Plan Review Details - Permit 01030426
Plan Review Stops For Permit 01030426
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-04-04 Cont ID  
Sent By jwitmer Date 2001-04-04 Time 07:47 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-04 00:00:00PROVISO: STORM SHUTTERS REQUIRED UNDER
 SEPERAE PERMIT. JW

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-05-04 Cont ID  
Sent By dpalmer Date 2001-05-04 Time 08:36 Rev Time 0.00
Received By dpalmer Date 2001-05-04 Time 08:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-04-17 Cont ID  
Sent By dpalmer Date 2001-04-17 Time 17:56 Rev Time 0.00
Received By dpalmer Date 2001-04-17 Time 17:56 Sent To  
Notes
2001-04-17 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS THAT WERE SUBMITTED SHOW
 LOAD FOR NEW GARAGE ONLY? WHAT ABOUT
 LOAD IN EXSITING HOUSE? WHAT SIZE IS
 EXISTING SERVICE THAT FEEDS NEW
 EQUIPMENT?
  
 2)NOTE: PLEASE NOTE STILL NOTHING
 SUBMITTED SHOWING CONDUIT SIZES ON
 RISER OR
 WIRE SIZES ON RISER OR WIRE SIZES GOING
 TO MAIN HOUSE? PLEASE SHOW.
  
 3)NOTE: PLEASE NOTE PLANS SHOW OPTIONAL
 FEED TO HOUSE BEING OVERHEAD? AT 10`FT.
 PLEASE SEE 230-24 FOR CLEARENCES.
  
  
 4)NOTE: PLEASE NOTE THAT NOW PLANS SHOW
 NEW EQUIPMENT BEING INSTALLED.
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 5)NOTE: PLEASE CLARIFY SMALL APPLIANCE
 CIRCUITS SHOWN FOR GARAGE?
  
 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. GROUNDING FOR DETACHED BLDG.
  
 7)NOTE PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-29 Cont ID  
Sent By dpalmer Date 2001-03-29 Time 17:43 Rev Time 0.00
Received By dpalmer Date 2001-03-29 Time 17:43 Sent To  
Notes
2001-03-29 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT THERE IS NOT
 ENOUGH ELECTRICAL DETAIL FOR REVIEW OF
 FEED/OR SERVICE TO GARAGE. WIRE SIZES,
 CONDUITS, ETC. WHERE IS POWER COMING
 FROM.?
 2)NOTE: PLEASE SEE 210-8 FOR ALL
 OUTLETSIN GARAGE TO BE GFI /GFI
 PROTECTED.
  
 PLEASE SUBMIT MORE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-04-04 Cont ID  
Sent By jleech Date 2001-04-04 Time 08:17 Rev Time 0.00
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-28 Cont ID  
Sent By jleech Date 2001-03-28 Time 19:16 Rev Time 0.25
Received By jleech Date 2001-03-28 Time 19:16 Sent To  
Notes
2001-03-28 00:00:00NO A/C PLANS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-03-28 Cont ID  
Sent By jleech Date 2001-03-28 Time 19:16 Rev Time 0.33
Received By jleech Date 2001-03-28 Time 19:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-03-15 Cont ID  
Sent By sgraham Date 2001-03-15 Time 12:24 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved