| Plan Review Stops For Permit 01030543 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-04-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-27 |
Time |
12:12 |
Rev Time |
2.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-27 00:00:00 | PROVISO: PRODUCT APPROVAL BE SUBMITTED | | | FOR ALL GLAZED OPENINGS, THE LOAD TO BE | | | TESTED AT 1.5 THE DESIGN PRESSURE JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-03-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-29 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-04-27 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2001-03-29 00:00:00 | O/B SIMMONS, RONALD | | | 369 PALMETTO ST | | | PERMIT # 01030543 | | | | | | 1)- SBC 104.2.2 ADDITIONAL INFORMATION | | | : SURVEY REQUIRED (2 COPIES) A RECENT | | | SURVEY WITH IN A YEAR OLD. | | | | | | 2)- DISCREPANCY BETWEEN THE ENERGY SHEET | | | ATTIC INSULATION R-30 VS. SHEET A2 R-19. | | | | | | 3)- STATE MEMORANDUM 692; PRE CONSTRUC- | | | TION SOIL TREATMENT FOR SOIL,SBC.103.7.- | | | 3.3.5 ADDITIONAL SOIL TREATMENTSHALL BE | | | APPLIED UNDER ALL EXTERIOR CONCRETE ON | | | GRADE WITHIN (1) FOOT OF THE PRIMARY | | | STRUCTURE SIDEWALLS (PATIO). | | | | | | 4)- SBC 1606.2.6.2 COMPONENTS & CLADDING | | | ALL GLAZED OPENINGS (WINDOWS & DOORS) | | | ARE REQUIRED TO WITH TESTING FOR WIND, | | | A 10 SECOND PERIOD AT LOAD EQUAL TO 1.5 | | | TIMES THE DESIGN PRESSURE (1707.4). | | | | | | 5)- SBC 1707.5 CONCRETE ROOF TILE, | | | REQUIRES TESTING FOR RESISTANCE FOR OVER | | | TURNING IN ACCORDANCE WITH THE SBCCI | | | SSTD 11, THE CITY ACCEPTS SBCCI REPORTS | | | OR DADE COUNTY PRODUCT APPROVALS. | | | | | | 6)- SBC 1606.4.1/1707.4.1.: GLAZED OPEN- | | | INGS REQUIRE PRODUCT TESTING FOR LARGE | | | MISSLE RESISTANCE TESTING OR STORM | | | SHUTTERS THAT HAVE BEEN TESTED, A COPY | | | OF THE CITIES POLICY IS ENCLOSED,WITH A | | | SAMPLE SCHEDULE. THE DESIGN CERTIFICA- | | | TION SHEET INDICATES THAT THIS REQUIRE- | | | MENT WILL BE "BY OTHERS". A SEPERATE | | | PERMIT & FEES WILL BE ASSESSED IF THIS | | | REQUIREMENT IS MET AFTER THE ISSUANCE OF | | | THE BUILDING PERMIT. | | | | | | 7)- PLANS WILL BE REQUIRED TO HAVE | | | COUNTY IMPACT FEE STAMPS BEFORE THE | | | ISSUANCE OF THE PERMIT. | | | | | | 8)- STATE RADON CHARGES OF $5.68 WILL BE | | | ASSESSED BY THE CITY. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-04-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-23 |
Time |
18:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-23 |
Time |
18:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-03-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-26 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-26 |
Time |
18:07 |
Sent To |
|
|
| Notes |
| 2001-03-26 00:00:00 | **************** UNSAT **************** | | | | | | 1) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 2)(NOTE: PLEASE SHOW GROUNDING | | | ELECTRODEGOING TO BUILDING STEEL AND | | | COLD WATER | | | PER 250-50 | | | | | | 3)NOTE: PLEASE NOTE SERVICE ENTRANCE | | | CONDUCTORS SHOWN AT 3-00`S "THIN". | | | SHOWN FROM METER TO PANEL? PLEASE | | | CLARIFY THIS SIZE AND INSULATION TYPE.?? | | | | | | 4)NOTE: PLEASE SEE ELECTRICAL NOTES<< | | | "C" CONDUIT SIZE?, "D" SUB-PANEL CALCS?? | | | | | | 5) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 6) PLEASE NOTE MISSING OUTLET(S) REQ`D | | | BY 210-52E OF THE NEC. | | | | | | 7) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | | | 8)NOTE: PLEASE SEE RISER DIAGRAM,, PLEAS | | | E CLARIFYNOTE SHOWING2-#3`S,1-#2 IN | | | 1/2" CONDUIT. FIRST CONDUIT IS WAY TOO | | | SMALL AND WHAT DOES THIS GO TO. | | | | | | 9)NOTE: PLEASE SHOW SERVICE ENTRANCE | | | CONDUCTORS ON RISER. | | | | | | PLEASE CLARIFY AND SUBMIT ALL THE ABOVE | | | INFORMATION FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-04-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-25 |
Time |
15:06 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-04-25 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2001-04-25 00:00:00 | PROVISO NOTES ON MECH PERMIT 01030776 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-03-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-20 |
Time |
14:51 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-03-20 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2001-03-20 00:00:00 | ******************DENIED**************** | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW.MUST SUBMIT AHU AND CONDENSING | | | UNIT EQUIPMENT I.E., MANUFACTURER, | | | SIZE, SEER, HEAT STRIP, ETC..NEED | | | LOCATION OF AHU AND ACCESS TO AHU. | | | DESIGNATE DUCT SIZE, GRILLES, CFM BEING | | | DISTRIBUTED, AND LOCATION OF RETURN AIR | | | GRILLE AS WELL AS CONDENSATE DRAIN. | | | | | | SUBMIT PLANS WITH MECHANICAL PERMIT | | | APPLICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-04-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-04-26 |
Time |
18:29 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2001-04-26 |
Time |
18:29 |
Sent To |
|
|
| Notes |
| 2001-04-26 00:00:00 | PROVISO; | | | REVISED RISER DIAGRAM REQUIRED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-03-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-21 |
Time |
19:35 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2001-03-21 |
Time |
19:35 |
Sent To |
|
|
| Notes |
| 2001-03-21 00:00:00 | DENIED; | | | | | | PLUMBING CODE USED IN WEST PALM BEACH IS | | | THE 94 SPC NOT SFC. | | | | | | PLUMBING RISER IS NOT SIZED PROPERLY. | | | A.MIMINUM PIPE UNDER SLAB IS 2" NOT | | | 1 1/2" | | | B.WASHING MACHINE WASTE IS 2" MIN. | | | C.W/C AND SHOWER DRAIN CAN BE USED AS | | | CLEANOUTS. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-03-16 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-03-16 |
Time |
11:54 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|