Plan Review Details - Permit 01030147
Plan Review Stops For Permit 01030147
Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status F Date 2003-04-14 Cont ID  
Sent By shernand Date 2003-05-05 Time 11:26 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-04-14 00:00:00REVISIONS DATED 1/14/03 SHEETS A.4.16.1
 AND A 5.1.24. GUARDHOUSE DOORS.
  
 SBC 1012.1.2-97 REQUIRES EXIT DOORS TO
 BE SIDE SWINGING.PLEASE REVISE AS
 NECESSARY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status F Date 2003-04-14 Cont ID  
Sent By hpiskura Date 2003-04-14 Time 10:08 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-04-14 00:00:00ENTRANCE DOOR COMPARATIVE ANALYSIS
 LOCATION L 055.
  
 FBC 1707.4.2 REQUIRES TESTING AND
 LABELING OF WINDOWS AND DOORS.
  
 A SEPARATE PERMIT IS REQUIRED FOR
 WINDOWS AND DOORS NOT INCLUDED WITH THE
 ORIGINAL PERMIT APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status F Date 2003-04-14 Cont ID  
Sent By hpiskura Date 2003-04-14 Time 10:05 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-04-14 00:00:00RE: FIFTEENTH FLOOR FRENCH DOOR PRODUCT
 APPROVALS.
  
 A SEPARATE PERMIT AND FEES ARE REQUIRED
 FOR WINDOWS, DOORS, ETC. SUBMITTED
 SUBSEQUENT TO THE PRIME PERMIT BEING
 ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status F Date 2003-03-19 Cont ID  
Sent By shernand Date 2003-04-11 Time 13:38 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-03-19 00:00:00SHEET S5, REVISIONS 2 THROUGH 6,
 ENGINEER'S SIGNATURE DATE 3/14/03.
  
 SHEET S5 OF THE CITY PERMIT SET SHOWS
 REVISON #1 DATED 5/2/01.THIS SHEET
 SHOWS REVISIONS NUMBERED UP TO #6 DATED
 5/2/02.WHAT ARE THE OTHER REVISIONS
 AND WHY ARE THEY BEING PROVIDED NEARLY
 A YEAR LATER AND SUBSEQUENT TO THE WORK
 BEING ACCOMPLISHED?
  
 WHAT IS THE DIMENSION OF THE NEW AREA
 SHOWN AS #6?WHAT WILL THE FUNCTION
 AND USE BE?WHERE ARE THE SUPPORTING
 ARCHITECTURAL PLANS?CHANGES TO THE
 EXTERIOR ARE SUBJECT TO PRIOR REVIEW BY
 THE PLANNING DEPARTMENT.
  
 IT APPEARS THIS WORK PROVIDES ADDED
 VALUE TO THE BUILDING AND IS SUBJECT TO
 ADDITIONAL PERMIT FEES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2003-03-07 Cont ID  
Sent By sthyng Date 2003-03-17 Time 08:53 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-03-07 00:00:00ROOFING SUBMITTALS DATED 2/8/02 WEST
 COAST ROOFING. PERMIT #01050621
  
 THE SITE SPECIFIC ENGINEERING DATED
 8/13/01 IS NOT SIGNED AND SEALED, DOES
 NOT CONTAIN AN INVESTIGATION OF THE
 "DENS DECK," AND HAS NOT BEEN REVIEWED
 BY THE ENGINEER OF RECORD.
  
 THE SBCCI REPORT 9822A IS NOT CURRENT.
  
 THE SITE SPECIFIC ENGINEERING REFERENCES
 THE CURRENT FBC.SEE FBC 1609.4.3 RE:
 LOAD REDUCTION AND ALLOWABEL STRESS
 INCREASES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2003-02-27 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 14:33 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-02-27 00:00:00REVISION 8 DATED 11/11/02 FOR PH UNIT G,
 ARCHITECTURAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2003-01-16 Cont ID  
Sent By hpiskura Date 2003-01-16 Time 16:57 Rev Time 0.00
Received By hpiskura Date 2003-01-16 Time 16:57 Sent To  
Notes
2003-01-16 00:00:00REVISIONS DATED 12/13/02 MARKED SK1 AND
 RE: A.4.3.1.
  
 PROVIDE A FIRE DESIGN NUMBER FOR THE
 TWO HR RATED CEILING ON THE STAIR
 CONNECTOR TO DEMONSTRATE COMPLIANCE
 WITH FBC 704.2.1.2.
  
 SK3 DATED 11/26/2000 "NEW DETAIL"
 EMERGENCY OVERFLOW SCUPPER.WHAT
 VOLUME OF WATER IS ANTICIPATED TO FLOW
 THROUGH THE UNDEFINED FIBERGLASS SCREEN
 AREA?
  
 SK4 DATED 11/26/2000 AND NOTED A.4.12.1
 AND SK5 DATED 11/26/2000 AND NOTED
 A.4.15.1.THE CHANGE FROM ROOF AREA TO
 BALCONY REQUIRES ADDITIONAL DETAILS FOR
 THE ALUM GUARD RAIL, FLOOR SURFACE TO BE
 USED, AND COMPLIANCE WITH THE FAIR
 HOUSING ACT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2002-12-18 Cont ID  
Sent By hpiskura Date 2002-12-18 Time 10:43 Rev Time 0.00
Received By hpiskura Date 2002-12-18 Time 09:32 Sent To  
Notes
2002-12-18 00:00:00REVISIONS 604, 804, 1003, 1004, 603

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2002-12-10 Cont ID  
Sent By btrobaug Date 2002-12-16 Time 17:00 Rev Time 0.00
Received By hpiskura Date 2002-12-10 Time 10:48 Sent To  
Notes
2002-12-10 00:00:00REVISION #7 DATED 9/2/02 SHEETS 4.7.1, 4
 .7.2, & 4.7.3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2002-11-19 Cont ID  
Sent By btrobaug Date 2002-11-25 Time 17:58 Rev Time 0.00
Received By hpiskura Date 2002-11-19 Time 11:10 Sent To  
Notes
2002-11-19 00:00:00UNIT 803 CITY DATE 11/19/02 4.9.1,2,3

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2002-10-30 Cont ID  
Sent By hpiskura Date 2002-10-30 Time 10:03 Rev Time 0.00
Received By hpiskura Date 2002-10-30 Time 08:32 Sent To  
Notes
2002-10-30 00:00:00REVISIONS DATED 10/11/02 FOR UNITS 704,
 703, 702 AND 904.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2002-03-21 Cont ID  
Sent By pkrauss Date 2002-03-21 Time 12:49 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-03-21 00:00:00 
 WINDOW AND DOOR SUBMITTAL
  
 1]
 SUBMIT TEST REPORT AND SPECS FOR THE
 2400ST SLIDING GLASS DOORS.
 ALSO FOR 345PO OPERABLE WINDOW.
  
 2]
 SHEET 28 AND 29 CALLS FOR DOOR WITH
 GLAZING, REPORT SUBMITTED HAS SOLID
 STEEL.
  
 3]
 ONLY SUBMITTED 2SETS, ALL SUBMITTALS
 SHALL BE IN THREES.
  
 4]
 ALL SHOP DRAWINGS SHALL BE REVIEWED AND
 SIGNED BY DESIGNER OF RECORD.
  
 5]
 PROVIDE - AND + PRESSURES FOR ALL
 OPENINGS ON ELEVATIONS, SIGNED AND
 SEALED BY DESIGNER OF RECORD.
  
  
 L. MARTINEZ
 659-8096
 #8456
 WINDOW AND DOOR SUBMITTAL APPROVED
 L. MARTINEZ
 659 8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2001-09-21 Cont ID  
Sent By hpiskura Date 2001-09-21 Time 08:45 Rev Time 0.00
Received By hpiskura Date 2001-09-20 Time 16:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2001-08-29 Cont ID  
Sent By hpiskura Date 2001-08-29 Time 09:48 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-08-29 00:00:00RE: INFORMATION INCLUDED WITH
 TRANSMITTAL LETTER DATED 8/28/01 BCBE
 CONSTRUCTION FROM STUART FALKNOR AND
 THESTH LETTER DATED 8/13/01 TITLED
 "THIRD
 PLAN REVIEW" COMMENTS.
  
 TILE ROOF ASSEMBLY NOA 99-1102.04 IS FOR
 A WOOD DECK ASSEMBLY. TESTING IS
 REQUIRED FOR THE "DENS DECK"
 APPLICATION IF THAT IS THE INTENDED
 PURPOSE OF THE CATALOG SHEET COPIES
 PROVIDED.
  
 THE GAF NOA 00-0331.10 IS MISSING THE
 PAGES CONTAINING THE DESIGN WIND
 PRESSURE AND THE LIMITATIONS.
  
 THE ABOVE ITEMS CAN BE PROVISIONALLY
 ACCEPTED.
  
 NEW SHEET A.2.2.1 CITES 1999 STANDARD
 BUILDING CODE.AS STATED IN THE
 EARLIER REVIEW COMMENTS, THE CITY
 CURRENTLY INVOKES THE 1997 EDITION.
  
 THE STH RESPONSE TO ITEM #6 "THE
 CALCULATED GARAGE AREA FOR EXHAUSTING
 DOES NOT INCLUDED THE PRIVATE GARAGES,
 AS THEY ARE CONDITIONED SPACES." IS OK
 AS LONG IT IS DEMONSTRATED THAT THE
 "CONDITIONED AIR" IS EXCHANGED AT THE
 RATE OF AT LEAST SIX TIMES PER HOUR IN
 ACCORDANCE WITH SBC 411.4.2,1997.
  
 THE SPECIFICATION SHEETS PROVIDED HAVE
 CONFUSING WIND DESIGN INFORMATION AND
 SPECIFICATION 08520 FIXED ALUMINUM
 WINDOWS, DOES NOT ADDRESS HURRICANE
 MISSILE IMPACT RESISTANCE.THE WIND
 PRESSURES ARE THOSE SET OUT IN THE WIND
 TUNNEL TESTING THAT THE BUILDING WAS
 DESIGNED TO.THE MISSILE IMPACT
 TESTING MUST MEET SSTD 12-97 OR HAVE A
 CURRENT DADE COUNTY ACCEPTANCE REPORT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-08-15 Cont ID  
Sent By hpiskura Date 2001-08-15 Time 09:43 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-08-15 00:00:00SEE PREVIOUS CHECKLIST DATED 7/17/01.
  
 THE NOTICE OF ACCEPTANCE REPORT
 #99-0204.07 FOR THE WINDOW WALL SYSTEM
 DOES NOT HAVE THE COMPONENTS MARKED OR
 THEIR LOCATIONS TO BE INSTALLED IN THE
 BUILDING.
  
 NOA 99-0505.08 DOORS IS NOT MARKED.
  
 NOA 01-0129.09 STEEL DOOR.SAME.
  
 NO CHANGE TO SPECIFICATION RE: WIND
 DESIGN REQUIREMENTS.
  
 PRESSURIZED STAIR CALCULATIONS UNCHANGED
 GARAGE SMOKE REMOVAL RE: VOLUME AND
 PRIVATE GARAGES NOT ADDRESSED FROM
 PREVIOUS CHECKIST.
  
 IN SUMMARY.DEMONSTRATE COMPLIANCE WITH
 SBC 412.6 #5 FOR THE STAIRS.SBC
 412.5#3 FOR THE ELEVATOR LOBBY AREA.
 PROVIDE CURRENT TEST REPORTS FOR THE
 DOORS, WINDOWS, AND ROOF COVERINGS
 TOGETHER WITH THE INFORMATION REQUIRED
 THAT IS CONTAINED WITHIN THOSE REPORTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-07-17 Cont ID  
Sent By hpiskura Date 2001-07-17 Time 14:57 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-07-17 00:00:00THE PRODUCT TEST REPORTS FOR THE ROOF
 COVERING, WINDOWS AND DOORS HAVE NOT
 BEEN PROVIDED.THE SPECIFICATIONS FOR
 THE WINDOWS AND STOREFRONT SYSTEM CALL
 A 110
 MPH WINDLOAD DESIGN.THIS MUST BE
 CORRECTED TO REFLECT THE RESULTS OF
 THE WIND TUNNEL TESTING.AT NO TIME WAS
 THIS BUILDING CONSIDERED IN A 110 MPH
 WIND ZONE FOR DESIGN PURPOSES.
 NOTE 4 UNDER CODES AND STANDARDS
 CALLS FOR HAND AND GUARD
 RAILS TO BE DESIGNED TO 1608.2.THE
 CODE SECTIONS ARE NOT A SUBSTITUTE FOR
 SPECIFIC INFORMATION.SEE SBC 104.2.
  
 THE STAIR PRESSURE CALCULATIONS ARE NOT
 SIGNED AND SEALED.FURTHER THE
 CALCULATIONS DO NOT CLEARLY INDICATE
 HOW THE BAROMETRIC RELIEF VENTS WILL
 PROVIDE THE 2500 CFM FLOW AS REQUIRED
 BY SBC 412.11 #5 PLEASE CLARIFY AND
 REVISE AS NECESSARY.
  
 SHEET M.5.0.1 SHOWS THE STAIR
 PRESSURIZATION FANS IN CLOSE PROXIMITY
 TO THE LOBBY AND OTHER EXHAUST FANS.
  
 HOW WILL THE CALCULATED GARAGE EXHAUST
 ACCOMMODATE THE "PRIVATE AIR
 CONDITIONED GARAGES WITH THEIR DOORS
 CLOSED?
  
 THE ARCHITECT PLANS SHEET A.1.1.1 CALL
 OUT A 14' CEILING HEIGHT AND 698080 SF
 IN AREA.THE WADSWORTH CALCULATIONS
 NOTE AN 11' CEILING HEIGHT AND 53017 SF
 FLOOR AREA.PLEASE JUSTIFY THE
 DIFFERENCES.NOTE TOO, ALL INFORMATION
 PREPARED BY AN ARCHITECT OR AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD, ARE
 REQUIRED TO HAVE THE EMBOSSED SEAL,
 SIGNATURE AND DATE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-05-29 Cont ID  
Sent By hpiskura Date 2001-05-29 Time 16:40 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-05-29 00:00:00PLEASE PROVIDE A RECENT PROPERTY SURVEY
  
 SHOW HOW HURRICANE MISSILE IMPACT
 RESISTANCE FOR THE GLAZED EXTERIOR
 PORTIONS WILL BE ACCOMPLISHED.
  
 THE PLANS MUST HAVE THE IMPACT FEE STAMP
 ON THEM.
  
 PROVIDE TEST DATA FOR THE WINDOWS, DOORS
 AND ROOF COVERING.
  
 UNIT TYPES E AND G DO NOT COMPLY WITH
 SBC 1004.1.4
  
 ENTRY VESTIBULES E32 AND G40 DO NOT
 COMPLY WITH THE ELEVATOR LOBBY
 SEPARATION REQUIERMENTS OF SBC 412.6.
  
 THE USE OF WOOD WITHIN THE CONSTRUCTION
 OF TYPE I & II BUILDINGS IS REQUIED TO
 BE FIRE RETARDANT TREATED.
  
 CITING A CODE SECTION IS NOT ACCEPTABLE
 IN LIEU OF SPECIFIC DESIGN INFORMATION
 WITH REGARDS TO THE HAND AND GUARD
 RAILS.
  
 SHOW HOW DAMP PROOFING WILL BE
 ACCOMPLISHED ON THE WEST SIDE OF THE
 GARAGE.SEESBC 1814.3.
  
 THE DESIGNERS RESPONSES TO THE FIRST
 CHECKLIST WERE REVIEWED AND THESE ARE
 THE SUBSEQUENT FINDINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-05 Cont ID  
Sent By hpiskura Date 2001-04-05 Time 09:26 Rev Time 0.00
Received By hpiskura Date 2001-03-30 Time 15:53 Sent To  
Notes
2001-04-05 00:00:001 THIS BUILDING WILL BE IN AN FLOOD
 ZONE A5 WITH A 7.0' BFE
 2THIS WILL BE A THRESHOLD BUILDING AND
 REQUIRES AN THRESHOLD INSPECTION PLAN
 AND INSPECTOR.CONTACT DON NEELY FOR
 ADDITIONAL INFORMATION659-8096 X 8333.
 3PLEASE PROVIDE A RECNT PROPERTY
 SURVEY WITH THE PERMIT APPLICATION.
 4SHOW HOW THE GLAZED PORTIONS OF THE
 BLDG WILL COMPLY WITH THE CITY'S
 HURRICANE MISSILE IMPACT ORDINANCE.
 5IMPACT FEES MUST BE PAID TO THE
 COUNTY BEFORE A PERMIT CAN BE ISSUED.
 CALL 233-5025 FOR MORE INFORMATION.
 6AT TIME OF PERMIT APPLICATION PROVIDE
 TEST DATA - PRODUCT APPROVALS FOR THE
 DOORS WINDOWS AND ROOF COVERING.SEE
 SBC 104.2.
 7RESIDENTIAL UNIT TYPES A AND D HAVE
 TRAVEL DISTANCES > 75' AND MUST COMPLY
 WITH SBC 1004.1.4 AND SBC 1004.1.2.
 8THE EXIT STAIR LAYOUT DOES NOT COMPLY
 WITH SBC 1004.1.4.
 9SBC 412.6.2 REQUIRES AT LEAST ONE
 EXIT ACCESS WITHOUT TRAVEL THROUGH AN
 ELEVATOR LOBBY.
 10THE EXIT DISCHARGE FOR THE NORTH
 HALF OF THE STAIRS DOES NOT COMPLY WITH
 SBC 1010.
 11 PROVIDE COPIES OF THE SOIL AND WIND
 TUNNEL REPORTS.
 12SPECIFY FIRE RETARDANT LUMBER ON
 SHEET A6 AND AS NECESSARY THROUGHOUT.
 13SHEET S7 DOES NOT SHOW DESIGN LOADS
 FO CORRIDORS OR PUBLIC ROOMS AND THE
 LOBBIES ARE SHOWN AS 40 PSF.SEE SBC
 1604.1.
 14LATERAL SOIL PRESSURE IS NOT SHOWN
 IN THE DESIGN LOADS FOR THE GARAGE.
 SEE SBC 1608.1.
 15SHOW THE DESIGN LOADS FOR THE
 VARIOUS RAILINGS.SEE SBC 1608.2
 16WATER PROOFING OR DAMP PROOFING
 MEASURES ARE NOT SHOWN FOR THE PORTIONS
 OF THE GARAGE BELOW GRADE.SBC 1814.
 17SHOW THE LOCATION OF THE RELIEF
 VENTS IN THE STAIRS AND THE
 CALCULATIONS AND OPERATION TO MAINTAIN
 THE 2500CFM REQUIRED BY SBC 412.11 #5.
 OR COMPLY WITH SBC 1005.6.
 18HOW WILL SMOKE CONTROL FOR THE
 WINDOWLESS ROOMS BE PROVIDED?SBC
 412.5.
 19SHOW THE VENTILATION FOR THE GARAGE.
 SBC 411.4.2.
 20ELECTRICAL PANELS E17A AND E17B BOTH
 SHOW NORTH STAIRS FANS.THE MECHA
 PLANS SHOW 5 HP AND THE LEEC PLANS SHOW
 10 HP FANS.PLEASE CLARIFY.
 21SHOW THE EMERGENCY ROOF DRAIN
 OVERFLOW METHOD.SBC 1517.6.4.3.

Review Stop E ELECTRICAL
Rev No 33 Status P Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-06-05 Time 14:01 Rev Time 0.25
Received By dpalmer Date 2003-05-08 Time 08:55 Sent To  
Notes
2003-05-08 00:00:00SUBMITTAL/ CERTIFICATIONLETTER FOR
 EM GEN.

Review Stop E ELECTRICAL
Rev No 32 Status P Date 2003-05-07 Cont ID  
Sent By dpalmer Date 2003-05-07 Time 14:48 Rev Time 0.25
Received By dpalmer Date 2003-05-07 Time 14:48 Sent To P
Notes
2003-05-07 00:00:00REV FOR WATERFALL EQUIPMENT RM.

Review Stop E ELECTRICAL
Rev No 31 Status P Date 2003-04-22 Cont ID  
Sent By shernand Date 2003-05-05 Time 10:27 Rev Time 0.33
Received By dpalmer Date 2003-04-22 Time 16:15 Sent To  
Notes
2003-04-22 00:00:00REV FO RUNIT #1001 OK.

Review Stop E ELECTRICAL
Rev No 30 Status P Date 2003-04-22 Cont ID  
Sent By dpalmer Date 2003-04-22 Time 16:03 Rev Time 0.00
Received By dpalmer Date 2003-04-22 Time 16:15 Sent To  
Notes
2003-04-22 00:00:00REV OK FOR UNIT #803

Review Stop E ELECTRICAL
Rev No 29 Status P Date 2003-04-22 Cont ID  
Sent By dpalmer Date 2003-04-22 Time 15:46 Rev Time 0.33
Received By dpalmer Date 2003-04-22 Time 15:46 Sent To  
Notes
2003-04-22 00:00:00REV OK, FOR UNTI #301

Review Stop E ELECTRICAL
Rev No 28 Status P Date 2003-04-22 Cont ID  
Sent By dpalmer Date 2003-04-22 Time 15:42 Rev Time 0.33
Received By dpalmer Date 2003-04-22 Time 15:42 Sent To  
Notes
2003-04-22 00:00:00ELECTRICAL RISER REV,FOR 400A DISC`S

Review Stop E ELECTRICAL
Rev No 27 Status P Date 2003-04-22 Cont ID  
Sent By dpalmer Date 2003-04-22 Time 15:42 Rev Time 0.25
Received By dpalmer Date 2003-04-22 Time 13:47 Sent To  
Notes
2003-04-22 00:00:00OK, LOBBY EQUIPMENT RM REV .

Review Stop E ELECTRICAL
Rev No 26 Status P Date 2003-04-22 Cont ID  
Sent By dpalmer Date 2003-04-22 Time 13:36 Rev Time 0.25
Received By dpalmer Date 2003-04-22 Time 13:36 Sent To  
Notes
2003-04-22 00:00:00REV FOR UNIT #1204 OK.

Review Stop E ELECTRICAL
Rev No 25 Status P Date 2003-04-22 Cont ID  
Sent By dpalmer Date 2003-04-22 Time 12:56 Rev Time 0.30
Received By dpalmer Date 2003-04-22 Time 12:56 Sent To  
Notes
2003-04-22 00:00:00UNIT # 603
 REDLINED RECEPT FOR 210-52

Review Stop E ELECTRICAL
Rev No 24 Status P Date 2003-03-18 Cont ID  
Sent By shernand Date 2003-04-18 Time 15:15 Rev Time 0.50
Received By dpalmer Date 2003-03-18 Time 08:56 Sent To  
Notes
2003-03-18 00:00:00****** POOL EQUIPMENT ROOM ************

Review Stop E ELECTRICAL
Rev No 23 Status F Date 2003-02-26 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 18:14 Rev Time 0.50
Received By dpalmer Date 2003-02-26 Time 18:13 Sent To  
Notes
2003-02-26 00:00:00*************** UNSAT **************
  
 UNIT G/FIRST FLOOR/PENTHOUSE
  
 1)NOTE: PLEASE CORRELATE LOADS ON G1,
 W/ LOADS ON G2, G3.
  
 2)NOTE: PLEASE SEE MAX LOAD ON 15A/#14
 1440. PLEASE SEE SOME SHOWN OVER.
 PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 22 Status F Date 2003-02-26 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 17:37 Rev Time 0.50
Received By dpalmer Date 2003-02-26 Time 16:25 Sent To  
Notes
2003-02-26 00:00:00**************** UNSAT *************
 PH-3
 1)NOTE: PLEASE SEE PANEL SCHEDULE FOR
 F1, PLEASE CORRELATE LOADS FOR SUB
 PANELS F2 AND F3.
  
 2)NOTE: PLEASE SEE LOADS ON 15A BRKRS
 LOADS EXCEED 80%, PLEASE CLARIFY IF
 LOADS THAT ARE ON 20A CIRCUITS, SHOWN AS
 1440 ARE SWITCHED WITH 15A CIRCUTIS??
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IFTHERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 21 Status F Date 2003-02-26 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 16:03 Rev Time 0.50
Received By dpalmer Date 2003-02-26 Time 16:03 Sent To  
Notes
2003-02-26 00:00:00********** UNSAT ***************
 UNIT 1204
 1)NOTE: PLEASE SEE LOADS SHOWN ON 15A
 BRKRS. LOADS EXCEED 80%.
  
 2)NOTE: PLEASE SEE LOADS ON PANEL "A"
 FEEDING SUB PANEL. PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE RECEPT AT MASTER
 BATH SINK LOCATION. MIN 3" PER 210-52D
  
 UNIT 1204

Review Stop E ELECTRICAL
Rev No 20 Status P Date 2003-02-26 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 16:02 Rev Time 0.50
Received By dpalmer Date 2003-02-26 Time 16:02 Sent To  
Notes
2003-02-26 00:00:00REV FOR LOBBY /LOWER LEVEL.

Review Stop E ELECTRICAL
Rev No 19 Status F Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 07:17 Rev Time 1.50
Received By dpalmer Date 2003-02-18 Time 07:17 Sent To  
Notes
2003-02-18 00:00:00************** UNSAT ***************
  
 PLANS HAVE BEEN SUBMITTED FOR FINAL
 "AS-BUILT" REVISED DRAWINGS, PLEASE
 SEE THE FOLLOWING NOTES.
  
 1)NOTE: PLEASE SEE UNIT 301, EQUIPMENT
 GROUNDING CONDUCTOR SHOWN AS ALUM.
 AS PER LOCAL AMENDMENTS, 310-2 ALUM
 SHALL NOT BE USED FOR GROUNDING. PLEASE
 NOTE, ALL OTHER UNITS ARE SHOWN AS CU.
  
 2)NOTE: PLEASE SEE UNIT #803, PLEASE
 SEE LOADS SHOWN ON 15A BRKRS. MAX VA
 ON 15A IS 1440. (80%) THIS HAS BEEN
 CORRECTED ON ALL OF THE OTHER SHEETS
 SUBMITTED.
  
  
 3)NOTE: PLEASE SEE LOADS THAT DO NOT
 CORRELATE. MAIN PANELS SHOW ONE LOAD
 AND SUB PANELS SHOW DIFFERENT LOAD.
 UNIT 1001,603, PH-3.
  
 PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 18 Status P Date 2003-02-14 Cont ID  
Sent By dpalmer Date 2003-02-14 Time 05:51 Rev Time 0.25
Received By dpalmer Date 2003-02-14 Time 05:51 Sent To  
Notes
2003-02-14 00:00:00REV FOR CONDUITS.

Review Stop E ELECTRICAL
Rev No 17 Status P Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 19:07 Rev Time 0.25
Received By dpalmer Date 2003-02-06 Time 19:07 Sent To  
Notes
2003-02-06 00:00:00UNIT #804 ONLY

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2003-01-14 Cont ID  
Sent By dpalmer Date 2003-01-14 Time 07:01 Rev Time 6.00
Received By dpalmer Date 2003-01-14 Time 07:01 Sent To  
Notes
2003-01-14 00:00:00NOTES TO FOLLOW.
 ********** NOTES/PROVISO ***********
  
 BEFORE MARCH 1ST, 2003
  
 PLEASE NOTE, THESE ARE MOSTLY THE SAME
 NOTES FOR ALL OF THE FOLLOWING UNITS.
 PLEASE NOTE SOME UNITS MAY BE DIFFERENT
 DUE TO MODEL AND OWNER CHANGES.
  
 1)NOTE: PLEASE CORRELATE ALL LOAD
 CALCULATIONS AND PANEL SCHEDULES PER
 UNIT. PLEASE SEE LOADS SHOWN ON
 SUB-PANELS, THESE DO NOT CORRELATE WITH
 MAIN PANEL LOAD SCHEDULE.
  
 2)NOTE: PLEASE NOTE SOME UNITS APPEAR TO
 HAVE RECEPTS MORE THAN 3' FROM SINKS,
 PER 210-52D.
  
 3)NOTE: PLEASE ALSO NOTE SOME UNITS ARE
 MISSING OUTLETS IN ORDER TO MEET 210-52.
  
 4)NOTE: PLEASE NOTE, ORIG PLANS WERE
 SUBMITTED FOR MOSTLY GAS APPL/DRYERS,
 DUE TO MANY CHANGES IN LOADS TO UNIT
 PLANS. PLEASE RECONFIGURE LOAD CALCULAT-
 IONS FOR BLDG SERVICE AND SUBMIT REVISED
 PLAN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE 03/01/03. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 UNITS, 603,604,804,1003,1004,
 704,904 702,703

Review Stop E ELECTRICAL
Rev No 15 Status F Date 2003-01-07 Cont ID  
Sent By dpalmer Date 2003-01-07 Time 08:30 Rev Time 0.75
Received By dpalmer Date 2003-01-07 Time 08:30 Sent To  
Notes
2003-01-07 00:00:00************* UNSAT *****************
 6TH FLR UNIT 601 REV.
  
 1)NOTE: PLEASE SEE OVERLOADING OF
 CIRCUITS IN PANEL.
 PLEASE BREAK DOWN LOAD CALACULATIONS
 TO SEE IF 200AQ PANEL IS ADEQUATE FOR
 UNIT. LOAD IS SHOWN AT OVER 345 A'S???
  
 PLEASE SUBMITTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 14 Status F Date 2002-12-27 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 12:06 Rev Time 0.25
Received By dpalmer Date 2002-12-27 Time 12:06 Sent To  
Notes
2002-12-27 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE REVISED PANEL SCHED.
 LOAD EXCEEDS RATING OF EQUIPMENT.PLEASE
 ALSO NOTE, LOAD CALCS NEED TO CORRELATE
 TO ART 220 OFTHE NEC.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 13 Status F Date 2002-12-16 Cont ID  
Sent By jleahy Date 2002-12-16 Time 08:58 Rev Time 4.30
Received By jleahy Date 2002-12-16 Time 08:53 Sent To  
Notes
2002-12-16 00:00:00UNIT 603PANEL C2#4,8 OVERLOADED
  
 UNIT 604PANEL D2#6 OVERLOADED
 SUB POANEL LOADS DO NOT MATCH
 LOAD SHOWN IN MAIN PANEL
  
 UNIT804CIRCUIT #6 OVERLOADED
  
 UNIT 1003CIRCUIT 4,8OVERLOADED
  
 UNIT 1004CIRCUIT 6 OVERLOADED
  
 ALSO NEED TO SUPPLY CUT SHEET FOR FIXTUR
 RA-600LM/RA-AD

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2002-12-16 Cont ID  
Sent By jleahy Date 2002-12-16 Time 08:52 Rev Time 4.00
Received By jleahy Date 2002-12-13 Time 14:26 Sent To  
Notes
2002-12-13 00:00:00UNIT 702 CIRCUIT #3 IS OVERLOADED PER
 PLAN.LOAD ON SUB PANEL NOT THE SAME
 WHEN PUT INTO MAIN PANEL.
  
 UNIT 703 SAME WITHN SUB PANEL, CIRCUIT
 #4,8 IN C2 ARE OVERLOADED PER PLAN.
  
 UNIT 704 SAME WITH PANELS, CIRCUIT #6
 IN D2 IS OVERLOADED PER PLAN.
  
 UNIT 904SAME WITH PANELS, CIRCUIT #6 IS
 OVERLOADED PER PLAN.

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2002-12-06 Cont ID  
Sent By dpalmer Date 2002-12-06 Time 12:05 Rev Time 0.00
Received By dpalmer Date 2002-12-06 Time 11:27 Sent To  
Notes
2002-12-27 00:00:00SEE OTHER NOTES ON PREVIOUS REVIEWS.

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2002-08-07 Cont ID  
Sent By dpalmer Date 2002-08-07 Time 06:33 Rev Time 0.00
Received By dpalmer Date 2002-08-07 Time 06:33 Sent To  
Notes
2002-08-07 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE REVISIONS NEED TO
 BE SHOWN AS CLOUDS OR TRIANGLES.
 NO REV INDICATED.
  
 2)NOTE: PLEASE NOTE THAT GROUNDING
 CONDUCTOR SHOWN FEEDING PANELS SHALL NOT
 BE ALUM. PER LOCAL AMENDMENTS. 310-2-B-2
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2002-06-07 Cont ID  
Sent By dpalmer Date 2002-06-07 Time 06:52 Rev Time 0.00
Received By dpalmer Date 2002-06-07 Time 06:24 Sent To  
Notes
2002-06-07 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT THE LAST FOUR
 REVISIONS THAT HAVE BEEN SUBMITTED HAVE
 HAD COMMENTS AND EACH TIME ANOTHER REV
 COMES IN, IT HAS NOTHING TO DO WITH
 COMMENTS FROM ANY OF THE OTHER REV OR
 COMMENTS. PLEASE NOTE THAT REV FROM
 NOV OF 2001 ARE NOW BEING SUBMITTED.WE
 HAVE ALREADY HAD REVS THAT WERE A LATER
 DATE THAT HAVE ALREADY BEEN SUBMITTED??
 PLEASE SEE COMMENTS FROM OTHER REVIEWS
 AND SUBMIT THOSE TO INCLUDE ALL REVISION
 S.
  
 2)NOTE: PLEASE NOTE THATSOME SHEETS
 DO NOT INDICATE ON PANEL SCHEDULES OF
 THE REV MADE? PLEASE NOTE E.3.1.3,E.2.1.
 1,E.4.1.3.
  
 3)NOTE: PLEASE ALSO NOTE THAT TWO DIFFER
 -ENT SETS AND ROLLS WERE SUBMITTED AND
 ONLY REV FEES FOR ONE ROLL WERE ADDED.
 PLEASE NOTE THERE ARE ADDTIONAL FEES DUE
  
 PLEASE SUBMIT UP-DATED REVISIONS, AND
 ADDRESS COMMENTS FROM THIS REVIEW AND
 ALL PREVIOUS REVIEWS THAT HAVE STILL NOT
 BEEN ADDRESSED. ONCE AGAIN,,,,IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2002-05-07 Cont ID  
Sent By btrobaug Date 2002-05-07 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2002-05-07 Time 18:36 Sent To  
Notes
2002-05-07 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT A NOTE FROM
 PREVIOUS TWO REVIEWS HAS NOT BEEN
 ADDRESSED AND STILLS SHOWS UP ON PLANS??
 PLEASE NOTE IF PLANS ARE SUBMITTED FOR
 THE THIRD TIME FOR THE SAME COMMENTS
 AND THEY ARE NOT ADDRESS, UNDER 553-80
 OF THE FS/FAC, PLANS CAN BE SUBJECT TO
 A 4X THE PLAN REVIEW/REVISION FEE.
 PLEASE NOTE THAT A PANEL SCHEDULE WAS
 NOT SUBMITTED THIS TIME TO VERIFY THE
 SAME CIRCUITS AS ASK FOR ON THE OTHER
 REVIEWS.
  
 2)NOTE: PLEASE NOTE THAT PLANS ARE NOW
 BEING SUBMITTED FOR ADDING TWO NEW
 1600A SERVICES. PLEASE NOTE THAT ALL
 REQ`MENTS OF 230-2 WOULD NEED TO BE MET
 AND PLANS ARE COMPLETE ENOUGHT FOR THAT.
 PLEASE ALSO NOTE THAT PLANS ARE SHOWING
 NEW OVER HEAD FEEDS WHICH SHOWS MORETHAN
 8'FT OF UNPROTECTED CONDUCTORS INSIDE
 THE BLDG. THIS IS NOT PERMITTED PER
 LOCAL AMENDMENTS 230-70
  
 3)NOTE:PLEASE ALSO NOTE THAT A COMPLETE
 2HR SEPARATION WOULD BE NEEDED BETWEEN
 EXISTING BLDG AND NEW ELECTRICAL ROOM
 WITH A SEPARATE FEED FROM FPL IF A
 SECOND SERVICE WAS PERMITTED TO THE SAME
 BLDG.
  
 4)NOTE: PLEASE NOTE GROUPING OF MAINS
 PER 230-72. IDENTIFICATION PER 230-2E
  
 5)NOTE:PLEASE NOTE THAT SERVICE ENTRANCE
 CONDUCTORS DO NOT MEET 240-3C. 310-16
 110-14C
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2001-12-24 Cont ID  
Sent By dpalmer Date 2001-12-24 Time 06:51 Rev Time 0.00
Received By dpalmer Date 2001-12-24 Time 06:51 Sent To  
Notes
2001-12-24 00:00:00***************** UNSAT ***********
  
 1)NOTE: PLEASE NOTE THAT LIGHTNING
 PROTECTION SYSTEM MUST BE SUBMITTED WITH
 A SEPARATE PERMIT APPLICATION AND PLANS.
 MUST PAY FOR PERMIT FEES ETC UNDER NEW
 APPLICATION.
 PLEASENOTE THAT THIS IS THE SAME
 FROM THE LAST TIME THE LIGHTNING SUB-
 -MITTALS WERE TURNED IN.
  
 PLEASE SUBMIT SEPARATELY WITH SEPARATE
 PERMIT APPLICATION. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2001-11-05 Cont ID  
Sent By dpalmer Date 2001-11-05 Time 20:10 Rev Time 0.00
Received By dpalmer Date 2001-11-05 Time 20:10 Sent To  
Notes
2001-11-05 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT OUTLETS SHOWN
 ON E.1.2.1 ARE SHOWN AS 2-POLE AND NOTED
 AS 208V 3-PHASE AND 30AMPS? PLEASE NOTE
 THAT PANEL SCHEDULES SHOW AS 1-POLE
 20AMP OUTLETS.
 CIRCUITS ARE SHOWN AS 2-POLE?
  
 PLEASE CLARIFY AND CORRECT. PLEASE
 SUBMIT FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-11-02 Cont ID  
Sent By dpalmer Date 2001-11-02 Time 06:50 Rev Time 0.00
Received By dpalmer Date 2001-11-02 Time 06:49 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-08-15 Cont ID  
Sent By jleahy Date 2001-08-15 Time 11:02 Rev Time 0.00
Received By jleahy Date 2001-08-15 Time 11:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-07-12 Cont ID  
Sent By jleahy Date 2001-07-12 Time 14:10 Rev Time 2.00
Received By jleahy Date 2001-07-12 Time 14:07 Sent To  
Notes
2001-07-12 00:00:00MISSING ALL BUT 5 PAGES NEED ALL
 DRAWINGS FOR THE ELECTRICAL WORK!!!!!

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-05-30 Cont ID  
Sent By jleahy Date 2001-05-30 Time 10:33 Rev Time 5.00
Received By jleahy Date 2001-05-30 Time 10:10 Sent To  
Notes
2001-05-30 00:00:00E6.1.1 SHOWS RISER WITH NO WIRE SIZES
 AND/OR CONDUIT SIZES.
  
 NEED A SCHEDULE FOR MCC SIZE OF WIRES TO
 THE DIFFERNET LOADS, SHOW SIZES OF FUSE
 OR CIRCUIT BREAKERS TO LOADS FED BY MCC
  
 PLEASE SHOW HOW IN THE PENTHOUSES THAT
 ONE METER WILL BE FEEDING THREE PANELS
 FOR UNITS F(2), G , AND JSUBMIT RISER
  
 PLANS ARE GENERALY IN GOOD SHAPE BUT
 THERISER DIAGRAM IS VERY CONFUSING, A
 ONE
 LINE FOR THE NORMAL AND ONE FOR THE
 EMERGENCY RISERS WOULD BE GREAT SHOWING
 WHATFEEDS WHAT WITHOUT HAVING TO GO TO
 SEVER
 AL PAGES TO GET THE INFORMATION!

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-29 Cont ID  
Sent By dpalmer Date 2001-03-29 Time 06:14 Rev Time 0.00
Received By dpalmer Date 2001-03-28 Time 19:12 Sent To  
Notes
2001-03-29 00:00:00****************UNSAT ****************
  
 1)NOTE:PLEASE NOTE WIRE SIZE SHOWN FOR
 "MCC" AT 500MCM AL. PLEASE SEE 75DEGREE
 COLLUMN IN 310-16. "310A"`S
 2)NOTE: PLEASE NOTE THAT MANY PAGES ARE
 NOT READABLE. PRINT IS BLURRED AND VERY
 SMALL. MOSTLY ON SHEETS THAT GIVE YOU
 A COMPLETE OVER VIEW OF BLDG.
  
 3)NOTE:E.2.2.2 MISSING OUTLETS PER LOCAL
 CODE. PLEASE NOTE THAT THE LOCAL CODE
 REQ`S MIN OUTLET SPACING OF EVERY 12` IN
 OFFICE SPACE AND EVERY 20`OF WALL SPACE
 IN STORAGE/HALLWAY AREAS. ONLY WALLS OF
 UNENCUMBERED SPACE. 210-50
  
 4)NOTE: PLEASE NOTE THAT THERE ARE SHEET
 S WITH NO ELECTRICAL SHOWN.E.2.2.2,
 E.4.1.2,E.4.1.3,E.4.2.0,E.4.2.2 ,,,,,,
  
 5)NOTE: PLEASE NOTE ALL HOUSE LOADS THAT
 ARE CONTINUOUS NEED TO BE SHOWN AT 125%
 WHERE ARE LOADS SHOWN FOR "MCC".
 RISER DIAGRAM IS MISSING CONDUIT/WIRE
 SIZE FROM MCC MAIN TO MCC.? PLEASE CLARI
 FY.
  
 6)NOTE: IN ADDITION; PLEASE SHOW CONDUIT
 AND WIRE SIZES ON LINE DIAGRAM FOR
 RISER. WE HAVE RUN INTO MANY PROBLEMS
 ON JOBS WHERE CONTRACTORS ARE NOT LOOKIN
 G AT PANEL SCHEDULES FOR CONDUIT AND WIR
 E SIZES. CONDUIT AND WIRE SIZES CAN BE S
 HOWN AS TYPICAL FOR COMMON UNITS.
  
 7)NOTE: PLEASE CLARIFY GROUNDING ELECTRO
 DE SYSTEM.PER 250-50
  
 8)NOTE: PLEASE CLARIFY TYPE OF FUEL FOR
 GENERATOR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS OR
 IF YOU WOULD LIKE A MEETING, PLEASE CALL
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2001-09-17 Cont ID  
Sent By mamini Date 2001-09-17 Time 14:32 Rev Time 3.00
Received By mamini Date 2001-09-17 Time 14:32 Sent To  
Notes
2001-09-17 00:00:00PASSED WITH PROVISOS:
  
 1. THIS PERMIT INCLUDES ALL UNDERGROUND
 UTILITY WORKS & PAVEMENTS ON THE
 PROPOSED SITE.WATER CROSS CONNECTIONS
 MUST BE DONE AFTER THE WATER MAIN DESIGN
 IN N. FLAGLER DR. IS FINAL & APPROVED
 BY THE PUBLIC UTILITIES ENGINEERING
 SERVICES DEPARTMENT.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2001-05-25 Cont ID  
Sent By mamini Date 2001-05-25 Time 15:59 Rev Time 4.00
Received By mamini Date 2001-05-25 Time 15:58 Sent To  
Notes
2001-05-25 00:00:00FAILED:
 1. PLEASE REFER TO PREVIOUS REVIEW
 COMMENTS DATED 3-8-01 AND ADDRESS ITEMS
 2, 11 AND 12.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-03-08 Cont ID  
Sent By mamini Date 2001-03-08 Time 13:04 Rev Time 4.00
Received By mamini Date 2001-03-08 Time 13:03 Sent To  
Notes
2001-03-07 00:00:00FAILED:
 1. THE "APPLICATION FOR COSTRUCTION
 WITHIN PUBLIC R.O.W MUST BE SUBMITTED TO
 CITY ENGINEERS OFFICE PRIOR TO COMMENCE-
 MENT OF ANY WORK IN PUBLIC R.O.W.
 2. SUBMIT CONSTRUCTION PLANS, DETAILS,
 SPECIFICATION, HYDRAULIC, STORM WARTER
 CALCULATION AND ALSO SUBMIT PERVIOUS &
 IMPERVIOUS CALCULATION ON 8 1/2 X 11
 SHEETS WHICH INCLUDE NAME, ADDRESS,
 PROPERTY CONTROL NUMBER SIGNED AND
 SEALED BY DESIGN ENGINEER TO:
 1000 45TH STREET SUITE # 15
 WEST PALM BEACH, FL 33407
 3. A TRUCK WASHOUT AREA SHOULD BE ADDED
 TO SITE PLAN AT EXITS AND MAINTAINED
 DURING CONSTRUCTION.
 4. ALL BROKEN SIDEWALK, CURBS(& GUTTERS)
 ALONG THE PROPERTY (ALL SIDES) SHOULD BE
 REPLACED.
 5. ALL DRIVEWAYS THAT WILL NOT BE USED
 MUST BE REMOVED AND REPLACED WITH
 REGULAR CURBS (& GUTTERS).
 6. ALL DRIVEWAY MUST BE CONSTRUCTED PER
 CITY OF WPB STANDARD.
 7. SHOW CLEAN OUT LOCATION ON SANITARY
 SEWER LATERAL, ON THE PROPERTY AT BACK
 OF THE SIDEWALK IF POSSIBLE.
 8. SHOW LOCATION OF DUMPSTER IF KNOWN.
 9. IF KITCHEN FACILITIES ARE PLANED,
 THEN OIL SEPARATORS WILL NEED TO BE
 INSTALLED TO MEET THE CITY WASTEWATER
 DISCHARGE ORDINANCE.
 10. LOCATION OF METERS AND BACKFLOW
 PREVENTERS TO BE COORDINATED WITH THE
 CITY.
 11. DISCHARGE INTO THE INTERCOASTAL
 WATER WAY SHOULD BE MAINTAINED AT PRE-
 BUILDING RATES.
 12. PERMITS FROM SFWMD AND DEP MUST BE
 OBTAINED FOR DISCHARGING INTO THE
 INTERCOASTAL WATER WAY.
 13. SANITARY MANHOLES ON SHEET C4 ARE
 LABELED SM-1 THROUGH SM-3.PROFILE FOR
 SANITARY SEWER ON SHEET C8, THEY ARE
 LABELED MH-1 THROUGH MH-4 AND SM-4 IS
 MISSING ON SHEET C4, PLEASE VERIFY.
 14. ADD NOTES INDICATING THE REQUIRED
 CLEARANCES FOR WATER CROSSING OVER
 STORM OR SANITARY LINES AND IN CASE OF
 CONFILECT.
 15. PROVIDE CHARTS, DETAILS FOR THRUST
 BLOCKS.
 16. FOR STANDARD DETAILS CONTACT 561-
 659-8088 EXT. 2303
 17. PROVIDE ADDITIONAL INFORMATIONS AND
 SCHEDULES FOR REMOVAL OF EXISTING
 CONCRETE RETAINING WALL.
 17. A SEPARATE PERMITS APPLICATION
 MUST BE SUBMITTED TO CONSTRUCTION
 SERVICES (B&Z) FOR REMOVAL OF EXISTING
 CONCRETE RETAINIG WALL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 16 Status P Date 2003-04-22 Cont ID  
Sent By nmccray Date 2003-04-22 Time 15:33 Rev Time 0.00
Received By nmccray Date 2003-04-22 Time 15:33 Sent To  
Notes
2003-04-22 00:00:00REVISION TO LOBBY WATERWALL EQUIPMENT
 ROOM OK 04/22/03

Review Stop FIRE FIRE DEPARTMENT
Rev No 15 Status P Date 2003-04-10 Cont ID  
Sent By nmccray Date 2003-04-10 Time 11:00 Rev Time 0.00
Received By nmccray Date 2003-04-10 Time 11:00 Sent To  
Notes
2003-04-10 00:00:00PROVISO:
 1) WHAT IS BEING STORED IN THE POOL
 STORAGE AND POOL EQUIPMENT ROOMS.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 14 Status F Date 2003-03-18 Cont ID  
Sent By nmccray Date 2003-03-18 Time 13:22 Rev Time 0.00
Received By nmccray Date 2003-03-17 Time 13:22 Sent To  
Notes
2003-03-18 00:00:001) REVISION ON SHEET F.4.1.3
  
 2) SEPARATE PLAN AND PERMIT BY FIRE
 SPRINKLER CONTRACTOR IS REQUIRED.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status F Date 2003-03-17 Cont ID  
Sent By nmccray Date 2003-03-17 Time 15:28 Rev Time 0.00
Received By nmccray Date 2003-03-17 Time 11:05 Sent To  
Notes
2003-03-17 00:00:001) REVISION FOR SHEET F.3.2.3/1204
  
 2) SEPARATE PLAN AND PERMIT BY FIRE
 SPRINKLER CONTRACTOR IS REQUIRED.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status F Date 2003-03-17 Cont ID  
Sent By nmccray Date 2003-03-17 Time 15:18 Rev Time 0.00
Received By nmccray Date 2003-03-17 Time 15:18 Sent To  
Notes
2003-03-17 00:00:001) REVISION FOR SHEET F.4.2.2/PH3
  
 2) SEPARATE PLAN AND PERMIT BY FIRE
 SPRINKLER CONTRACTOR IS REQUIRED.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status F Date 2003-03-17 Cont ID  
Sent By nmccray Date 2003-03-17 Time 14:52 Rev Time 0.00
Received By nmccray Date 2003-03-17 Time 14:51 Sent To  
Notes
2003-03-17 00:00:001) REVISION ON SHEETS F.2.1.1 , F.2.1.2
 AND F.2.1.3
  
 2) SEPARATE PLAN AND PERMIT BY SPRINKLER
 CONTRACTOR IS REQUIRED.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2002-12-26 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 15:50 Rev Time 0.00
Received By mcarsill Date 2002-12-26 Time 09:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2002-12-06 Cont ID  
Sent By mcarsill Date 2002-12-06 Time 14:43 Rev Time 0.00
Received By mcarsill Date 2002-12-06 Time 14:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2002-05-23 Cont ID  
Sent By mcarsill Date 2002-05-23 Time 08:41 Rev Time 0.00
Received By mcarsill Date 2002-05-23 Time 08:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2001-12-28 Cont ID  
Sent By mcarsill Date 2001-12-28 Time 13:07 Rev Time 0.00
Received By mcarsill Date 2001-12-28 Time 13:07 Sent To  
Notes
2001-12-28 00:00:00INSTALLATION OF TEMPORARY FIRE HYDRANT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2001-11-01 Cont ID  
Sent By dpalmer Date 2001-11-02 Time 08:52 Rev Time 0.00
Received By mcarsill Date 2001-11-01 Time 08:14 Sent To  
Notes
2001-11-01 00:00:00VARIOUS CUT SHEETS FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2001-10-30 Cont ID  
Sent By mcarsill Date 2001-10-30 Time 08:53 Rev Time 0.00
Received By mcarsill Date 2001-10-30 Time 08:53 Sent To  
Notes
2001-10-30 00:00:001) ELECTRICAL PAGES SUBMITTED. PLEASE
 EXPLAIN INFORMATION WITH REGARDS TO
 PERMIT APPLICATION "GARAGE VENTILATION
 SYSTEM".
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-08-01 Cont ID  
Sent By mcarsill Date 2001-08-01 Time 15:00 Rev Time 0.00
Received By mcarsill Date 2001-08-01 Time 15:00 Sent To  
Notes
2001-08-01 00:00:001) LOCATIONS OF ILLUMINATED EXIT SIGNS
 AND EMERGENCY LIGHTS (ADDITIONAL ONES)
 MAY BE NECESSARY AS REQUIRED BY FIRE
 RESCUE PERSONNEL.
 2) STAIRWAY PRESSURIZATION SHALL COMPLY
 WITH NFPA 101, THE LIFE SAFETY CODE,
 SECTION 5-2.3.9.
 3) ENTIRE BUILDING AND MECHANICAL,
 ELECTRICAL, AND FIRE SYSTEMS TO COMPLY
 WITH APPLICABLE CODES AND RECOGNIZED
 STANDARDS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-07-31 Cont ID  
Sent By mcarsill Date 2001-07-31 Time 08:32 Rev Time 0.00
Received By mcarsill Date 2001-07-31 Time 08:32 Sent To  
Notes
2001-07-31 00:00:00GENERATOR CUT SHEETS FOR DIESEL UNIT
 PLANNED FOR ROOM.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-05-24 Cont ID  
Sent By mcarsill Date 2001-05-24 Time 15:41 Rev Time 0.00
Received By mcarsill Date 2001-05-24 Time 15:41 Sent To  
Notes
2001-05-24 00:00:001) GAS METER PRODUCT APPROVAL DISPLAYS
 NO UL OR FM APPROVALS.
 2) NO PLAN REVIEW COMMENTS REGARDING GAS
 INSTALLATION BY GAS COMPANY.
 3) DRYER SHAFTS NOT PROVIDED WITH ENOUGH
 CLEAN-OUT LOCATIONS FOR THE REMOVAL
 OF COMBUSTIBLE LINT. ONLY TWO ARE SHOWN
 AT CHANGE OF DIRECTIONS.
 4) EXPLAIN DOORS AND BALCONIES.
 5) PLEASE PROVIDE PERCENTAGE OF OPENINGS
 PER EXTERIOR WALLS IN PARKING GARAGE.
 PLEASE INDICATE ON PLANS WHETHER THE
 PARKING GARAGE IS CONSIDERED OPEN OR
 CLOSED.
 6) TRASH CHUTES ARE NOT PERMITTED TO
 OPEN INTO THE ELEVATOR EQUIPMENT ROOMS.
 THESE CHUTES ARE TO TERMINATE INTO THE
 OPEN AIR WITH A MINIMUM OF THREE FEET
 ABOVE THE ROOF. PLEASE PROVIDE DETAILS
 FOR TRASH CHUTE TERMINATIONS.
 7) HOW IS ACCESS PROVIDED TO GAS METER
 AND GAS SHUT-OFF VALVE.
 8) PLEASE EXPLAIN HOW PRODUCTS OF
 COMBUSTION WILL NOT ENTER THE
 STAIRTOWERS WHERE OPENINGS ARE PRESENT
 NEAR THE DUAL BALCONIES. THIS OFFICE
 DOES UNDERSTAND THAT THESE MATERIALS
 WILL RISE, BUT WHAT PREVENTS ANY
 CONTAMINATION.
 9) PLEASE INDICATE WHERE THE ELEVATOR
 LOCATED IN THE NORTHWEST CORNER OF
 THE PROPERTY TRAVELS TO.
 10) PLEASE INDICATE EMERGENCY LIGHTING
 IN GARAGE.
 11) PLEASE EXPLAIN GARAGE EXHAUST FANS
 ON/OFF CONTROLS IN FIRE COMMAND ROOM.
 12) PLEASE EXPLAIN ELEVATOR SECURITY
 SWITCHES.
 13) HOW DOES BUILDING SECURITY FEATURES
 AFFECT EXITING.
 14) EXIT DOOR ON PAGE E.1.1.1 NEAR
 GENERATOR ROOM DOES NOT SWING IN THE
 DIRECTION OF EXIT TRAVEL.
 15) PLEASE NOTE ON THE PLANS THAT A
 MINIMUM OF SIX AIR CHANGES ARE REQUIRED
 WITHIN THE CLOSED PARKING GARAGE. GARAGE
 VENTILATION FANS ARE TO BE PROVIDED
 WITH EMERGENCY POWER.
 16) NO LITERATURE PROVIDED BY BCBE OR
 CIVIL ENGINEERS. NO LITERATURE PROVIDED
 FOR GAS FIREPLACES.
 17) PLEASE INDICATE THE WIDTH OF THE
 OPENINGS AT THE STAIRS NEAR THE
 BALCONIES.
  
 WRITER DID SPEAK TO MIKE GOTWALT AND
 OBTAINED SOME ANSWERS TO SOME OF THESE
 PLAN REVIEW COMMENTS HOWEVER WRITER WAS
 NOT COMPLETED.
  
 PLEASE INDICATE HOW SMOKE COULD BE
 REMOVED FROM THE CORE AREAS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-03-08 Cont ID  
Sent By mcarsill Date 2001-03-08 Time 09:28 Rev Time 0.00
Received By mcarsill Date 2001-03-08 Time 09:27 Sent To  
Notes
2001-03-08 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE REQUIREMENTS.
 2) PLEASE DEFINE FIRE INGRESS AND EGRESS
 ROUTES FOR THE BUILDING.
 3) FUTURE DOCK CONSTRUCTION AND FIRE
 PROTECTION FOR THEM NOT SHOWN.
 4) ONLY ONE FIRE DEPARTMENT CONNECTION
 IS SHOWN ON THE DRAWING. SINCE THE
 BUILDING IS CONSIDERED HIGH-RISE, TWO
 FIRE DEPARTMENT CONNECTIONS ARE
 REQUIRED.
 5) THE LANE AROUND THE BUILDING IS TO BE
 A FIRE LANE WITH APPROPRIATE SIGNAGE AND
 PAVEMENT MARKINGS.
 6) THE PORTACOCHERE MUST BE AT LEAST
 13'- 6" HIGH SO FIRE AND PARAMEDICAL
 APPARATUS CAN PASS UNDERNEATH IT.
 7) ELEVATORS TO COMPLY WITH ANSI A17.1,
 PHASE ONE AND PHASE TWO ELEVATOR RECALL.
 ELEVATORS TO COMPLY WITH THE STRETCHER
 REQUIREMENTS OF STANDARD BUILDING CODE,
 SECTION 3003.4.
 8) SIGNS ARE REQUIRED IN THE STAIRWELLS
 INDICATING THE STORY, THE TERMINUS OF
 THE STAIR AT THE TOP AND BOTTOM, AND THE
 IDENTIFICATION OF THE STAIR.
 9) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR THE WALLS
 AND CEILINGS.
 10) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS IN THE
 ASSEMBLY AREAS OF THE BUILDING.
 11) TEMPORARY STANDPIPES AND STAIRS WILL
 BE REQUIRED DURING CONSTRUCTION.
 12) PLEASE PROVIDE MORE DETAILS ON THE
 GAS METER ROOMS LOCATED ON EACH FLOOR.
 13) WHAT WILL THE DEAD SPACE ON PAGE
 A.3.2.1 BE USED FOR.
 14) HOW IS THE GAS SHUTOFF VALVE SHOWN
 ON PAGE P.0.0.1 "TYPICAL FUEL GAS
 APPLIANCE PIPING DETAIL" MADE
 ACCESSIBLE.
 15) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER DRAWINGS.
 16) A KNOX-BOX RAPID ENTRY SYSTEM IS
 REQUIRED FOR THE BUILDING.
 17) PLEASE PROVIDE PRODUCT LITERATURE
 FOR THE GAS FIREPLACES.
 18) A TWO HOUR FIRE SEPARATION IS
 REQUIRED BETWEEN THE PARKING GARAGE AND
 THE BUILDING.
 19) A CODE SUMMARY IS REQUIRED FOR THE
 PARKING GARAGE AND RESIDENTIAL TOWER.
 PLEASE INDICATE TYPE OF CONSTRUCTION
 AND CODES USED FOR DESIGN. PLEASE
 INDICATE NUMBER OF OPENINGS FOR THE
 PARKING GARAGE.
 20) ROOMS IN THE GARAGE SHALL BE
 SEPARATED FROM THE PARKING AREAS BY
 AT LEAST ONE HOUR. THE GENERATOR AND
 FIRE PUMP ROOM IF DIESEL FUEL IS
 PRESENT, MUST BE SEPARATED BY TWO HOUR
 CONSTRUCTION.
 21) FIRE DAMPERS TO COMPLY WITH UL 555.
 22) STAIR PRESSURIZATION FANS ARE TO
 ACTIVATE WHEN THE FIRE SPRINKLER SYSTEM
 OR FIRE ALARM SYSTEM HAS OPERATED.
 23) EMERGENCY LIGHTING REQUIRED IN FIRE
 PUMP ROOM.
 24) WILL THE GUARD HOUSE BE STAFFED
 FULL TIME.
 25) WHAT ROUTE DOES FIRE RESCUE USE TO
 GET TO THE UPPER LEVEL.
 26) THE SCISSOR STAIRS MUST BE SEPARATED
 FROM ONE ANOTHER SINCE A SINGLE SHAFT
 IS BEING USED TO PROVIDE TWO SEPARATE
 EXITS FROM SINGLE AREAS. TWO HOUR FIRE
 SEPARATIONS WILL BE REQUIRED BETWEEN THE
 TWO SCISSOR STAIRS LOCATED IN A SINGLE
 TWO HOUR RATED FIRE SHAFT.
 27) PLEASE PROVIDE INCLINE DRAWINGS TO
 THE SECOND LEVEL WHERE THE FIRE COMMAND
 ROOM WILL BE LOCATED.
 28) STAIRS TO COMPLY WITH NEW STAIR
 REQUIREMENTS OF THE LIFE SAFETY CODE.
 29) HANDRAILS AND GUARDS TO COMPLY WITH
 REQUIREMENTS OF THE LIFE SAFETY CODE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2003-06-05 Cont ID  
Sent By shernand Date 2003-06-05 Time 14:01 Rev Time 0.00
Received By shernand Date 2003-06-05 Time 14:01 Sent To E
Notes
2003-06-05 00:00:00BT

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2003-05-20 Cont ID  
Sent By shernand Date 2003-05-20 Time 16:43 Rev Time 0.00
Received By shernand Date 2003-05-20 Time 16:43 Sent To  
Notes
2003-05-20 00:00:00DON NEELEY DESK, SUBMITTAL LETTER

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-15 Time 08:57 Rev Time 0.00
Received By shernand Date 2003-05-15 Time 08:57 Sent To Z
Notes
2003-05-15 00:00:00SITE PLAN FOR LANDSCAPING

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2003-05-12 Cont ID  
Sent By shernand Date 2003-05-12 Time 11:01 Rev Time 0.00
Received By shernand Date 2003-05-12 Time 11:01 Sent To  
Notes
2003-05-12 00:00:00DON NEELY DESK, LETTERS FOR SUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2003-05-09 Cont ID  
Sent By shernand Date 2003-05-09 Time 16:56 Rev Time 0.00
Received By shernand Date 2003-05-09 Time 16:56 Sent To  
Notes
2003-05-09 00:00:00DON NEELY DESK. ACEPTANCE LETTER SUBMITT
 ALS

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2003-05-09 Cont ID  
Sent By shernand Date 2003-05-09 Time 09:21 Rev Time 0.00
Received By shernand Date 2003-05-09 Time 09:21 Sent To  
Notes
2003-05-09 00:00:00DON NEELY DESK, TWO SUBMITTALS WITH
 LETTERS

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2003-05-07 Cont ID  
Sent By shernand Date 2003-05-07 Time 14:56 Rev Time 0.00
Received By shernand Date 2003-05-07 Time 14:56 Sent To  
Notes
2003-05-07 00:00:00DON NEELY DESK. CERTIFICATIONS AND
 LETTERS.

