL BE CAPABLE OF
 CONTAINING THE FLOW FOR A PERIOD OF 20
 MINUTES.
 6)- THE PRE-ENGINEERED METAL BUILDING
 HOUSING THE CHEMICALS WILL NEED TO
 SUPPLY SIGNED & SEALED ENGINEERED DRAW-
 INGS BEFORE THE ISSUANCE OF THE PERMIT,
 OR IT MAY BE BROUGHT IN UNDER SEPERATE
 PERMIT WITH ADDITIONAL FEES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-12 Cont ID  
Sent By jwitmer Date 2001-04-12 Time 18:36 Rev Time 4.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-12 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01030582
 4325 N HAVERHILL RD
 EAST CENTRAL REGIONAL
 WASTE WATER TREATMENT PLANT
 UNITED ENGINEERING CORP.
 (305) 994-7360
  
 1)- SBC 704 SPECIAL HAZARD OCCUPANCIES
 407.1.1.1. STORAGE, DISPENSING, HANDLING
 AND THE USE OF SOLID,LIQUID & GASEOUS
 HAZARDOUS MATERIALS SHALL BE IN ACCORD-
 ANCE WITH THIS SECTION & THE STANDARD
 FIRE PREVENTION CODE.
  
 HAZARDOUS OCCUPANCY
 H2: CLASS I,II,ORIII-A FLAMMABLES OR
 COMBUSTIBLE LIQUIDS.
 H4:HEALTH HAZARDS, CORROSIVES,IRRITANTS.
  
 2)- SBC 407.1.3 REQUIRES AN AUTOMATIC
 PROTECTION SYSTEM.
  
 3)- SBC 407 2.3.4.(1-4) SHOW COMPLIANCE
 WITH THESE SYSTEMS.
  
 4)- SBC 104.2.2. ADDITIONAL INFORMATION
 REQUIRED, PLEASE PROVIDE INFORMATION ON
 THE STORAGE TANKS, THE SECONDARY CONTAIN
 MENT SYSTEM, IS THERE A MEMBRANE APPLIED
 TO THE CONTAINMENT AREA? IS THERE A
 DRAIN? ETC?
  
 5)- THE OPEN STRUCTURE ABOVE, WILL THERE
 BE A CORROSIVE PROBLEM WITH THE CONTENTS
 OF THE TANKS? SULFURIC ACID/ FERRIC SUL-
 FATE?
  
 6)- THE PRE-ENGINEERED METAL BUILDING
 HOUSING THE CHEMICALS WILL NEED TO SUP-
 PLY SIGNED & SEALED ENGINEERED DRAWINGS
 BEFORE THE ISSUANCE OF THE PERMIT OR IT
 MAY BE BROUGHT IN UNDER SEPERATE PERMIT
 WITH ADDITIONAL FEES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-04-03 Cont ID  
Sent By dpalmer Date 2001-04-03 Time 11:59 Rev Time 0.00
Received By dpalmer Date 2001-04-02 Time 22:48 Sent To  
Notes
2001-04-03 00:00:00**************** PROVISO **************
  
