Plan Review Details - Permit 01030517
Plan Review Stops For Permit 01030517
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2002-05-07 00:00:00FOR REVISIONS #6 DATED 3/8/02
 FORREVISIONS #6 DATED 3/8/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2001-12-10 Cont ID  
Sent By jwitmer Date 2001-12-10 Time 13:53 Rev Time 0.50
Received By jwitmer Date 2001-12-10 Time 13:53 Sent To  
Notes
2001-12-10 00:00:00PINNACLE PALMS- CLUBHOUSE
 PERMIT 01030517
 601 EXECUTIVE CENTER DR
 CLUBHOUSE- TRUSSES
  
 1)- FL. ST. STATUTE 61G15-31/003(2)
 TRUSS ENGINEERS ARE TO SIGN ENGINEERING
 TRUSS SHEETS SEE ATTACHED SHEET.
  
 2)- TRUSS DESIGN ENGINEERING DESIGNED TO
 ASCE 7-93 STRUCTURAL S-10 NOTE X WIND
 LOADS BUILDINGS A,B,D & CLUBHOUSE ARE
 DESIGNED TO CHAPTER 16 SBC.
 ONLY BUILDING "C" DESIGNED TO ASCE 7-95.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2001-11-13 Cont ID  
Sent By jwitmer Date 2001-11-13 Time 09:15 Rev Time 1.00
Received By jwitmer Date 2001-11-13 Time 09:15 Sent To  
Notes
2001-11-13 00:00:00REVISION: 11/13/01 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-10-29 Cont ID  
Sent By jwitmer Date 2001-10-29 Time 08:28 Rev Time 1.50
Received By jwitmer Date 2001-10-29 Time 08:28 Sent To  
Notes
2001-10-29 00:00:00REVISION: 10/29/01

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-08-21 Cont ID  
Sent By jwitmer Date 2001-08-21 Time 19:04 Rev Time 0.50
Received By jwitmer Date 2001-08-21 Time 19:04 Sent To  
Notes
2001-08-21 00:00:00REVISION: HEIGTH MODIFICATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-05-18 Cont ID  
Sent By jwitmer Date 2001-05-18 Time 08:01 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-05-18 00:00:00601 EXECUTIVE CENTER DRIVE
 BUILDING: CLUBHOUSE
 PERMIT # 01030517
  
 PROVISO:
 1)- PRODUCT APPROVAL FOR ALL GLAZED OPEN
 INGS & EXTERIOR DOORS WILL BE REQUIRED.
 GLAZED OPENINGS TO COMPLY WITH THE
 CITIES LARGE MISSLE IMPACT POLICY FOR
 GLAZED OPENINGS ON LARGE PROJECTS.
 SBCCI REPORT OR DADE COUNTY REPORT ARE
 ACCEPTED BY THE CITY, (3) COPIES WILL
 BE REQUIRED.
  
 2)- ROOFING WILL REQUIRE A SEPERATE
 PERMIT & WILL ALSO REQUIRE PRODUCT APPRO
 VAL EITHER SBCCI OR DADE COUNTY REPORTS
 ARE ACCEPTED, (3) COPIES WILL BE
 REQUIRED.
  
 3)- WINDOW & DOOR BUCK ATTACHMENT WILL
 BEREQUIRED. IF THE PRODUCT APPROVAL
 DOESN'T SUPPLY THIS INFORMATION IT WILL
 BE THE RESPONSIBILITY OF THE DESIGN
 PROFESSIONAL FOR THE ADDITIONAL
 INFORMATION.
  
 JIM WITMER
 PLAN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-05-07 Cont ID  
Sent By jwitmer Date 2001-05-07 Time 16:32 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-05-07 00:00:00BUILDING PLAN REVIEW
 PLAN CHECK # 01030517
 601 EXECUTIVE CENTER DRIVE
 BUILDING : CLUBHOUSE
  
 1)- DOCUMENTS, PROOF OF OWNERSHIP
  
 2)- NOTICE OF COMMENCEMENT TO BE RECORD-
 ED WITH THE COUNTY COURTHOUSE.
  
 3)- SBC AMENDMENTS 1804.2.7.2 SOILS
 REPORT MISSING.
  
 4)- MISSING DESIGN CRITERIA!
  
 5)- MISSING WINDOW BUCK ATTACHMENT!
  
 6)- PRODUCT APPROVAL FOR ALL GLAZED
 OPENINGS WILL BE REQUIRED FOR ALL OPEN-
 INGS. MUST COMPLY WITH CITY POLICY, WE
 WILL PROVISO ACCORDING TO CITY POLICY.
  
 7)- ROOFING WILL BE UNDER SEPERATE
 PERMIT, REQUIRING PRODUCT APPROVAL
 REPORTS.
  
 8)- FAIR HOUSING ACT SEE A3.1 DETAIL 7:
 SEE SECTION FOR SSIDE REACH FOR HIGH
 LOW SIDE REACH REQUIREMENTS, USE FL.
 ACCESSIBILITY CODE 4.2.6 54".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-11 Cont ID  
Sent By jwitmer Date 2001-04-11 Time 06:37 Rev Time 17.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-11 00:00:00PROJECT: PENNACLE PALMS
 601 EXECUTIVE CENTER DR
 CLUBHOUSE: 01030517
 BUILD. "A" 01040479
 BUILD. "B" 01040480
 BUILD. "C" 01040481
 BUILD. "D" 01040482
 ARCHITECT REG
 P 659-2383
 F
 CONTACT PERSON:SEAN (305)561-3901
 F(305)859-9858
 DELAN CONST: (PROJECT)
  
 THE COMMENTS FOUND IN THIS REVIEW WILL
 BE COMMON TO BUILDINGS A,B,C & D. BUILD-
 ING "C" COMMENTS WILLBE MORE RESTRICTIVE
 SINCE ITS A TYPE II BUILDING.
  
 1)- DOCUMENTS SHOWING OWNERSHIP, THE
 PROPERTY APPRAISERS OFFICE INDICATES
 THAT ASPENWOODS IS STILL THE OWNER.
  
 2)- BEFORE ISSUANCE OF A PERMIT A NOTICE
 OF COMMENCEMENT HAS TO BE FILED & RECORD
 ED WITH THE COUNTY,ONCE FILED WORK HAS
 TO START WITHIN 90 DAYS OR IT WILL BE
 VOID AND WILL BE REQUIRED TO BE REFILED.
  
 3)- THE ADDRESS THAT WAS GIVEN IS WRONG.
 THE CORRECT ADDRESS WILLBE 601 EXECUTIVE
 CENTER DRIVE. ONE SITE ADDRESS WILL BE
 GIVEN AND EACH BUILDING WILL BE ASSIGNED
 A TENANT(BUILDING) ADDRESS.
  
 4)- THE PLANS INDICATE THAT ARDAMAN &
 ASSOCIATES, INC. HAS COMPLETED A SOILS
 TEST, THE BUILDING DEPARTMENT WILL NEED
 A COPY INDICATING THE MINIMUM SAFE BEAR-
 ING CAPACITY OF THE SOIL.
  
 5)MISSING IS THE DESIGN CRITERIA FOR THE
 BUILDINGS. BUILDINGS < 60' IN HEIGHT CAN
 BE DESIGNED TO CHAPTER 16 OF THE SBC.
 BUILDINGS > 60' ARE TO BE DESIGNED TO
 ASCE 7-95.
  
