Plan Review Details - Permit 01030464
Plan Review Stops For Permit 01030464
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-28 Cont ID  
Sent By jwitmer Date 2001-04-28 Time 08:33 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-28 Cont ID  
Sent By jwitmer Date 2001-03-28 Time 17:41 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-28 00:00:005 MANGONIA CIRCLE
 O/B: RUSSEL, PERCIVAL/
 BONNICK, CURTIS
 PERMIT # 01030464
  
 1)- SBC 1804.2 SOIL TEST REPORT,
 BEARING VALUE
  
 2)- SBC 1707.4.1 STORM SHUTTERS:
 WEST PALM POLICY SEE ATTACHMENT KEY AND
 SAMPLE INSTALLATION SCHEDULE.
  
 3)- SBC 1606.2..6.2.: COMPONENTS &
 CLADDING. MISSING PRODUCT APPROVAL
 REPORTS FOR:
 A): SLIDING GLASS DOORS
 B): FRONT DOOR & SIDE LITE
  
 4)- SBC 102.2.2: ADDITIONAL INFORMATION:
 THERE IS NO ATTACHMENT DETAIL FOR THE
 (2) 2X12 WOOD BEAMS LOCATED OVER THE
 FRONT ENTRY, THE DETAIL DOESN'T CLARIFY
 HOW TO TIE BACK INTO THE ROOF TRUSSES.
  
 5)- TRUSS DRAWING; CAN'T LOCATE THE
 TTRUSSES 15,16 & 17.
  
 6)- PLANS ARE TO BE STAMPED BY THE
 COUNTY FOR IMPACT FEES.
  
 7)- ADDITIONAL FEES DUE TO CITY:
 1000:$418.94
 123016.81
 121011.37
 122011.37
 _______
  
 TOTAL $458.49
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-05-17 Cont ID  
Sent By dpalmer Date 2001-05-17 Time 10:49 Rev Time 0.00
Received By dpalmer Date 2001-05-17 Time 10:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-04-25 Cont ID  
Sent By dpalmer Date 2001-04-25 Time 18:27 Rev Time 0.00
Received By dpalmer Date 2001-04-25 Time 18:27 Sent To  
Notes
2001-04-25 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 WERE ADDRESSED.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 THE CODE ARTYS: WERE WRITTEN ON PLANS??
 THIS DOES NOT GIVE US THE AIC RATING
 FORNEW EQUIPMENT.
  
 3)NOTE: PLEASE NOTE THAT ALL THE OTHER
 CHANGES THAT WERE MADE, WERE DONE IN
 PENCIL? THIS IS NOT PERMITTED UNDER
 104.2 AND 104.2.7. ALSO ALL PLANS THAT
 ARE SIGNED AND SEALED BY AN
 ARCH/ENGINEER ARE TO BE DONE BY THAT
 PERSON PER F.S. AND F.A.C 471.025 AND
 481.221.
  
 PLEASE HAVE PLANS RE-DONE UNDER COUNTY
 AND CITYWIDE ADMINISTRATIVE CODE.
 104.2& .7.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-26 Cont ID  
Sent By dpalmer Date 2001-03-26 Time 18:51 Rev Time 0.00
Received By dpalmer Date 2001-03-26 Time 18:51 Sent To  
Notes
2001-03-26 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT LOAD
 CALCULATIONS AND LOADS ON PANEL
 SCHEDULE ARE NOT COMPLETE. PLEASE DO
 SO. 215-5.
  
 2)NOTE: PLEASE NOTE LOADS FOR LIGHTING,
 WELL PUMP, SPRINKLER PUMP??
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) NOTE: PLEASE SHOW GROUNDING
 ELECTRODE GOING TO BUILDING STEEL AND
 COLD WATER. PER 250-50
 PLEASE NOTE THAT WE ARE
 UNDER THE "99" NEC. THERE IS A NOTE REF
 TO
 ART 250-83C? THIS IS NOT IN THE "99"NEC.
  
 5) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 PLEASE NOTE THAT IF THERE IS GOING TO BE
 CATV AND OR TELEPHONE IN THE HOUSE THEN
 LOCATIONS NEED TO BE SHOWN ON PLANS.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-03-24 Cont ID  
Sent By jleech Date 2001-03-24 Time 06:53 Rev Time 0.33
Received By jleech Date 2001-03-24 Time 06:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-03-20 Cont ID  
Sent By jleech Date 2001-03-20 Time 18:13 Rev Time 0.33
Received By jleech Date 2001-03-20 Time 18:12 Sent To  
Notes
2001-03-20 00:00:00PROVISO:
 SANITARY RISER DIAGRAM DOES NOT
 MEET CODE. SUBMIT SANITARY RISER
 DIAGRAM FOR INSPECTION. MUST REFLECT
 FLOOR PLAN

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-17 Cont ID  
Sent By sgraham Date 2001-05-17 Time 14:52 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***