| Plan Review Stops For Permit 01030534 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-08-28 |
Time |
14:12 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
2001-08-28 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2001-08-28 00:00:00 | APPROVED WITH PROVISO: | | | | | | 1-APPLY FOR SEPARATE PERMITS FOR | | | ELECTRICAL, MECHANICAL AND PLUMBING | | | WORK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2001-08-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-08-20 |
Time |
17:36 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
2001-08-20 |
Time |
17:36 |
Sent To |
|
|
| Notes |
| 2001-08-20 00:00:00 | CHECKLIST: | | | | | | 1-ORIGINAL ENERGY CALCULATIONS WERE NOT | | | REVISED AS REQUESTED ON PREVIOUS | | | CHECKLISTS. | | | NOTE: BRING ENERGY CALCULATIONS TO | | | THOMAS ABBOTT (PERSON WHO PREPARED THE | | | ORIGINAL ENERGY CALCULATIONS). | | | I TALKED TO THOMAS ABBOT ABOUT THIS | | | ENERGY CALCULATIONS. HE KNOWS WHAT TO | | | DO FOR RENOVATION PROJECTS. | | | NOTE: ENGINEER OF RECORD TO SIGN, SEAL | | | & DATE THE REVISED ENERGY CALCULATIONS | | | & PROVIDE HIS INFORMATION AS REQUIRED | | | BY CHAPTER 471 OF FLORIDA STATUTES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-08-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-07-28 |
Time |
12:26 |
Rev Time |
1.50 |
| Received By |
jgomez |
Date |
2001-07-28 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2001-07-28 00:00:00 | 1-REVISE ORIGINAL ENERGY CALCULATIONS | | | TO SHOW EXISTING STRUCTURE (NOT NEW), | | | ACTUAL NUMBER OF UNITS, FLOOR TYPE. | | | NOTE: ENERGY CALCS FOR MULTIFAMILY UNITS | | | TO BE SIGNED & SEALED BY THE ENGINEER. | | | 2-APPLY FOR SEPARATE PERMITS FOR | | | ELECTRICAL, MECHANICAL AND PLUMBING | | | WORK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-07-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-07-13 |
Time |
13:02 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2001-07-13 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2001-07-13 00:00:00 | THIRD CHECKLIST: | | | 1-ENERGY CALCULATIONS ARE WRONG: | | | A)THIS IS NOT A NEW BUILDING. | | | B)NUMBER OF UNITS IS WRONG. | | | C)NO INFORMATION ON FLOOR TYPES. | | | D)WHAT ABOUT UNITS ON THE FIRST FLOOR? | | | E)OWNER/AGENT TO SIGN AND DATE AT THE | | | BOTTOM OF ENERGY CALCULATIONS FORM. | | | 2-CLEARLY SPECIFY SIZE & TYPE OF EGRESS | | | WINDOWS. WHAT'S A 24EH WINDOW? | | | -PRODUCT APPROVAL SUBMITTED IS FOR | | | SINGLE HUNG WINDOWS. A 24SH WINDOW | | | DOESN'T COMPLY WITH THE MINIMUM EGRESS | | | REQUIREMENTS OF SEC. 1005.4 SBC 1997. | | | 3-SPECIFY SIZE OF ENTRY DOORS TO COMPLY | | | WITH TABLE 1004 SBC 1997. | | | 4-PRODUCT APPROVAL FOR DOORS REQUIRES A | | | 2X STRUCTURAL BUCK. ENGINEER TO | | | PROVIDE 2X STRUCTURAL BUCK DETAIL. | | | -PROVIDE BUCK DETAIL FOR WINDOWS TOO. | | | 5-NEED TO APPLY FOR SEPARATE PERMITS FOR | | | MECHANICAL, PLUMBING & ELECTRICAL WORK | | | 6-NEED TO APPLY FOR SEPARATE PERMITS FOR | | | FENCE AND FOR PARKING WORK. | | | 7-SPECIFY HOW IS THE ONE HOUR TENANT | | | SEPARATION ACHIEVED BETWEEN THE FIRST | | | AND SECOND FLOOR. SEC 704.3 SBC 1997. | | | 8-CONTRACTOR NEEDS TO UPDATE INSURANCE. | | | 9-SEE COMMENTS BY THE FIRE CAPTAIN. | | | 10-ENGINEER TO SEE COMMENTS ON PLANS. | | | | | | | | | NOTE: | | | ENGINEER NEEDS TO REVISE ORIGINAL DWGS | | | AND PROVIDE THE REQUESTED INFORMATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-05-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-05-07 |
Time |
12:00 |
Rev Time |
1.50 |
| Received By |
jgomez |
Date |