 6)- COMPONENTS & CLADDING:SBC 1606.2.6.2
 ARE TO BE DESIGNED TO MEET WIND LOADS,
 A)- WINDOW & DOOR BUCKS: THE DESIGNER
 OF RECORD NEEDS TO INDICATE THE
 FASTENING SCHEDULE AND THE TYPE OF
 FASTTENERS TO BE USED.
 B)- DOORS, SWING OR OVERHEAD NEED TO
 HAVE PROOF OF PRODUCT TESTING FOR
 WIND. IF THERE IS GLAZING IN THE
 ASSEMBLY SEE WPB POLICY FOR GLAZED
 OPENINGS. WE ACCEPT SBCCI REPORTS
 AS WELL AS DADE COUNTY ACCEPTANCE
 REPORTS.
 C)- GLAZED OPENINGS,WINDOWS DOORS,SLID-
 ING GLASS DOORS WILL REQUIRE PRO-
 DUCT TESTING FOR LARGE MISSLE IM-
 PACT TESTING FOR GLAZED OPENINGS,
 SEE ATTACHED COPY OF THE CITY
 POLICY FOR DETAILS, LARGE, MID OR
 HIGH-RISE STRUCTURES.SBC 1606.4 &
 1707.4.1 AMENDMENTS.
 D)- ROOFING MATERIALS: SBC 1503.3.2.
 ARE TO BE DESIGNED TO 110 MPH WIND.
 1707.5 CEMENT TILE ARE TO BE TESTED
 FOR THERE MOMENT OF OVER TURNING,
 PRODUCT APPROVAL TESTING REPORTS
 ARE REQUIRED.
 E)- SATELLITE DISHES: SEE ATTACHED CITY
 POLICY, REQUIREMENTS FOR PERMITTING
 (COMMERCIAL).
  
 7)- SBC 803.3 PLEASE INDICATE THE MINI-
 MUM INTERIOR FINISH CLASSIFICATION FOR
 THE INTERIOR OF STRUCTURES.
  
 8)- SBC 2304.1.2 COUNTY AMENDMENTS:SOIL
 TREATMENT FOR TERMITES REQUIRED BEFORE
 THE PLACEMENT OF CONCRETE.
  
 9)- SHEET A 2.1 SEC 2/A 5.3 IS MISSING
 THE VERTICAL SHAFT INFORMATION, 4 STOR-
 IES OR MORE REQUIRES 2 HR TABLE 705.2,
 LESS THAN 4 STORIES 1 1/2 HR.
  
 10)- A 9.0 DOOR SCHEDULE DOESN'T INDI-
 CATE THE TYPE OF LABEL NOR THE RATING
 REQUIRED FOR THE DOOR, SBC 104.2.2 ADD-
 ITIONAL INFO REQUIRED.
  
 11)- FL. STATE STATUTE 553.895 WILL
 REQUIRE FIRE SPRINKLER PLANS SINCE THE
 BUILDING WILL BE USED AS A PUBLIC
 LODGING ESTABLISHMENT.SBC 903.7.6.
  
 12)- SBC 905.2 AUTOMATIC FIRE DETECTION
 SYSTEMS REQUIRED.
  
 13)- REFUSE ROOM, PLEASE PROVIDE ADD.
 INFORMATION ON THE FEFUSE CHUTE, 4 STOR-
 IES OR MORE REQUIRES 2 HR RATING, 1 1/2
 HR. PROTECTIVES, , < 4 STORIES 1 1/2
 RATING.
  
 14)- ADDITONAL INFORMATION: A 8.0 STAIR
 SECTION (5) FIRST FLOOR THE SPACE UNDER
 THE STAIRWELL IN DICATES A 3'-0" OPENING
 IS THIS GOING TO BE USED FOR STORAGE?
  
 15)- SHEET A 3.1 DETAIL 2 INDICATES
 METAL LATH, SBC 2504.2.2/ ASTM C 1063
 WHICH WILL BE USED FLAT RIBBED EXSPANDED
 METAL OR 3/8" RIBBED LATH? NAIL SPACING
 FOR HORIZONTAL SURFACES, & PENETRATION
 REQUIRED FOR NAILS OR STAPLES?
  
 16)- S-8 DEPICTS A WX8.5 STEEL BEAM,
 FOR THE A/C ROOF UNITS TO ATTACH TO.
 SHOW ATTACHMENT DETAILS FOR STEEL TO
 BUILDING AND THE WEILD REQUIRED FOR THE
 STRUCTURAL COMPONENTS, 18" MIN. CLEAR-
 ENCE REQUIRED.
  
 17)- TYPE II & TYPE IV BUILDINGS TABLE
 600, 602: TYPE II, 606 : TYPE IV BUILD-
 INGS REQUIRE NONCOMBUSTIBLE MATERIALS
 FOR TRUSSES AND SHEATHING.
  
 18)- TABLE 600:TYPE II BUILDINGS SHOW
 FIRE RESISTANCE RATINGS FOR FLOORS,
 COLUMNS,& BEAMS.
  
 19)- SBC 609.2 NON COMBUSTIBLE MATERIALS
 ARE TO BE USED IN INTERIOR WALLS TYPEII
 NOR TYPE IV CONSTRUCTION. SBC 707
 COMBUSTIBLES IN CONSEALED SPACES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 E 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-04-29 Cont ID  
Sent By dpalmer Date 2002-04-29 Time 19:47 Rev Time 0.00
Received By dpalmer Date 2002-04-29 Time 19:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-05-22 Cont ID  
Sent By dpalmer Date 2001-05-22 Time 16:20 Rev Time 0.00
Received By dpalmer Date 2001-05-22 Time 16:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-05-18 Cont ID  
Sent By dpalmer Date 2001-05-18 Time 14:56 Rev Time 0.00
Received By dpalmer Date 2001-05-18 Time 14:56 Sent To  
Notes
2001-05-18 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED TO
 HAVE SHEET E-8 FOR COMPLETE REVIEW.
 ALL OTHER SHEETS SUBMITTED WERE OK.
  
 PLEASE COMPLETE SET AND SUBMIT FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-04-02 Cont ID  
Sent By dpalmer Date 2001-04-02 Time 18:28 Rev Time 0.00
Received By dpalmer Date 2001-04-02 Time 18:28 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2001-05-17 Cont ID  
Sent By mamini Date 2001-05-17 Time 10:51 Rev Time 2.00
Received By mamini Date 2001-05-17 Time 10:51 Sent To  
Notes
2001-05-17 00:00:00PASSED:
 1. PER OUR MEETING WITH MR. ANTONIO
 QUEVEDO (CIVIL ENGINEER) OF KEITH &
 BALLBE', INC. AT 10:00 AM THIS MORNING
 WITH MR. MIKE CARSILLO IN ATTENDACE, ALL
 PREVIOUS REVIEW COMMENTS HAVE BEEN
 ADDRESSED AND IMPLEMENTED TO FINAL
 CONTRACT PLANS.
 IF ANY QUESTION PLEASE CONTACT 561- 659-
 8096 EXT. 8492

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2001-05-08 Cont ID  
Sent By mamini Date 2001-05-08 Time 08:07 Rev Time 3.00
Received By mamini Date 2001-05-08 Time 08:01 Sent To  
Notes
2001-05-08 00:00:00FAILED:
 1. PLEASE REFER TO PREVIOUS REVIEW
 COMMENTS DATED 4-10-01.SEE ATTACHED

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-04-10 Cont ID  
Sent By mamini Date 2001-04-10 Time 13:14 Rev Time 4.00
Received By mamini Date 2001-04-10 Time 11:18 Sent To  
Notes
2001-04-10 00:00:00FAILED:
 1. PLEASE CHANGE, THE CITY OF SUNRISE TO
 THE CITY OF WEST PALM BEACH IN GENERAL
 NOTES. SEE SHEET GN1 OF 1
 2. PLEASE PROVIDE POLLUTION PREVENTION
 PLAN.THE POLLUTION PREVENTION PLAN
 SHALL BE INSTALLED IN THE FILED PRIOR
 TO ANY EARTHWORK.THE POLLUTION
 PREVENTION PLAN SHALL BE KEPT ON SITE AT
 ALL TIME DURING CONSTRUCTIONS.
 3. PLEASE PROVIDE DRAINAGE CALCULATIONS
 TO JOSE DEL RIO, STORM WATER ENGINEER
 100045TH STREET WEST PALM BEACH, FL
 33415(561) 659- 8040 FOR APPROVAL.
 4. PLEASE PROVIDE PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR ENTIRE SITE
 SIGNED AND SEALED BY DESIGN ENGINEER.
 THIS INFORMATION SHOULD SUBMITTED ON A
 8 1/2 X 11 SHEET WITH PROPERTY CONTROL
 NUMBER, NAME AND ADDRESS.SUBMITT TO
 MANNY GONZALEZ , 100045TH STREET WEST
 PALM BEACH, FL 33415(561) 659- 8040.
 5. ALL DRIVEWAY APPROACHES MUST BE AT
 MINIMUM PER THE CITY OF WEST PALM BAECH
 STANDARD.
 6. THE "APPLICATION FOR CONSTRUCTION
 WITHIN PUBLIC R.O.W" MUST BE SUBMITTED
 TO CITY ENGINEER, RICHARD PITTMAN,AT
 100045TH STREET WEST PALM BEACH, FL
 33415(651) 659- 8040.
 7. PERIMETER BERM SHOULD BE CONSTRUCTED
 AT 18.27 AS SHOWN IN DETAILS A-A & B-B
 ON SHEET PD2 OF 2. SHEET PD1 OF 2 SHOWS
 8.27.
 8. PLEASE SHOW INVERT ELEVATION FOR
 WATER MAIN AND CROWN ELEVATION FOR SEWER
 LINE AS MARKED ON SHEET WS1 OF 8.
 9. A CLEAN-OUT WILL NEED TO BE INSTALLED
 IN SANITARY SEWER LATERAL, ON THE
 PROPERTY, AT THE BACK OF SIDEWALK.
 10. A SEPARATE IRRIGATION METER IS
 SUGGESTED, AN APPROVED BACKFLOW
 PREVENTER WILL NEED TO BE INSTALLED ON
 THIS LINE.
 IF ANY QUESTION PLEASE CONTACT (561)-
 659-8096 EXT. 8492

