Plan Review Details - Permit 01030376
Plan Review Stops For Permit 01030376
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-12 Cont ID  
Sent By dpalmer Date 2001-03-12 Time 10:36 Rev Time 0.00
Received By dpalmer Date 2001-03-12 Time 10:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-11 Cont ID  
Sent By dpalmer Date 2001-03-11 Time 10:57 Rev Time 0.00
Received By dpalmer Date 2001-03-11 Time 10:57 Sent To  
Notes
2001-03-11 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 THIS IS INFORMATION NEEDED FOR ALL PLANS
 WHEN CHANGING/ INSTALLING NEW EQUIPMENT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  