2001-05-07 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2001-05-07 00:00:00 | SECOND CHECKLIST: | | | | | | 1-PROVIDE ENERGY CALCULATIONS (NOT DONE | | | FROM PREVIOUS CHECKLIST. | | | 2-CLEARLY SPECIFY SIZE AND TYPE OF | | | EGRESS WINDOWS TO VERIFY THAT THEY | | | COMPLY WITH SECTION 1005.4 SBC 1997. | | | -CLARIFY WHAT IS (2)24 EH SPECIFIED ON | | | PLANS. | | | -IF THESE ARE TO BE SINGLE HUNG WINDOWS | | | THEN SIZE 24 DOESN'T COMPLY WITH THE | | | EGRESS REQUIREMENTS SEC 1005.4 SBC/97. | | | 3-PROVIDE TWO COPIES OF CURRENT PRODUCT | | | APPROVALS FOR WINDOWS AND DOORS TO BE | | | REPLACED. | | | 4-NEED TO APPLY FOR SEPARATE PERMITS FOR | | | MECHANICAL, PLUMBING AND ELECTRICAL | | | WORK. | | | 5-NEED TO APPLY FOR SEPARATE PERMIT FOR | | | CONCRETE BLOCK FENCE AND FOR PARKING | | | WORK. | | | 6-SPECIFY HOW IS THE ONE HOUR TENANT | | | SEPARATION ACHIEVED BETWEEN FIRST AND | | | SECOND FLOOR. SEC 704.3 SBC 1997. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-03-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-03-30 |
Time |
15:43 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2001-03-30 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2001-03-30 00:00:00 | CHECKLIST: | | | 1-DRAWINGS NEED TO BE SIGNED, SEALED AND | | | DATED BY THE ENGINEER AS REQUIRED BY | | | CHAPTER 471 FLORIDA STATUTES. | | | 2-PROVIDE ENERGY CALCULATIONS. | | | 3-CLEARLY SPECIFY SIZE AND TYPE OF | | | EGRESS WINDOWS TO VERIFY THAT THEY | | | COMPLY WITH SEC 1005.4 SBC 1997. | | | 4-PROVIDE CURRENT SBCCI OR DADE COUNTY | | | PRODUCT APPROVAL FOR ALL WINDOWS AND | | | EXTERIOR DOORS TO BE REPLACED. | | | 5-NEED TO APPLY FOR SEPARATE PERMITS FOR | | | MECHANICAL, PLUMBING AND ELECTRICAL | | | WORK. PROVIDE COMPLETE INFORMATION SO | | | PLAN REVIEWERS FOR THOSE DISCIPLINES | | | CAN PERFORM THEIR REVIEWS. | | | 6-SPECIFY SAFETY GLASS WHERE REQUIRED. | | | SEE PLANS AND SEC 2405.2 SBC 1997. | | | 7-THE 6' PRIVACY WALL TO BE DONE UNDER | | | A SEPARATE PERMIT. PROVIDE SURVEY | | | SHOWING EXACT LOCATION AND COMPLETE | | | CONSTRUCTION DETAILS. | | | -WILL NEED LETTER OF RELEASE FROM THE | | | UTILITIES DEPARTMENT. | | | 8-PARKING WORK NEED TO BE DONE UNDER A | | | SEPARATE PERMIT. PROVIDE COMPLETE | | | INFORMATION WHEN APPLYING FOR SUCH | | | PERMIT. | | | 9-CLARIFY IF HAND RAILS ARE NEW, THEN | | | PROVIDE COMPLETE INSTALLATION DETAILS. | | | -SPECIFY CONNECTIONS. | | | 10-CONSTRUCTION VALUE DECLARED BY THE | | | CONTRACTOR IS EXTREMELY LOW. PROVIDE A | | | DETAILED TAKE OFF OF THE SCOPE OF WORK | | | | | | | | | | | | | | | -IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT 659-8096 EXT. 8232. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2001-08-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-08-03 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2001-08-03 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2001-08-03 00:00:00 | GENERAL CONTRACTOR SAID SUB-CONTRACTOR | | | WILL PULL OUT SEPARATE PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2002-01-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-07 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-07 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2001-05-07 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLAN NOTES | | | CALLFOR ELECTRICAL WORK WITH NO DETAIL | | | FOR | | | THAT WORK. PLEASE SUBMIT MORE DETAIL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2001-08-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-02 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-02 |
Time |
15:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2001-07-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-05 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-05 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2001-07-05 00:00:00 | 1) STILL NEED MORE INFORMATION ON | | | EGRESS WINDOWS PLANNED FOR USE. | | | 2) STILL NEED INFORMATION ON INTERIOR | | | FINISH. | | | 3) PLEASE PROVIDE WIDTHS FOR NEW DOORS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-05-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-10 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-10 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2001-05-10 00:00:00 | 1) PLEASE EXPLAIN DOORS ON STAIRS. THEY | | | APPEAR TO OPEN OUTWARD ONTO THE | | | BALCONY LEAVING VERY LITTLE ROOM. | | | 2) PLEASE EXPLAIN NOTES FOR THE EGRESS | | | WINDOWS. | | | 3) NO INTERIOR FINISH INFORMATION | | | PROVIDED FOR WALLS AND CEILINGS OF | | | APARTMENTS. PLEASE SPECIFY CLASS A, B, | | | OR C. | | | 4) WHAT SIZES ARE THE DOORS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-04-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-06 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-06 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2001-04-06 00:00:00 | 1) APARTMENT DOORS ARE TO BE AT LEAST | | | 20 MINUTE FIRE RATED AND BE EQUIPPED | | | WITH SELF-CLOSING DEVICES. | | | 2) INTERIOR FINISH ON WALLS AND CEILINGS | | | TO BE CLASS A OR B. PLEASE NOTE THIS | | | ON PLANS. | | | 3) NO DETAILS PROVIDED FOR EMERGENCY | | | EGRESS WINDOWS. | | | 4) TENANT SEPARATION BETWEEN APARTMENTS | | | TO COMPLY WITH BUILDING CODE | | | REQUIREMENTS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
N |
Date |
2001-08-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-20 |
Time |
10:21 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-08-20 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2001-08-20 00:00:00 | *******************DENIED*************** | | | | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW.PLEASE SUBMIT PLANS WITH MECHAN | | | ICAL PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2001-07-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-25 |
Time |
14:04 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2001-07-25 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2001-07-25 00:00:00 | *******************DENIED*************** | | | | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW.PLEASE SUBMIT PLANS WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-07-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-06 |
Time |
14:59 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-07-06 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2001-07-06 00:00:00 | ********************DENIED************** | | | | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW. | | | | | | PROVIDE EQUIPMENT INFORMATION (MAKE, | | | MODEL, SEER, HEAT KW, ETC.) | | | | | | SHOW LOCATIONS OF EQUIPMENT BEING | | | INSTALLED AS WELL AS DUCT & GRILL SIZES. | | | | | | INDICATE SIZE AND TERMINATION OF | | | CONDENSATE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-05-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-11 |
Time |
14:37 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2001-05-11 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2001-05-11 00:00:00 | *******************DENIED*************** | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW. | | | | | | PLEASE PROVIDE MECHANICAL PLANS WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE | | | CONTACTPATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-05-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-05-07 |
Time |
17:27 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-05-07 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2001-05-07 00:00:00 | REVIEW NOTES.PASSED | | | | | | WATER HEATER PANS REQUIRED FOR WATER | | | HEATERS ON SECOND FLOOR, WITH 1" DRAIN | | | LINES TERMINATING OUTSIDE 6" ABOVE THE | | | GROUND. | | | | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-08-06 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-08-06 |
Time |
08:14 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|