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-05-10 Cont ID  
Sent By mcarsill Date 2002-05-10 Time 10:01 Rev Time 0.00
Received By mcarsill Date 2002-05-10 Time 10:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-05-17 Cont ID  
Sent By mcarsill Date 2001-05-17 Time 09:42 Rev Time 0.00
Received By mcarsill Date 2001-05-17 Time 09:42 Sent To  
Notes
2001-05-17 00:00:001) MISSING ELECTRICAL PAGES NOTED. THEY
 INCLUDE E7,E8,E9,E10,E11.
 2) ON 5/16/01 WRITER SPOKE TO JIM
 GILLESPIE OF GILLESPIE AND ASSOCIATES,
 795-0833. HE ADVISED THAT A SEPARATE
 SERVICE FROM A TRANSFORMER FEEDS THE
 FIRE PUMP INTO A SERVICE RATED FIRE
 PUMP CONTROLLER. THE MISSING DRAWINGS
 ARE TO BE BROUGHT TO CITY HALL BY REG.
 3) EXIT SIGN SHOULD BE RELOCATED OVER
 DOOR THAT OPENS BETWEEN THE PLANTER AND
 COLUMN.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-05-02 Cont ID  
Sent By mcarsill Date 2001-05-01 Time 15:19 Rev Time 0.00
Received By mcarsill Date 2001-05-01 Time 15:18 Sent To  
Notes
2001-05-01 00:00:001) ALL UNDERGROUND FIRE MAINS ARE TO BE
 LISTED FOR FIRE PROTECTION SERVICE AND
 COMPLY WITH NFPA 24, FIRE SERVICE MAINS
 AND THEIR APPURTENANCES.
 2) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATION OF THE FIRE
 SPRINKLER SYSTEM AND FIRE PUMP ASSEMBLY.
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATION OF THE FIRE ALARM
 SYSTEM. CUT SHEETS, WIRING DIAGRAM, AND
 BATTERY CALCULATIONS ARE TO BE PROVIDED.
 4) FIRE SPRINKLER SYSTEM AND FIRE ALARM
 SYSTEMS ARE TO BE SUPERVISED BY A
 LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 5) EMERGENCY LIGHTING REQUIRED IN
 CARD,PARTY, TV ROOM.
 6) INGRESS AND EGRESS INTO THE COMPLEX
 SHALL BE A MINIMUM OF TWENTY FEET IN
 CLEAR WIDTH. BATTERY BACK-UP FEATURE
 SHALL BE PROVIDED FOR GATE-ARMS SHOULD
 LOSS OF POWER OCCUR. TRAFFIC CALMING
 HUMPS ARE NOT TO INTERFERE WITH FIRE
 RESCUE MOVEMENT INTO THE COMPLEX.
 7) PLEASE INDICATE PORTABLE FIRE
 EXTINGUISHER LOCATIONS.
 8) PLEASE EXPLAIN RATIONALE FOR THE
 SINGLE FIRE DEPARTMENT CONNECTION SHOWN
 ON THE OTHER DRAWINGS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-03-14 Cont ID  
Sent By mcarsill Date 2001-03-14 Time 10:52 Rev Time 0.00
Received By mcarsill Date 2001-03-14 Time 10:52 Sent To  
Notes
2001-03-14 00:00:001) PLEASE INDICATE FIRE RESCUE ACCESS
 INTO THE APARTMENT COMPLEX. THE OPENING
 THAT FIRE RESCUE IS EXPECTED TO PASS
 THRU MUST BE AT LEAST 20 FEET IN CLEAR
 WIDTH. HOW DOES FIRE RESCUE EQUIPMENT
 PASS THE SECURITY FEATURES PLANNED FOR
 THE COMPLEX DRIVE OPENINGS.
 2) UNDERGROUND FIRE LINES, FIRE HYDRANTS
 AND APPURTENACES TO COMPLY WITH NFPA 24.
 THIS EQUIPMENT TO MEET UTILITY AND FIRE
 RESCUE STANDARDS. WET FIRE HYDRANTS ARE
 TO BE PROVIDED PRIOR TO, DURING AND
 AFTER CONSTRUCTION.
 3) PLEASE INDICATE IF GATES OR FRAME
 ARMS WILL BE PROVIDED FOR SECURITY
 PURPOSES.
 4) BUILDING ADDRESSES REQUIRED PER CITY
 CODE REQUIREMENTS.
 5) CLUBHOUSE TO PROVIDE PROVISIONS FOR
 AT LEAST TWO HANDICAPPED PERSONS.
 6) PLEASE INDICATE HOW THE DRYER CHASE
 CAN BE CLEANED OF COMBUSTIBLE LINT
 BUILD-UP. PLEASE PROVIDE UL NUMBERS FOR
 ALL SHAFTS.
 7) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER DRAWINGS. ALL
 BUILDINGS ARE TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED. ALL ELECTRICAL,
 MECHANICAL AND SERVICE ROOMS ARE TO BE
 PROTECTED WITH FIRE SPRINKLER HEADS.
 ALSO ALL VERTICAL SHAFTS ARE TO BE
 FIRE SPRINKLER PROTECTED.
 8) EMERGENCY LIGHTING REQUIRED IN FIRE
 PUMP ROOM. OKAY, LOCATED ON PLANS.
 9) ALL BUILDINGS THREE STORIES OR MORE
 AND 50 FEET IN HEIGHT MUST HAVE
 STANDPIPE SYSTEMS IN ACCORDANCE WITH
 NFPA 14.
 10) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, THE LIFE SAFETY CODE, 1985
 EDITION.
 11) MORE DETAILS NEEDED FOR FIRE PUMP
 EQUIPMENT AND APPURTENANCES.
 12) IS ACCESS PROVIDED INTO THE WOOD
 TRUSS AREA.
 13) TENANT SEPARATIONS TO COMPLY WITH
 BUILDING CODE REQUIREMENTS.
 14) PLEASE BE ADVISED OF THE STRETCHER
 REQUIREMENTS OF THE STANDARD BUILDING
 CODE, SECTION 3003.4 FOR BUILDINGS FOUR
 OR MORE FLOORS.
 15) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION.
 16) IS BATTERY BACK-UP PLANNED FOR THE
 SECURITY FEATURES AT THE ENTRANCE SHOULD
 LOSS OF POWER RESULT.
 17) DOES THE NOTE ON PAGE E12 MEAN
 ONLY A SINGLE FIRE ALARM PANEL FOR THE
 COMPLEX. WHAT HAPPENS WHEN THIS PANEL
 IS DOWN FOR REPAIRS OR REPLACEMENT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pkrauss Date 2002-04-26 Time 07:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-05-24 Cont ID  
Sent By pkrauss Date 2001-05-24 Time 07:45 Rev Time 0.20
Received By pkrauss Date 2001-05-24 Time 07:45 Sent To  
Notes
2001-05-24 00:00:00NOTES ON PERMIT 01040480

