| Plan Review Stops For Permit 01030517 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-07 00:00:00 | FOR REVISIONS #6 DATED 3/8/02 | | | FORREVISIONS #6 DATED 3/8/02 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-12-10 |
Time |
13:53 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2001-12-10 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2001-12-10 00:00:00 | PINNACLE PALMS- CLUBHOUSE | | | PERMIT 01030517 | | | 601 EXECUTIVE CENTER DR | | | CLUBHOUSE- TRUSSES | | | | | | 1)- FL. ST. STATUTE 61G15-31/003(2) | | | TRUSS ENGINEERS ARE TO SIGN ENGINEERING | | | TRUSS SHEETS SEE ATTACHED SHEET. | | | | | | 2)- TRUSS DESIGN ENGINEERING DESIGNED TO | | | ASCE 7-93 STRUCTURAL S-10 NOTE X WIND | | | LOADS BUILDINGS A,B,D & CLUBHOUSE ARE | | | DESIGNED TO CHAPTER 16 SBC. | | | ONLY BUILDING "C" DESIGNED TO ASCE 7-95. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2001-11-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-13 |
Time |
09:15 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2001-11-13 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2001-11-13 00:00:00 | REVISION: 11/13/01 JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-29 |
Time |
08:28 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2001-10-29 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | REVISION: 10/29/01 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2001-08-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-21 |
Time |
19:04 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2001-08-21 |
Time |
19:04 |
Sent To |
|
|
| Notes |
| 2001-08-21 00:00:00 | REVISION: HEIGTH MODIFICATIONS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-05-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-18 |
Time |
08:01 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-18 00:00:00 | 601 EXECUTIVE CENTER DRIVE | | | BUILDING: CLUBHOUSE | | | PERMIT # 01030517 | | | | | | PROVISO: | | | 1)- PRODUCT APPROVAL FOR ALL GLAZED OPEN | | | INGS & EXTERIOR DOORS WILL BE REQUIRED. | | | GLAZED OPENINGS TO COMPLY WITH THE | | | CITIES LARGE MISSLE IMPACT POLICY FOR | | | GLAZED OPENINGS ON LARGE PROJECTS. | | | SBCCI REPORT OR DADE COUNTY REPORT ARE | | | ACCEPTED BY THE CITY, (3) COPIES WILL | | | BE REQUIRED. | | | | | | 2)- ROOFING WILL REQUIRE A SEPERATE | | | PERMIT & WILL ALSO REQUIRE PRODUCT APPRO | | | VAL EITHER SBCCI OR DADE COUNTY REPORTS | | | ARE ACCEPTED, (3) COPIES WILL BE | | | REQUIRED. | | | | | | 3)- WINDOW & DOOR BUCK ATTACHMENT WILL | | | BEREQUIRED. IF THE PRODUCT APPROVAL | | | DOESN'T SUPPLY THIS INFORMATION IT WILL | | | BE THE RESPONSIBILITY OF THE DESIGN | | | PROFESSIONAL FOR THE ADDITIONAL | | | INFORMATION. | | | | | | JIM WITMER | | | PLAN REVIEW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-05-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-07 |
Time |