 1)NOTE: PLEASE SUBMIT PLANS SHOWING ALL
 BRANCH CIRCUIT #`S AND CORRELATE WITH
 PANEL SCHEDULES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL ELECTRICAL
 INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-03-16 Cont ID  
Sent By mamini Date 2001-03-16 Time 10:41 Rev Time 3.00
Received By mamini Date 2001-03-16 Time 10:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-06-13 Cont ID  
Sent By mcarsill Date 2001-06-13 Time 10:53 Rev Time 0.00
Received By mcarsill Date 2001-06-13 Time 10:53 Sent To  
Notes
2001-06-13 00:00:00ON JULY 13, 2001, WRITER AND JIM
 WHITMER RECEIVED A LETTER FROM DAVID
 HOLT, P.E. OF CAMP DRESSER & MCKEE. THE
 LETTER ADVISED THAT A FIRE SPRINKLER
 SYSTEM WILL BE INSTALLED TO PROTECT
 THE METHANOL STORAGE TANK. THE FIRE
 SPRINKLER SYSTEM IS TO MEET HIGH-HAZARD
 REQUIREMENTS AND BE DESIGNED BY A
 LICENSED FIRE PROTECTION ENGINEER. THE
 FIRE SPRINKLER SYSTEM IS TO BE PERMITTED
 INSTALLED AND INSPECTED PRIOR TO THE
 METHANOL TANK BEING ERECTED AND FILLED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-06-07 Cont ID  
Sent By mcarsill Date 2001-06-07 Time 15:13 Rev Time 0.00
Received By mcarsill Date 2001-06-07 Time 15:13 Sent To  
Notes
2001-06-07 00:00:001) THIS OFFICE HAS IDENTIFIED THE
 BUILDING AS A HIGH-HAZARD OCCUPANCY
 AND WILL REQUIRE SOME TYPE OF APPROVED
 FIRE SUPPRESSION SYSTEM FOR THE
 AREA CONTAINING THE METHANOL STORAGE.
 2) PLEASE PROVIDE APPROVALS FOR THE
 STORAGE TANKS.
 3) PLEASE INDICATE THE TYPES OF PRESSURE
 OF THE MATERIALS STORED IN THE TANKS.
 4) PLEASE INDICATE COMPLIANCE WITH CITY
 CODE SECTION 11, WHICH REQUIRES AT LEAST
 A 2" VENT PIPE FOR THE METHANOL STORAGE.
 5) PLEASE SHOW LOCATIONS OF ALL FIRE
 HYDRANTS, FIRE EXTINGUISHING EQUIPMENT
 AND FIRE PROTECTION FEATURES.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-03-28 Cont ID  
Sent By mcarsill Date 2001-03-28 Time 15:13 Rev Time 0.00
Received By mcarsill Date 2001-03-28 Time 15:13 Sent To  
Notes
2001-03-28 00:00:001) PLEASE PROVIDE MATERIAL SAFETY DATA
 SHEETS FOR THE STORAGE OF METHANOL,
 FERRIC SULFATE, AND CAUSTIC MATERIALS.
 2) PLEASE BE ADVISED THAT COMPLIANCE
 WITH CITY ORDINACE 3206-99 HAZARDOUS
 MATERIALS OF CHAPTER 11 WILL BE
 REQUIRED.
 3) PLEASE PROVIDE INFORMATION ON THE
 STORAGE TANKS BEING USED TO HOLD THE
 METHANOL, FERRIC SULFATE AND THE CAUSTIC
 MATERIALS.
 4) PLEASE INDICATE THE WARNING SIGNS AND
 VERBAGE PLANNED FOR THE METHANOL, FERRIC
 SULFATE AND CAUSTIC STORAGE AREAS.
 5) WHAT TYPES OF FIRE PROTECTION IS
 PLANNED FOR THE METHANOL STORAGE AREA.
 6) WHAT PRECAUTIONS ARE PLANNED FOR
 SPILLS, LEAKS, AND OTHER TYPES MISHAPS
 IN THE STORAGE AREA.
 7) PLEASE DISPLAY COMPLIANCE WITH NFPA
 30, FOR THE METHANOL STORAGE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-04-17 Cont ID  
Sent By pkrauss Date 2001-04-17 Time 11:48 Rev Time 0.45
Received By pkrauss Date 2001-04-17 Time 10:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-05-27 Cont ID  
Sent By pschmitz Date 2001-05-27 Time 17:00 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-27 00:00:00PLUMBING PLAN REVIEW RE-SUB
 RECLAIMED WATER,TO REPLENISH WET LANDS.
 AS PER CHRIS HELFRICH PEWPBPU DEPT.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-05 Cont ID  
Sent By pschmitz Date 2001-05-05 Time 05:33 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-05 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) INFORMATION ON THE USE OF POTABLE
 WATER, IN THIS PROCESS, AND LOCATION OF
 EACH OUTLET AND HOW IT IS PROTECTED.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096 X 8233

Review Stop Z ZONING
Rev No 1 Status N Date 2001-07-19 Cont ID  
Sent By lmartine Date 2001-07-19 Time 13:50 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***