| Plan Review Stops For Permit 01030451 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-03-13 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-13 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-13 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2001-03-13 00:00:00 | 1) DUCT SMOKE DETECTORS ARE REQUIRED IN | | | AIR HANDLING SYSTEMS OVER 2000 CFM. WHEN | | | ACTIVATED, THESE DEVICES ARE TO SHUT | | | DOWN AIR HANDLING SYSTEMS AND ACTIVATE | | | THE FIRE ALARM SYSTEM. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|