| Plan Review Stops For Permit 01030349 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-04-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-11 |
Time |
10:19 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-04-11 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2001-04-11 00:00:00 | ******************PROVISO*************** | | | | | | PLAN M0.1 NOTE #14, SHOULD NOT HAVE BEEN | | | REMOVED, FAN SHUTDOWN BY DUCT SMOKE DETE | | | CTOR FOR UNITS SERVING A COMMON PLENUM I | | | S REQUIRED WITH NOTIFICATION TO ALARM/ST | | | ROBE IN NORMALLY OCCUPIED AREAS. | | | | | | M2.1 FIRE DAMPER IS NOW GOING TO BE | | | UNDER THE SCOPE OF THE ADJACENT TENENT | | | BUILD OUT, PLANS APPROVED 1/16/01 | | | INDICATE THE FIRE DAMPER WAS EXISTING. | | | THIS FIRE DAMPER MUST REMAIN OR BE REPLA | | | CED WITH THIS BUILD OUT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-03-08 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2001-03-08 |
Time |
14:46 |
Rev Time |
0.25 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-08 00:00:00 | OK PER NDENMARK SEE MASTER 00120683 |
|
|
|