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-05-10 Cont ID  
Sent By pkrauss Date 2001-05-10 Time 15:22 Rev Time 0.30
Received By pkrauss Date 2001-05-10 Time 15:15 Sent To  
Notes
2001-05-10 00:00:00*******************PROVISO**************
  
 IF COPPER IS BEING USED FOR CHILLED WATE
 R LINES IS SHALL BE BRAZED AS PER 1997 S
 MC TABLE 1205.
  
 ADDITIONAL PERMIT REQUIRED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-03-26 Cont ID  
Sent By pkrauss Date 2001-03-26 Time 14:35 Rev Time 2.00
Received By pkrauss Date 2001-03-26 Time 12:45 Sent To  
Notes
2001-03-26 00:00:00 
  
  
 PLEASE PROVIDE DETAILS FOR CONDENSER
 STANDS ON ROOF.
  
 NO OUTSIDE AIR CALCULATIONS FOR CLUB
 HOUSE AS PER ASHREA 62-89.
  
 NO AIR BALANCE SCHEDULE.
  
 INDICATE ACCESS FOR CLEANING OF DRYER
 EXHAUST VENTS.
  
 ARE STAIRWELL ENCLOSURES OPEN?

Review Stop P PLUMBING
Rev No 9 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 8 Status P Date 2003-01-22 Cont ID  
Sent By kstevens Date 2003-01-22 Time 08:59 Rev Time 0.10
Received By kstevens Date 2003-01-22 Time 08:58 Sent To  
Notes
2003-01-22 00:00:00SUBMITTAL - DOMESTIC PUMP PACKAGE

Review Stop P PLUMBING
Rev No 7 Status P Date 2002-02-20 Cont ID  
Sent By kstevens Date 2002-02-20 Time 10:58 Rev Time 0.50
Received By kstevens Date 2002-02-20 Time 10:58 Sent To  
Notes
2002-02-20 00:00:00REVISION FOR AIR CHAMBERS/W-HEATER KIT.
 AREA

Review Stop P PLUMBING
Rev No 6 Status F Date 2002-02-10 Cont ID  
Sent By pschmitz Date 2002-02-10 Time 09:21 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-02-10 00:00:00DENIEDPAUL SCHMITZ
 REVISIONS FOR SHTS P-6, A2-4,ONLY ONE
 SHT OF EACH SUBMITTED
 561 659-8096X8233

Review Stop P PLUMBING
Rev No 5 Status F Date 2001-11-29 Cont ID  
Sent By kstevens Date 2001-11-29 Time 16:35 Rev Time 0.33
Received By kstevens Date 2001-11-29 Time 16:35 Sent To  
Notes
2001-11-29 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PREVIOUS COMMENTS NOT ADDRESSED.
 2) SHT P-6 WATER HAMMER ARRESTORS SHALL
 BE LOCATED CLOSE TO FIXTURES IN AN
 "EFFECTIVE RANGE" NOT AT TOP OF DROPS AS
 SHOWN.
 3) SHT A2.4 WATER HEATER IN A/C CLOSET
 BY KITCHENETTE AND WATER HEATER CH-2 UN-
 DER COUNTER AT SINK ON WATER RISER DIA-
 GRAM SHT P-6. PLEASE CLARIFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-10-19 Cont ID  
Sent By kstevens Date 2001-10-19 Time 16:28 Rev Time 0.33
Received By kstevens Date 2001-10-19 Time 16:27 Sent To  
Notes
2001-10-19 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHEET P-6 AIRCHAMBERS SEC 607.8.3
 ACCESSIBLE & RECHARGEABLE, "TEMPORARY
 FIX". USE WATER HAMMER ARRESTORS AND
 SIZE AND LOCATE PER MANUFACTURE INSTALL-
 ATION INSTRUCTIONS AND WH-PDI 201. NOT
 AT TOP OF DROP BUT NEAR SOURCE (FIXTURE)
  
