Plan Review Details - Permit 01030153
Plan Review Stops For Permit 01030153
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-06-06 Cont ID  
Sent By jwitmer Date 2001-06-06 Time 15:48 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-06 00:00:00TRUSS REVIEW: OK 6/6/01 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-06-04 Cont ID  
Sent By jwitmer Date 2001-06-04 Time 15:59 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-04 00:00:00NO TRUSS PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-28 Cont ID  
Sent By jwitmer Date 2001-04-28 Time 09:32 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-03-28 Cont ID  
Sent By jwitmer Date 2001-03-28 Time 13:23 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-28 00:00:00BUILDING PLAN REVIEW
  
 1)- NOTICE OF COMMENCEMENT TO BE FILED
 WITH THE COUNTY COURTHOUSE BEFORE ISSU-
 ANCE OF THE PERMIT.
  
 2)- SBC 1804.2.2 COUNTY AMENDMENTS:
 SOILS BEARING REPORT WITH MINIMUM SAFE
 BEARING VALUES.
  
 3)- SBC 1804.1.3: MINIMUM FOUNDATION
 DEPTH, THE BOTTOM OF THE FOUNDATION MUST
 BE A MINIMUM OF 12" BELOW GRADE.SEE
 SH.A-4 DETAIL 7.
  
 4)- SBC 2306.1 TABLEFASTENING SCHEDULE
 SHEETA-3 NOTE 11 NAILING PATTERN BACK-
 WARDS 6" O.C. AT EDGES/ 4" O.C. IN FIELD
 TABLE 2306.1. NAILING AT EDGES 4"O.C. &
 6" O.C. AT INTERMEDIATES AND FIELD.
  
 5)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 THE CODE REQUIRES TESTING REPORTS INDI-
 CATING THAT MATERIALS THAT MAKE UP THE
 ENVELOP OF THE BUILDING COMPLY WITH THE
 HIGH WIND ZONES;
 A) GLAZED OPENINGS: SBC 1707.4 TO BE
 TESTED 10 SEC. AT 1 1/2 THE
 DESIGN PRESSURE.
 B) WINDOWS, DOORS & SLIDING GLASS
 DOORS ARE TO BE TESTED FOR
 IMPACT FROM WIND BORN DEBRIS, THE
 GLAZED OPENINGS REQUIRE LARGE
 MISSLE RESISTANT TESTING OR STORM
 SHUTTERS HAVING PASSED THIS TEST.
 SBCCI OR DADE COUNTY PRODUCT
 APPROVAL REPORTS ARE ACCEPTED.
 SBC 1606.4.1/ 1707.4.1.
 C) ROOFING MATERIALS TO COMPLY WITH
 SBC 1707.5 SHOW PRODUCT TESTING
 FOR CEMENT & CLAY TILE ROOFING
 MATERIALS. DADE COUNTY OR SBCCI.
 D) STORM SHUTTERS: SHEET A-4 INDI-
 CATES THAT STORM SHUTTERS WILL BE
 INSTALLED, IF INFORMATION ISN'T
 PROVIDED AT TIME OF ISSUANCE A
 SEPERATE PERMIT/ FEES WILL BE
 REQUIRED BEFORE THE ISSUANCE OF
 A CERTIFICATE OF OCCUPANCY.
  
 6)- SBC 2405.2.2(5) GLASS BLOCK ARE
 EXEMPT FROM HAZARDOUS LOCATIONS IF THE
 UNIFORM FACE THICKNESS OF THE BLOCK IS
 0.25".
  
 7)- A SEPERATE PERMIT WILL BE REQUIRED
 FOR THE POOL/ SPA, SCREEN ENCLOSURE,
 DECK MAY BE INCLUDED AT THIS TIME BUT
 NEEDS TO BE SPECIFIED & GENERATED.
  
 8)- ENEREGY CALC: FL. ENERGY CODE 600.1
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-23 Cont ID  
Sent By dpalmer Date 2001-04-23 Time 19:13 Rev Time 0.00
Received By dpalmer Date 2001-04-23 Time 19:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-12 Cont ID  
Sent By dpalmer Date 2001-03-12 Time 16:19 Rev Time 0.00
Received By dpalmer Date 2001-03-12 Time 16:19 Sent To  
Notes
2001-03-12 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
  
 3)NOTE:PLEASE NOTE, THAT PER 220-3-C1,
 NEED TO SUBMIT LOAD CALCULATIONS FOR
 EXISTING SERVICE WITH NEW SERVICE LOAD
 ADDED.
  
 4)NOTE: PLEASE NOTE NO GROUNDING SYSTEM
 IS HOWN FOR DETACHED HOUSE.
 NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50.
  
 5)NOTE: PLEASE CLARIFY LOAD SHOWN FOR
 PANEL IN GUEST HOUSE. LOAD SHOWN
 EXCEEDSSUB FEED OF 60AMPS. SHEET A-2
 SHOWS 60A SUBFEED AND A-4 SHOWS 80A ??
 PLEASE
 CALRIFY.
  
  
 PLEASE PUT ELECTRICAL DETAILS ON SAME
 SHEET. PLEASE SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-17 Cont ID  
Sent By pkrauss Date 2001-04-17 Time 15:08 Rev Time 0.40
Received By pkrauss Date 2001-04-17 Time 14:45 Sent To  
Notes
2001-04-17 00:00:00*******************PROVISO**************
  
 WHERE REFRIGERANT LINES PASS THROUGH
 CONCRETE FLOOR,LINES SHALL BE SLEEVED.
  
 PLEASE PROVIDE EQUIPMENT INFORMATION
 FORAIR HANDLER AND CONDENSER UNIT PRIOR
 TO INSPECTION.THIS INFORMATION SHALL
 ACCOMPANY THE PLANS AND PERMIT ON THE
 JOBSITE AT THE TIME OF INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-03-10 Cont ID  
Sent By jleech Date 2001-03-10 Time 09:06 Rev Time 0.25
Received By jleech Date 2001-03-10 Time 09:06 Sent To  
Notes
2001-03-10 00:00:00A/C DRAWINGS AND ENERGY CAULKS TO BE
 SUBMITED WITH A/C APPLICATION.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-10-25 Cont ID  
Sent By jleech Date 2001-10-25 Time 18:55 Rev Time 0.33
Received By jleech Date 2001-10-25 Time 18:55 Sent To  
Notes
2001-10-25 00:00:00REVISION; RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-04-19 Cont ID  
Sent By jleech Date 2001-04-19 Time 07:31 Rev Time 0.33
Received By jleech Date 2001-04-19 Time 07:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-03-10 Cont ID  
Sent By jleech Date 2001-03-10 Time 09:09 Rev Time 0.33
Received By jleech Date 2001-03-10 Time 09:09 Sent To  
Notes
2001-03-10 00:00:00DENIED;
  
 1.VENT THRU ROOF SHALL BE 3" SPN 904.3.
  
 2.HORIZONTALDRY VENTS ARE NOT PERMITED
  
 3.TUB AND BAR SINK ARE NOT VENTED.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-03-08 Cont ID  
Sent By sgraham Date 2001-03-08 Time 07:25 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***