16:32 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-07 00:00:00 | BUILDING PLAN REVIEW | | | PLAN CHECK # 01030517 | | | 601 EXECUTIVE CENTER DRIVE | | | BUILDING : CLUBHOUSE | | | | | | 1)- DOCUMENTS, PROOF OF OWNERSHIP | | | | | | 2)- NOTICE OF COMMENCEMENT TO BE RECORD- | | | ED WITH THE COUNTY COURTHOUSE. | | | | | | 3)- SBC AMENDMENTS 1804.2.7.2 SOILS | | | REPORT MISSING. | | | | | | 4)- MISSING DESIGN CRITERIA! | | | | | | 5)- MISSING WINDOW BUCK ATTACHMENT! | | | | | | 6)- PRODUCT APPROVAL FOR ALL GLAZED | | | OPENINGS WILL BE REQUIRED FOR ALL OPEN- | | | INGS. MUST COMPLY WITH CITY POLICY, WE | | | WILL PROVISO ACCORDING TO CITY POLICY. | | | | | | 7)- ROOFING WILL BE UNDER SEPERATE | | | PERMIT, REQUIRING PRODUCT APPROVAL | | | REPORTS. | | | | | | 8)- FAIR HOUSING ACT SEE A3.1 DETAIL 7: | | | SEE SECTION FOR SSIDE REACH FOR HIGH | | | LOW SIDE REACH REQUIREMENTS, USE FL. | | | ACCESSIBILITY CODE 4.2.6 54". | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-04-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-11 |
Time |
06:37 |
Rev Time |
17.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-11 00:00:00 | PROJECT: PENNACLE PALMS | | | 601 EXECUTIVE CENTER DR | | | CLUBHOUSE: 01030517 | | | BUILD. "A" 01040479 | | | BUILD. "B" 01040480 | | | BUILD. "C" 01040481 | | | BUILD. "D" 01040482 | | | ARCHITECT REG | | | P 659-2383 | | | F | | | CONTACT PERSON:SEAN (305)561-3901 | | | F(305)859-9858 | | | DELAN CONST: (PROJECT) | | | | | | THE COMMENTS FOUND IN THIS REVIEW WILL | | | BE COMMON TO BUILDINGS A,B,C & D. BUILD- | | | ING "C" COMMENTS WILLBE MORE RESTRICTIVE | | | SINCE ITS A TYPE II BUILDING. | | | | | | 1)- DOCUMENTS SHOWING OWNERSHIP, THE | | | PROPERTY APPRAISERS OFFICE INDICATES | | | THAT ASPENWOODS IS STILL THE OWNER. | | | | | | 2)- BEFORE ISSUANCE OF A PERMIT A NOTICE | | | OF COMMENCEMENT HAS TO BE FILED & RECORD | | | ED WITH THE COUNTY,ONCE FILED WORK HAS | | | TO START WITHIN 90 DAYS OR IT WILL BE | | | VOID AND WILL BE REQUIRED TO BE REFILED. | | | | | | 3)- THE ADDRESS THAT WAS GIVEN IS WRONG. | | | THE CORRECT ADDRESS WILLBE 601 EXECUTIVE | | | CENTER DRIVE. ONE SITE ADDRESS WILL BE | | | GIVEN AND EACH BUILDING WILL BE ASSIGNED | | | A TENANT(BUILDING) ADDRESS. | | | | | | 4)- THE PLANS INDICATE THAT ARDAMAN & | | | ASSOCIATES, INC. HAS COMPLETED A SOILS | | | TEST, THE BUILDING DEPARTMENT WILL NEED | | | A COPY INDICATING THE MINIMUM SAFE BEAR- | | | ING CAPACITY OF THE SOIL. | | | | | | 5)MISSING IS THE DESIGN CRITERIA FOR THE | | | BUILDINGS. BUILDINGS < 60' IN HEIGHT CAN | | | BE DESIGNED TO CHAPTER 16 OF THE SBC. | | | BUILDINGS > 60' ARE TO BE DESIGNED TO | | | ASCE 7-95. | | | | | | 6)- COMPONENTS & CLADDING:SBC 1606.2.6.2 | | | ARE TO BE DESIGNED TO MEET WIND LOADS, | | | A)- WINDOW & DOOR BUCKS: THE DESIGNER | | | OF RECORD NEEDS TO INDICATE THE | | | FASTENING SCHEDULE AND THE TYPE OF | | | FASTTENERS TO BE USED. | | | B)- DOORS, SWING OR OVERHEAD NEED TO | | | HAVE PROOF OF PRODUCT TESTING FOR | | | WIND. IF THERE IS GLAZING IN THE | | | ASSEMBLY SEE WPB POLICY FOR GLAZED | | | OPENINGS. WE ACCEPT SBCCI REPORTS | | | AS WELL AS DADE COUNTY ACCEPTANCE | | | REPORTS. | | | C)- GLAZED OPENINGS,WINDOWS DOORS,SLID- | | | ING GLASS DOORS WILL REQUIRE PRO- | | | DUCT TESTING FOR LARGE MISSLE IM- | | | PACT TESTING FOR GLAZED OPENINGS, | | | SEE ATTACHED COPY OF THE CITY | | | POLICY FOR DETAILS, LARGE, MID OR | | | HIGH-RISE STRUCTURES.SBC 1606.4 & | | | 1707.4.1 AMENDMENTS. | | | D)- ROOFING MATERIALS: SBC 1503.3.2. | | | ARE TO BE DESIGNED TO 110 MPH WIND. | | | 1707.5 CEMENT TILE ARE TO BE TESTED | | | FOR THERE MOMENT OF OVER TURNING, | | | PRODUCT APPROVAL TESTING REPORTS | | | ARE REQUIRED. | | | E)- SATELLITE DISHES: SEE ATTACHED CITY | | | POLICY, REQUIREMENTS FOR PERMITTING | | | (COMMERCIAL). | | | | | | 7)- SBC 803.3 PLEASE INDICATE THE MINI- | | | MUM INTERIOR FINISH CLASSIFICATION FOR | | | THE INTERIOR OF STRUCTURES. | | | | | | 8)- SBC 2304.1.2 COUNTY AMENDMENTS:SOIL | | | TREATMENT FOR TERMITES REQUIRED BEFORE | | | THE PLACEMENT OF CONCRETE. | | | | | | 9)- SHEET A 2.1 SEC 2/A 5.3 IS MISSING | | | THE VERTICAL SHAFT INFORMATION, 4 STOR- | | | IES OR MORE REQUIRES 2 HR TABLE 705.2, | | | LESS THAN 4 STORIES 1 1/2 HR. | | | | | | 10)- A 9.0 DOOR SCHEDULE DOESN'T INDI- | | | CATE THE TYPE OF LABEL NOR THE RATING | | | REQUIRED FOR THE DOOR, SBC 104.2.2 ADD- | | | ITIONAL INFO REQUIRED. | | | | | | 11)- FL. STATE STATUTE 553.895 WILL | | | REQUIRE FIRE SPRINKLER PLANS SINCE THE | | | BUILDING WILL BE USED AS A PUBLIC | | | LODGING ESTABLISHMENT.SBC 903.7.6. | | | | | | 12)- SBC 905.2 AUTOMATIC FIRE DETECTION | | | SYSTEMS REQUIRED. | | | | | | 13)- REFUSE ROOM, PLEASE PROVIDE ADD. | | | INFORMATION ON THE FEFUSE CHUTE, 4 STOR- | | | IES OR MORE REQUIRES 2 HR RATING, 1 1/2 | | | HR. PROTECTIVES, , < 4 STORIES 1 1/2 | | | RATING. | | | | | | 14)- ADDITONAL INFORMATION: A 8.0 STAIR | | | SECTION (5) FIRST FLOOR THE SPACE UNDER | | | THE STAIRWELL IN DICATES A 3'-0" OPENING | | | IS THIS GOING TO BE USED FOR STORAGE? | | | | | | 15)- SHEET A 3.1 DETAIL 2 INDICATES | | | METAL LATH, SBC 2504.2.2/ ASTM C 1063 | | | WHICH WILL BE USED FLAT RIBBED EXSPANDED | | | METAL OR 3/8" RIBBED LATH? NAIL SPACING | | | FOR HORIZONTAL SURFACES, & PENETRATION | | | REQUIRED FOR NAILS OR STAPLES? | | | | | | 16)- S-8 DEPICTS A WX8.5 STEEL BEAM, | | | FOR THE A/C ROOF UNITS TO ATTACH TO. | | | SHOW ATTACHMENT DETAILS FOR STEEL TO | | | BUILDING AND THE WEILD REQUIRED FOR THE | | | STRUCTURAL COMPONENTS, 18" MIN. CLEAR- | | | ENCE REQUIRED. | | | | | | 17)- TYPE II & TYPE IV BUILDINGS TABLE | | | 600, 602: TYPE II, 606 : TYPE IV BUILD- | | | INGS REQUIRE NONCOMBUSTIBLE MATERIALS | | | FOR TRUSSES AND SHEATHING. | | | | | | 18)- TABLE 600:TYPE II BUILDINGS SHOW | | | FIRE RESISTANCE RATINGS FOR FLOORS, | | | COLUMNS,& BEAMS. | | | | | | 19)- SBC 609.2 NON COMBUSTIBLE MATERIALS | | | ARE TO BE USED IN INTERIOR WALLS TYPEII | | | NOR TYPE IV CONSTRUCTION. SBC 707 | | | COMBUSTIBLES IN CONSEALED SPACES. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 E 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-04-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-04-29 |
Time |
19:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-04-29 |
Time |
19:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-05-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-22 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-22 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-18 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-18 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2001-05-18 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED TO | | | HAVE SHEET E-8 FOR COMPLETE REVIEW. | | | ALL OTHER SHEETS SUBMITTED WERE OK. | | | | | | PLEASE COMPLETE SET AND SUBMIT FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-04-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-02 |
Time |
18:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-02 |
Time |
18:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2001-05-17 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-05-17 |
Time |
10:51 |
Rev Time |
2.00 |
| Received By |
mamini |
Date |
2001-05-17 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2001-05-17 00:00:00 | PASSED: | | | 1. PER OUR MEETING WITH MR. ANTONIO | | | QUEVEDO (CIVIL ENGINEER) OF KEITH & | | | BALLBE', INC. AT 10:00 AM THIS MORNING | | | WITH MR. MIKE CARSILLO IN ATTENDACE, ALL | | | PREVIOUS REVIEW COMMENTS HAVE BEEN | | | ADDRESSED AND IMPLEMENTED TO FINAL | | | CONTRACT PLANS. | | | IF ANY QUESTION PLEASE CONTACT 561- 659- | | | 8096 EXT. 8492 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2001-05-08 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-05-08 |
Time |
08:07 |
Rev Time |
3.00 |
| Received By |
mamini |
Date |
2001-05-08 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2001-05-08 00:00:00 | FAILED: | | | 1. PLEASE REFER TO PREVIOUS REVIEW | | | COMMENTS DATED 4-10-01.SEE ATTACHED |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-04-10 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-04-10 |
Time |
13:14 |
Rev Time |
4.00 |
| Received By |
mamini |
Date |
2001-04-10 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2001-04-10 00:00:00 | FAILED: | | | 1. PLEASE CHANGE, THE CITY OF SUNRISE TO | | | THE CITY OF WEST PALM BEACH IN GENERAL | | | NOTES. SEE SHEET GN1 OF 1 | | | 2. PLEASE PROVIDE POLLUTION PREVENTION | | | PLAN.THE POLLUTION PREVENTION PLAN | | | SHALL BE INSTALLED IN THE FILED PRIOR | | | TO ANY EARTHWORK.THE POLLUTION | | | PREVENTION PLAN SHALL BE KEPT ON SITE AT | | | ALL TIME DURING CONSTRUCTIONS. | | | 3. PLEASE PROVIDE DRAINAGE CALCULATIONS | | | TO JOSE DEL RIO, STORM WATER ENGINEER | | | 100045TH STREET WEST PALM BEACH, FL | | | 33415(561) 659- 8040 FOR APPROVAL. | | | 4. PLEASE PROVIDE PERVIOUS AND | | | IMPERVIOUS CALCULATIONS FOR ENTIRE SITE | | | SIGNED AND SEALED BY DESIGN ENGINEER. | | | THIS INFORMATION SHOULD SUBMITTED ON A | | | 8 1/2 X 11 SHEET WITH PROPERTY CONTROL | | | NUMBER, NAME AND ADDRESS.SUBMITT TO | | | MANNY GONZALEZ , 100045TH STREET WEST | | | PALM BEACH, FL 33415(561) 659- 8040. | | | 5. ALL DRIVEWAY APPROACHES MUST BE AT | | | MINIMUM PER THE CITY OF WEST PALM BAECH | | | STANDARD. | | | 6. THE "APPLICATION FOR CONSTRUCTION | | | WITHIN PUBLIC R.O.W" MUST BE SUBMITTED | | | TO CITY ENGINEER, RICHARD PITTMAN,AT | | | 100045TH STREET WEST PALM BEACH, FL | | | 33415(651) 659- 8040. | | | 7. PERIMETER BERM SHOULD BE CONSTRUCTED | | | AT 18.27 AS SHOWN IN DETAILS A-A & B-B | | | ON SHEET PD2 OF 2. SHEET PD1 OF 2 SHOWS | | | 8.27. | | | 8. PLEASE SHOW INVERT ELEVATION FOR | | | WATER MAIN AND CROWN ELEVATION FOR SEWER | | | LINE AS MARKED ON SHEET WS1 OF 8. | | | 9. A CLEAN-OUT WILL NEED TO BE INSTALLED | | | IN SANITARY SEWER LATERAL, ON THE | | | PROPERTY, AT THE BACK OF SIDEWALK. | | | 10. A SEPARATE IRRIGATION METER IS | | | SUGGESTED, AN APPROVED BACKFLOW | | | PREVENTER WILL NEED TO BE INSTALLED ON | | | THIS LINE. | | | IF ANY QUESTION PLEASE CONTACT (561)- | | | 659-8096 EXT. 8492 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2002-05-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-10 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-10 |
Time |
10:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-05-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-17 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-17 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2001-05-17 00:00:00 | 1) MISSING ELECTRICAL PAGES NOTED. THEY | | | INCLUDE E7,E8,E9,E10,E11. | | | 2) ON 5/16/01 WRITER SPOKE TO JIM | | | GILLESPIE OF GILLESPIE AND ASSOCIATES, | | | 795-0833. HE ADVISED THAT A SEPARATE | | | SERVICE FROM A TRANSFORMER FEEDS THE | | | FIRE PUMP INTO A SERVICE RATED FIRE | | | PUMP CONTROLLER. THE MISSING DRAWINGS | | | ARE TO BE BROUGHT TO CITY HALL BY REG. | | | 3) EXIT SIGN SHOULD BE RELOCATED OVER | | | DOOR THAT OPENS BETWEEN THE PLANTER AND | | | COLUMN. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-05-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-01 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-01 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2001-05-01 00:00:00 | 1) ALL UNDERGROUND FIRE MAINS ARE TO BE | | | LISTED FOR FIRE PROTECTION SERVICE AND | | | COMPLY WITH NFPA 24, FIRE SERVICE MAINS | | | AND THEIR APPURTENANCES. | | | 2) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE INSTALLATION OF THE FIRE | | | SPRINKLER SYSTEM AND FIRE PUMP ASSEMBLY. | | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE INSTALLATION OF THE FIRE ALARM | | | SYSTEM. CUT SHEETS, WIRING DIAGRAM, AND | | | BATTERY CALCULATIONS ARE TO BE PROVIDED. | | | 4) FIRE SPRINKLER SYSTEM AND FIRE ALARM | | | SYSTEMS ARE TO BE SUPERVISED BY A | | | LICENSED UL LISTED CENTRAL STATION | | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | | 5) EMERGENCY LIGHTING REQUIRED IN | | | CARD,PARTY, TV ROOM. | | | 6) INGRESS AND EGRESS INTO THE COMPLEX | | | SHALL BE A MINIMUM OF TWENTY FEET IN | | | CLEAR WIDTH. BATTERY BACK-UP FEATURE | | | SHALL BE PROVIDED FOR GATE-ARMS SHOULD | | | LOSS OF POWER OCCUR. TRAFFIC CALMING | | | HUMPS ARE NOT TO INTERFERE WITH FIRE | | | RESCUE MOVEMENT INTO THE COMPLEX. | | | 7) PLEASE INDICATE PORTABLE FIRE | | | EXTINGUISHER LOCATIONS. | | | 8) PLEASE EXPLAIN RATIONALE FOR THE | | | SINGLE FIRE DEPARTMENT CONNECTION SHOWN | | | ON THE OTHER DRAWINGS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-03-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-14 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-14 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2001-03-14 00:00:00 | 1) PLEASE INDICATE FIRE RESCUE ACCESS | | | INTO THE APARTMENT COMPLEX. THE OPENING | | | THAT FIRE RESCUE IS EXPECTED TO PASS | | | THRU MUST BE AT LEAST 20 FEET IN CLEAR | | | WIDTH. HOW DOES FIRE RESCUE EQUIPMENT | | | PASS THE SECURITY FEATURES PLANNED FOR | | | THE COMPLEX DRIVE OPENINGS. | | | 2) UNDERGROUND FIRE LINES, FIRE HYDRANTS | | | AND APPURTENACES TO COMPLY WITH NFPA 24. | | | THIS EQUIPMENT TO MEET UTILITY AND FIRE | | | RESCUE STANDARDS. WET FIRE HYDRANTS ARE | | | TO BE PROVIDED PRIOR TO, DURING AND | | | AFTER CONSTRUCTION. | | | 3) PLEASE INDICATE IF GATES OR FRAME | | | ARMS WILL BE PROVIDED FOR SECURITY | | | PURPOSES. | | | 4) BUILDING ADDRESSES REQUIRED PER CITY | | | CODE REQUIREMENTS. | | | 5) CLUBHOUSE TO PROVIDE PROVISIONS FOR | | | AT LEAST TWO HANDICAPPED PERSONS. | | | 6) PLEASE INDICATE HOW THE DRYER CHASE | | | CAN BE CLEANED OF COMBUSTIBLE LINT | | | BUILD-UP. PLEASE PROVIDE UL NUMBERS FOR | | | ALL SHAFTS. | | | 7) NO HYDRAULIC CALCULATIONS PROVIDED | | | WITH FIRE SPRINKLER DRAWINGS. ALL | | | BUILDINGS ARE TO BE COMPLETELY FIRE | | | SPRINKLER PROTECTED. ALL ELECTRICAL, | | | MECHANICAL AND SERVICE ROOMS ARE TO BE | | | PROTECTED WITH FIRE SPRINKLER HEADS. | | | ALSO ALL VERTICAL SHAFTS ARE TO BE | | | FIRE SPRINKLER PROTECTED. | | | 8) EMERGENCY LIGHTING REQUIRED IN FIRE | | | PUMP ROOM. OKAY, LOCATED ON PLANS. | | | 9) ALL BUILDINGS THREE STORIES OR MORE | | | AND 50 FEET IN HEIGHT MUST HAVE | | | STANDPIPE SYSTEMS IN ACCORDANCE WITH | | | NFPA 14. | | | 10) HANDRAILS AND GUARDS TO COMPLY WITH | | | NFPA 101, THE LIFE SAFETY CODE, 1985 | | | EDITION. | | | 11) MORE DETAILS NEEDED FOR FIRE PUMP | | | EQUIPMENT AND APPURTENANCES. | | | 12) IS ACCESS PROVIDED INTO THE WOOD | | | TRUSS AREA. | | | 13) TENANT SEPARATIONS TO COMPLY WITH | | | BUILDING CODE REQUIREMENTS. | | | 14) PLEASE BE ADVISED OF THE STRETCHER | | | REQUIREMENTS OF THE STANDARD BUILDING | | | CODE, SECTION 3003.4 FOR BUILDINGS FOUR | | | OR MORE FLOORS. | | | 15) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION. | | | 16) IS BATTERY BACK-UP PLANNED FOR THE | | | SECURITY FEATURES AT THE ENTRANCE SHOULD | | | LOSS OF POWER RESULT. | | | 17) DOES THE NOTE ON PAGE E12 MEAN | | | ONLY A SINGLE FIRE ALARM PANEL FOR THE | | | COMPLEX. WHAT HAPPENS WHEN THIS PANEL | | | IS DOWN FOR REPAIRS OR REPLACEMENT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2002-04-26 |
Time |
07:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-05-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-24 |
Time |
07:45 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2001-05-24 |
Time |
07:45 |
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | NOTES ON PERMIT 01040480 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-05-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-10 |
Time |
15:22 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-05-10 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2001-05-10 00:00:00 | *******************PROVISO************** | | | | | | IF COPPER IS BEING USED FOR CHILLED WATE | | | R LINES IS SHALL BE BRAZED AS PER 1997 S | | | MC TABLE 1205. | | | | | | ADDITIONAL PERMIT REQUIRED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-03-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-26 |
Time |
14:35 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2001-03-26 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2001-03-26 00:00:00 | | | | | | | | | | PLEASE PROVIDE DETAILS FOR CONDENSER | | | STANDS ON ROOF. | | | | | | NO OUTSIDE AIR CALCULATIONS FOR CLUB | | | HOUSE AS PER ASHREA 62-89. | | | | | | NO AIR BALANCE SCHEDULE. | | | | | | INDICATE ACCESS FOR CLEANING OF DRYER | | | EXHAUST VENTS. | | | | | | ARE STAIRWELL ENCLOSURES OPEN? |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2003-01-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-22 |
Time |
08:59 |
Rev Time |
0.10 |
| Received By |
kstevens |
Date |
2003-01-22 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2003-01-22 00:00:00 | SUBMITTAL - DOMESTIC PUMP PACKAGE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2002-02-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-20 |
Time |
10:58 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-02-20 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2002-02-20 00:00:00 | REVISION FOR AIR CHAMBERS/W-HEATER KIT. | | | AREA |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2002-02-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-02-10 |
Time |
09:21 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-10 00:00:00 | DENIEDPAUL SCHMITZ | | | REVISIONS FOR SHTS P-6, A2-4,ONLY ONE | | | SHT OF EACH SUBMITTED | | | 561 659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2001-11-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-29 |
Time |
16:35 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-11-29 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2001-11-29 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) PREVIOUS COMMENTS NOT ADDRESSED. | | | 2) SHT P-6 WATER HAMMER ARRESTORS SHALL | | | BE LOCATED CLOSE TO FIXTURES IN AN | | | "EFFECTIVE RANGE" NOT AT TOP OF DROPS AS | | | SHOWN. | | | 3) SHT A2.4 WATER HEATER IN A/C CLOSET | | | BY KITCHENETTE AND WATER HEATER CH-2 UN- | | | DER COUNTER AT SINK ON WATER RISER DIA- | | | GRAM SHT P-6. PLEASE CLARIFY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2001-10-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-19 |
Time |
16:28 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-10-19 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2001-10-19 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) SHEET P-6 AIRCHAMBERS SEC 607.8.3 | | | ACCESSIBLE & RECHARGEABLE, "TEMPORARY | | | FIX". USE WATER HAMMER ARRESTORS AND | | | SIZE AND LOCATE PER MANUFACTURE INSTALL- | | | ATION INSTRUCTIONS AND WH-PDI 201. NOT | | | AT TOP OF DROP BUT NEAR SOURCE (FIXTURE) | | | | | | 2) SHEET A2.4 WATER HEATER IN A/C CLOSET | | | BY KITCHENETTE AND WATER HEATER CH-2 UN- | | | DER COUNTER AT SINK ON WATER RISER DIA- | | | GRAM SHEET P-6. PLEASE CLAIRFY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-09-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-28 |
Time |
15:41 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-09-28 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2001-09-28 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) SHEET P-6 AIR CHAMBERS SEC 607.8.3 | | | ACCESSIBLE AND RECHARGEABLE, "TEMPORARY | | | FIX". USE WATER HAMMER ARRESTORS. SIZED | | | AND LOCATED PER MANUFACTURE | | | INSTALLATION INSTRUCTIONS AND WH-PDI 201 | | | | | | 2) SHEET A2.4 WATER HEATER IN A/C CLOSET | | | BY KITCHENETTE AND WATER HEATER CH-2 UN- | | | DER COUNTER AT SINK ON WATER RISER DIA- | | | GRAM SHEET P-6. PLEASE CLARIFY. | | | | | | 3) SHEET A2.4 & A8.1 KITCHENETTE SINK TO | | | COMPLY WITH FACBC-97 SEC 4.24 | | | | | | 4) SHEET A8.1 URNAL TO COMPLY WITH FACBC | | | -97 SEC 4.18.2 & 4.22.5. 17" TO LIP AFF | | | AND SHOW CLEAR FLOOR SPACE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-05-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-05-17 |
Time |
14:52 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-05-17 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2001-05-17 00:00:00 | NOTE: | | | | | | URNAL TO COMPLY WITH FACBC-97 | | | 4.18.2 & 4.22.5 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-04-06 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-04-06 |
Time |
14:26 |
Rev Time |
8.00 |
| Received By |
jleech |
Date |
2001-04-06 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2001-04-06 00:00:00 | DENIED; | | | | | | 1.(GENERAL NOTES) #15. COPIES OF ALL | | | DOCUMENTS TO BE FILED WITH THE | | | DEPARTMENT OF CONSTRUCTION SERVICES. | | | CHANGE "A" TO CITY OF WEST PALM BEACH. | | | "L" SAME AS "A". | | | | | | 2.BACKFLOW PREVENTERS SHALL BE INSTALLED | | | AT EACH BUILDING. | | | | | | 3.(SEWAGE COLLECTION SYSTEM) NOTE 8. | | | TWO COATS SHALL BE APPLIED TO THE OUT | | | SIDE. | | | | | | 4.(WATER DISTRIBUTION SYSTEM) NOTE 3 | | | CITY OF WEST PAKM BEACH NOT SUNRISE. | | | | | | 5.WATER HAMMER ARRESTERS TO COMPLY WITH | | | 607.8.1, 607.8.2 AND 608.8.3 | | | | | | 6.PAGE P-3 WASTE RISER S3 AND S4. THREE | | | INCH. STACK MAXIMUM LENTH IS 50 FT. | | | FROM THE HOUSE DRAIN THRU THE ROOF. | | | SPC 911.4 AND TABLE 911.4. | | | | | | 7.PAGE P-6 FLOOR DRAINS IN PUBLIC REST- | | | ROOMS SHALL HAVE TRAP PRIMERS.FLOOR | | | DRAINS IN LAUNDRY ROOM SHALL BE DEEP | | | SEAL. SEC. 409.4.1.1 AND 409.4.1.4. | | | | | | 8.PAGE A8.1 SHOW MEASURMENTS FOR TOILET | | | LOCATION. SHOW THE 18"SIDE TO COMPLY | | | WITH THE FHA. | | | | | | 9.WHAT HIGHT ABOVE THE ROOF ARE THE | | | OVERFLOW DRAINS SET ABOVE THE ROOF? | | | | | | 10.SHOW NUMBER OF UNITS IN EACH BUILDING | | | THAT WILL BE FURNISHED WITH GRAB BARS | | | AND HANDICAP ACCESSORIES. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-05-22 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-05-04 |
Time |
14:02 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-22 00:00:00 | APPROVED ANGELLAVANN | | 2001-05-04 00:00:00 | NEED MINOR AMENDENTS |
|
|