 2) SHEET A2.4 WATER HEATER IN A/C CLOSET
 BY KITCHENETTE AND WATER HEATER CH-2 UN-
 DER COUNTER AT SINK ON WATER RISER DIA-
 GRAM SHEET P-6. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-09-28 Cont ID  
Sent By kstevens Date 2001-09-28 Time 15:41 Rev Time 0.33
Received By kstevens Date 2001-09-28 Time 15:41 Sent To  
Notes
2001-09-28 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHEET P-6 AIR CHAMBERS SEC 607.8.3
 ACCESSIBLE AND RECHARGEABLE, "TEMPORARY
 FIX". USE WATER HAMMER ARRESTORS. SIZED
 AND LOCATED PER MANUFACTURE
 INSTALLATION INSTRUCTIONS AND WH-PDI 201
  
 2) SHEET A2.4 WATER HEATER IN A/C CLOSET
 BY KITCHENETTE AND WATER HEATER CH-2 UN-
 DER COUNTER AT SINK ON WATER RISER DIA-
 GRAM SHEET P-6. PLEASE CLARIFY.
  
 3) SHEET A2.4 & A8.1 KITCHENETTE SINK TO
 COMPLY WITH FACBC-97 SEC 4.24
  
 4) SHEET A8.1 URNAL TO COMPLY WITH FACBC
 -97 SEC 4.18.2 & 4.22.5. 17" TO LIP AFF
 AND SHOW CLEAR FLOOR SPACE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-05-17 Cont ID  
Sent By kstevens Date 2001-05-17 Time 14:52 Rev Time 1.00
Received By kstevens Date 2001-05-17 Time 14:52 Sent To  
Notes
2001-05-17 00:00:00NOTE:
  
 URNAL TO COMPLY WITH FACBC-97
 4.18.2 & 4.22.5

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-04-06 Cont ID  
Sent By jleech Date 2001-04-06 Time 14:26 Rev Time 8.00
Received By jleech Date 2001-04-06 Time 14:26 Sent To  
Notes
2001-04-06 00:00:00DENIED;
  
 1.(GENERAL NOTES) #15. COPIES OF ALL
 DOCUMENTS TO BE FILED WITH THE
 DEPARTMENT OF CONSTRUCTION SERVICES.
 CHANGE "A" TO CITY OF WEST PALM BEACH.
 "L" SAME AS "A".
  
 2.BACKFLOW PREVENTERS SHALL BE INSTALLED
 AT EACH BUILDING.
  
 3.(SEWAGE COLLECTION SYSTEM) NOTE 8.
 TWO COATS SHALL BE APPLIED TO THE OUT
 SIDE.
  
 4.(WATER DISTRIBUTION SYSTEM) NOTE 3
 CITY OF WEST PAKM BEACH NOT SUNRISE.
  
 5.WATER HAMMER ARRESTERS TO COMPLY WITH
 607.8.1, 607.8.2 AND 608.8.3
  
 6.PAGE P-3 WASTE RISER S3 AND S4. THREE
 INCH. STACK MAXIMUM LENTH IS 50 FT.
 FROM THE HOUSE DRAIN THRU THE ROOF.
 SPC 911.4 AND TABLE 911.4.
  
 7.PAGE P-6 FLOOR DRAINS IN PUBLIC REST-
 ROOMS SHALL HAVE TRAP PRIMERS.FLOOR
 DRAINS IN LAUNDRY ROOM SHALL BE DEEP
 SEAL. SEC. 409.4.1.1 AND 409.4.1.4.
  
 8.PAGE A8.1 SHOW MEASURMENTS FOR TOILET
 LOCATION. SHOW THE 18"SIDE TO COMPLY
 WITH THE FHA.
  
 9.WHAT HIGHT ABOVE THE ROOF ARE THE
 OVERFLOW DRAINS SET ABOVE THE ROOF?
  
 10.SHOW NUMBER OF UNITS IN EACH BUILDING
 THAT WILL BE FURNISHED WITH GRAB BARS
 AND HANDICAP ACCESSORIES.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-22 Cont ID  
Sent By sgraham Date 2001-05-04 Time 14:02 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-05-22 00:00:00APPROVED ANGELLAVANN
2001-05-04 00:00:00NEED MINOR AMENDENTS


Account Summary | Usage Policy | Privacy Policy