| Plan Review Stops For Permit 01030444 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-03-13 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-13 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-13 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2001-03-13 00:00:00 | 1) SMOKE DETECTORS WHEN INSTALLED ARE | | | TO BE A MINIMUM OF THREE FEET FROM | | | AIR CONDITONER DIFFUSERS. | | | 2) DUCT SMOKE DETECTORS WHEN ACTIVATED | | | ARE TO SHUT DOWN AIR HANDLING DEVICES | | | AND ACTIVATE THE FIRE ALARM SYSTEM. | | | 3) WHEN ACTIVATED, THE FIRE ALARM SYSTEM | | | IS TO BE AUDIBLE THROUGHOUT THE | | | BUILDING. | | | 4) FIRE ALARM SYSTEM TO BE CLASS A OR | | | FULLY ADDRESSABLE. | | | 5) FIRE ALARM SYSTEM IS TO BE MONITORED | | | BY A LICENSED UL LISTED CENTRAL STATION | | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | | 6) HEAT DETECTORS ASSOCIATED WITH THE | | | ELEVATOR(S) ARE TO SHUNT TRIP AND NOT | | | BE CONNECTED TO THE FIRE ALARM SYSTEM. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|