Plan Review Details - Permit 01030543
Plan Review Stops For Permit 01030543
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-27 Cont ID  
Sent By jwitmer Date 2001-04-27 Time 12:12 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-27 00:00:00PROVISO: PRODUCT APPROVAL BE SUBMITTED
 FOR ALL GLAZED OPENINGS, THE LOAD TO BE
 TESTED AT 1.5 THE DESIGN PRESSURE JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-29 Cont ID  
Sent By jwitmer Date 2001-03-29 Time 09:34 Rev Time 0.00
Received By jwitmer Date 2001-04-27 Time 09:58 Sent To  
Notes
2001-03-29 00:00:00O/B SIMMONS, RONALD
 369 PALMETTO ST
 PERMIT # 01030543
  
 1)- SBC 104.2.2 ADDITIONAL INFORMATION
 : SURVEY REQUIRED (2 COPIES) A RECENT
 SURVEY WITH IN A YEAR OLD.
  
 2)- DISCREPANCY BETWEEN THE ENERGY SHEET
 ATTIC INSULATION R-30 VS. SHEET A2 R-19.
  
 3)- STATE MEMORANDUM 692; PRE CONSTRUC-
 TION SOIL TREATMENT FOR SOIL,SBC.103.7.-
 3.3.5 ADDITIONAL SOIL TREATMENTSHALL BE
 APPLIED UNDER ALL EXTERIOR CONCRETE ON
 GRADE WITHIN (1) FOOT OF THE PRIMARY
 STRUCTURE SIDEWALLS (PATIO).
  
 4)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 ALL GLAZED OPENINGS (WINDOWS & DOORS)
 ARE REQUIRED TO WITH TESTING FOR WIND,
 A 10 SECOND PERIOD AT LOAD EQUAL TO 1.5
 TIMES THE DESIGN PRESSURE (1707.4).
  
 5)- SBC 1707.5 CONCRETE ROOF TILE,
 REQUIRES TESTING FOR RESISTANCE FOR OVER
 TURNING IN ACCORDANCE WITH THE SBCCI
 SSTD 11, THE CITY ACCEPTS SBCCI REPORTS
 OR DADE COUNTY PRODUCT APPROVALS.
  
 6)- SBC 1606.4.1/1707.4.1.: GLAZED OPEN-
 INGS REQUIRE PRODUCT TESTING FOR LARGE
 MISSLE RESISTANCE TESTING OR STORM
 SHUTTERS THAT HAVE BEEN TESTED, A COPY
 OF THE CITIES POLICY IS ENCLOSED,WITH A
 SAMPLE SCHEDULE. THE DESIGN CERTIFICA-
 TION SHEET INDICATES THAT THIS REQUIRE-
 MENT WILL BE "BY OTHERS". A SEPERATE
 PERMIT & FEES WILL BE ASSESSED IF THIS
 REQUIREMENT IS MET AFTER THE ISSUANCE OF
 THE BUILDING PERMIT.
  
 7)- PLANS WILL BE REQUIRED TO HAVE
 COUNTY IMPACT FEE STAMPS BEFORE THE
 ISSUANCE OF THE PERMIT.
  
 8)- STATE RADON CHARGES OF $5.68 WILL BE
 ASSESSED BY THE CITY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-23 Cont ID  
Sent By dpalmer Date 2001-04-23 Time 18:09 Rev Time 0.00
Received By dpalmer Date 2001-04-23 Time 18:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-26 Cont ID  
Sent By dpalmer Date 2001-03-26 Time 18:07 Rev Time 0.00
Received By dpalmer Date 2001-03-26 Time 18:07 Sent To  
Notes
2001-03-26 00:00:00**************** UNSAT ****************
  
 1) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 2)(NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50
  
 3)NOTE: PLEASE NOTE SERVICE ENTRANCE
 CONDUCTORS SHOWN AT 3-00`S "THIN".
 SHOWN FROM METER TO PANEL? PLEASE
 CLARIFY THIS SIZE AND INSULATION TYPE.??
  
 4)NOTE: PLEASE SEE ELECTRICAL NOTES<<
 "C" CONDUIT SIZE?, "D" SUB-PANEL CALCS??
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 6) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 7) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 8)NOTE: PLEASE SEE RISER DIAGRAM,, PLEAS
 E CLARIFYNOTE SHOWING2-#3`S,1-#2 IN
 1/2" CONDUIT. FIRST CONDUIT IS WAY TOO
 SMALL AND WHAT DOES THIS GO TO.
  
 9)NOTE: PLEASE SHOW SERVICE ENTRANCE
 CONDUCTORS ON RISER.
  
 PLEASE CLARIFY AND SUBMIT ALL THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-25 Cont ID  
Sent By pkrauss Date 2001-04-25 Time 15:06 Rev Time 0.35
Received By pkrauss Date 2001-04-25 Time 15:06 Sent To  
Notes
2001-04-25 00:00:00PROVISO NOTES ON MECH PERMIT 01030776

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-20 Cont ID  
Sent By pkrauss Date 2001-03-20 Time 14:51 Rev Time 0.40
Received By pkrauss Date 2001-03-20 Time 14:50 Sent To  
Notes
2001-03-20 00:00:00******************DENIED****************
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.MUST SUBMIT AHU AND CONDENSING
 UNIT EQUIPMENT I.E., MANUFACTURER,
 SIZE, SEER, HEAT STRIP, ETC..NEED
 LOCATION OF AHU AND ACCESS TO AHU.
 DESIGNATE DUCT SIZE, GRILLES, CFM BEING
 DISTRIBUTED, AND LOCATION OF RETURN AIR
 GRILLE AS WELL AS CONDENSATE DRAIN.
  
 SUBMIT PLANS WITH MECHANICAL PERMIT
 APPLICATION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-04-26 Cont ID  
Sent By jleech Date 2001-04-26 Time 18:29 Rev Time 0.33
Received By jleech Date 2001-04-26 Time 18:29 Sent To  
Notes
2001-04-26 00:00:00PROVISO;
 REVISED RISER DIAGRAM REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-03-21 Cont ID  
Sent By jleech Date 2001-03-21 Time 19:35 Rev Time 0.33
Received By jleech Date 2001-03-21 Time 19:35 Sent To  
Notes
2001-03-21 00:00:00DENIED;
  
 PLUMBING CODE USED IN WEST PALM BEACH IS
 THE 94 SPC NOT SFC.
  
 PLUMBING RISER IS NOT SIZED PROPERLY.
 A.MIMINUM PIPE UNDER SLAB IS 2" NOT
 1 1/2"
 B.WASHING MACHINE WASTE IS 2" MIN.
 C.W/C AND SHOWER DRAIN CAN BE USED AS
 CLEANOUTS.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-03-16 Cont ID  
Sent By sgraham Date 2001-03-16 Time 11:54 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***