| 2001-04-17 00:00:00 | ****************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT THE LOAD |
| | CALCULATIONS THAT WERE SUBMITTED SHOW |
| | LOAD FOR NEW GARAGE ONLY? WHAT ABOUT |
| | LOAD IN EXSITING HOUSE? WHAT SIZE IS |
| | EXISTING SERVICE THAT FEEDS NEW |
| | EQUIPMENT? |
| | |
| | 2)NOTE: PLEASE NOTE STILL NOTHING |
| | SUBMITTED SHOWING CONDUIT SIZES ON |
| | RISER OR |
| | WIRE SIZES ON RISER OR WIRE SIZES GOING |
| | TO MAIN HOUSE? PLEASE SHOW. |
| | |
| | 3)NOTE: PLEASE NOTE PLANS SHOW OPTIONAL |
| | FEED TO HOUSE BEING OVERHEAD? AT 10`FT. |
| | PLEASE SEE 230-24 FOR CLEARENCES. |
| | |
| | |
| | 4)NOTE: PLEASE NOTE THAT NOW PLANS SHOW |
| | NEW EQUIPMENT BEING INSTALLED. |
| | PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 5)NOTE: PLEASE CLARIFY SMALL APPLIANCE |
| | CIRCUITS SHOWN FOR GARAGE? |
| | |
| | 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. GROUNDING FOR DETACHED BLDG. |
| | |
| | 7)NOTE PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |