| 2001-03-21 00:00:00 | ************DENIED********************** |
| | 1. ALL MED GASSHALL COMPLY WITH 1999 |
| | NFPA 99C |
| | 2. SPECIFY PIPE MATERIALS ON PLAN. |
| | VACUUM PIPING TO COMPLY WITH 4-3.2.2.2 |
| | OXYGEN PIPING BE PER 4-3.1.2.7 |
| | 3. SPECIFY PIPE SIZES ON PLAN FOR O2 AND |
| | VACUUM SYSTEMS FOR REVIEW. |
| | 4. NOTE ON P-4 REFERS TO P-1 FOR VACUUM |
| | PUMP PIPING AND VALVE CONFIGURATION. |
| | P-1IS NOT INCLUDED FOR REVIEW. |
| | 5. THE MAIN VALVE (O2) IS SHOWN LOCATED |
| | AFTER THE FIRST BRANCH WHICH IS SHOWN |
| | CONNECTED BACK TO THE REST OF THE |
| | SYSTEM IN THE CORRIDOR. MAIN VALVE |
| | NEEDS TO BE PRIOR TO ANY BRANCH. |
| | 6. PIPING IS TO BE PROMINENTLY LABELED |
| | AS TO USE PRIOR TO INSTALLATION PER |
| | 4-3.2.2.2 |
| | 7. PRESSURE TEST PER 4-3.4.1.1 SHALL BE |
| | BEFORE WALLS ARE CLOSED. |
| | 8. THE EMERGENCY OXYGEN SUPPLY |
| | CONNECTION SHALL BE LOCATED ON THE |
| | EXTERIOR OF THE BUILDING WHERE IT IS |
| | ACCESSIBLE BY EMERGENCY SUPPLY VEHICHLE |
| | AT ALL TIMES. |
| | 9. NO AREA ALARMS ARE SHOWN FOR THE |
| | PROCEDURE ROOMS. PROVIDE INFORMATION ON |
| | AREA ALARMS PER 4-3.1.2.2 (C) |
| | 10. ALARM PANELS SHALL BE POWERED BY THE |
| | LIFE SAFETY BRANCH OF THE EMERGENCY |
| | SYSTEM PER 4-3.1.2.2 |
| | |
| | PROVIDE PLANS INCLUDING INFORMATION |
| | ABOVE FOR REVIEW. |
| | CONTACT PAUL SCHMITZ CHIEF PLUMBING |
| | INSPECTOR @ (561) 659-8096 EXT. 8233 |
| | FOR REQUIRED INSPECTIONS AND TESTS |
| | REQUIRED BY |
| | THIS OFFICE FOR THIS PERMIT TYPE. |