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 11:22 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 11:22 Sent To B
Notes
2003-05-05 00:00:00SUBMITTAL LETTERS, GAVE TO MIKE SIZEMORE

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 10:35 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 10:35 Sent To P
Notes
2003-05-05 00:00:002 REV, ONE SUBMITTAL ON KS DESK

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 10:29 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 10:29 Sent To FIRE
Notes
2003-05-05 00:00:00FIRE ALARM CERT. SUBMITTAL. PLACED ON
 FIRE CHAIR.

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 10:26 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 10:26 Sent To E
Notes
2003-05-05 00:00:00DP DESK. GENERATOR CERT. SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 10:23 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 10:23 Sent To B
Notes
2003-05-05 00:00:00HP DESK. 2 SUBMITTALS.5/5 2 ADDT'L
 SUBMITTALS FOR PRODUCT APPROVALS.

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-04-25 Time 16:41 Rev Time 0.00
Received By shernand Date 2003-04-25 Time 16:41 Sent To P
Notes
2003-04-25 00:00:00KSTEVENS

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-04-25 Time 09:09 Rev Time 0.00
Received By shernand Date 2003-04-25 Time 09:09 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2003-04-24 Cont ID  
Sent By shernand Date 2003-04-24 Time 12:00 Rev Time 0.00
Received By shernand Date 2003-04-24 Time 12:00 Sent To  
Notes
2003-04-24 00:00:00SUBMITTAL, LETTERS TO MIKE SIZEMORE PER
 HIS REQUEST.

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2003-04-23 Cont ID  
Sent By shernand Date 2003-04-23 Time 10:34 Rev Time 0.00
Received By shernand Date 2003-04-23 Time 10:34 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2003-04-22 Cont ID  
Sent By shernand Date 2003-04-22 Time 16:38 Rev Time 0.00
Received By shernand Date 2003-04-22 Time 16:38 Sent To B
Notes
2003-04-22 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2003-04-18 Cont ID  
Sent By shernand Date 2003-04-18 Time 15:15 Rev Time 0.00
Received By shernand Date 2003-04-18 Time 15:15 Sent To E
Notes
2003-04-18 00:00:00DP DESK.REVISIONS FOR 6 DIFFERENT UNITS.

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2003-04-17 Cont ID  
Sent By shernand Date 2003-04-17 Time 16:54 Rev Time 0.00
Received By shernand Date 2003-04-17 Time 16:54 Sent To  
Notes
2003-04-17 00:00:00COMM BOARD #9

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2003-04-17 Cont ID  
Sent By shernand Date 2003-04-17 Time 11:26 Rev Time 0.00
Received By shernand Date 2003-04-17 Time 11:26 Sent To B
Notes
2003-04-17 00:00:00HP DESK
 TWO SUBMITTALS ENCLOSED

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2003-04-14 Cont ID  
Sent By shernand Date 2003-04-14 Time 16:43 Rev Time 0.00
Received By shernand Date 2003-04-14 Time 16:43 Sent To B
Notes
2003-04-14 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2003-04-14 Cont ID  
Sent By shernand Date 2003-04-14 Time 16:42 Rev Time 0.00
Received By shernand Date 2003-04-14 Time 16:42 Sent To B
Notes
2003-04-14 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 13:38 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 13:37 Sent To B
Notes
2003-04-11 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 13:37 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 13:37 Sent To B
Notes
2003-04-11 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 13:36 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 13:36 Sent To B
Notes
2003-04-11 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 13:35 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 13:35 Sent To B
Notes
2003-04-11 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 13:34 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 13:34 Sent To B
Notes
2003-04-11 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2003-04-07 Cont ID  
Sent By shernand Date 2003-04-07 Time 16:09 Rev Time 0.00
Received By shernand Date 2003-04-07 Time 16:09 Sent To B
Notes
2003-04-07 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2003-04-04 Cont ID  
Sent By shernand Date 2003-04-04 Time 15:14 Rev Time 0.00
Received By shernand Date 2003-04-04 Time 15:14 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2003-04-04 Cont ID  
Sent By shernand Date 2003-04-04 Time 15:09 Rev Time 0.00
Received By shernand Date 2003-04-04 Time 15:09 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 16:08 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 16:08 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 11:10 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 11:10 Sent To B
Notes
2003-04-03 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2003-03-31 Cont ID  
Sent By btrobaug Date 2003-03-31 Time 16:09 Rev Time 0.00
Received By btrobaug Date 2003-03-31 Time 15:54 Sent To B
Notes
2003-03-31 00:00:00TO HHP./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2003-03-25 Cont ID  
Sent By sthyng Date 2003-03-25 Time 17:03 Rev Time 0.00
Received By sthyng Date 2003-03-25 Time 17:03 Sent To  
Notes
2003-03-25 00:00:00SUBMITTALS
  
 1.)ACCEPTANCE LETTER FOR ON SITE
 SANITARY LINE FROM ENGINEER OF RECORD -
 TO PLUMBING IN BOX
  
 2.)ROOFING SUBMITTALS RE-SUBMITTED
 IN RESPONSE TO HP COMMENTS - TO HP
 DESK

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-24 Time 16:09 Rev Time 0.00
Received By sthyng Date 2003-03-24 Time 16:09 Sent To  
Notes
2003-03-24 00:00:001.)MECHANICAL REVISION TO MECH BOX
 (REVISION AT MEDIA ROOM)
  
 2.)LETTER FROM STRUCTURAL ENGINEER
 REGARDING SCUPPER HEIGHTS AT THE ROOF
 AND THE ROOF DECK'S ABILIT TO HOLD THE
 PROPER WATER DEPTH TO MATCH THESE
 SCUPPER HEIGHTS - TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-24 Time 08:17 Rev Time 0.00
Received By sthyng Date 2003-03-24 Time 08:17 Sent To B
Notes
2003-03-24 00:00:00TO HP DESK
 ENGINEERING FOR STOREFRONT ALUM AT NW
 ELEVATOR STRUCTURE MISSING FROM ORIGINAL
 DRAWING

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2003-03-17 Cont ID  
Sent By sthyng Date 2003-03-17 Time 08:51 Rev Time 0.00
Received By sthyng Date 2003-03-17 Time 08:51 Sent To B
Notes
2003-03-17 00:00:001.) WRITTEN REQUEST FROM ARCHITECT OF
 RECORD T REMOVE 4 UNITS FROM CO OF
 THE NOTED PERMIT NUMBER.
  
 2.) STRUCTURAL REVISION TO UNIT 15F
 BALCONY.
  
 SENT TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 10:53 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 10:53 Sent To  
Notes
2003-03-13 00:00:00COMM BOARD #3 - REVISIONS TO E,P,M
  
 1.REVISED POOL EQUIPMENT ROOM
 DRAWINGS
  
 2.FOUNTAIN MECHANICAL ROOM ADDITION

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 10:47 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 10:47 Sent To M
Notes
2003-03-13 00:00:00REVISION TO CHANGE SLOT DIFFUSER
 DIMENSIONS AT LOBBY LEVEL SOCAL ROOM
 AND MAIN LOBBY AREA

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 10:03 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 10:01 Sent To P
Notes
2003-03-13 00:00:00RESUB FOR UNIT 601 PLUMBING/GAS COMMENTS
 FROM 1/14/03

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 09:57 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 09:57 Sent To B
Notes
2003-03-13 00:00:00SUBMITTALS/REVISIONS SENT TO HP DESK:
  
 1. FIRE CAULK DETAIL AT SCISSOR STAIRS
 TO WALL
  
 2.REVERSE DOOR SWING AT 04 (D-UNIT)
 UNIT MECHANICAL ROOM
  
 3.STAIR PRESSURIZATION LOUVER
 RELOCATED BY ARCHITECT/ENGINEER
  
 4.ADD RAILING/GATES TO POOL DECK PER
 REQUEST OF NEIL MELNICK, DON NEELY, RICK
 JONES MEETING ON 2/26/03
  
 5.DELETION OF MECHANICAL ROOM CEILING
 AND FLOOR ISOLATION DETAIL

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2003-03-05 Cont ID  
Sent By dpalmer Date 2003-03-05 Time 10:52 Rev Time 0.00
Received By dpalmer Date 2003-03-05 Time 10:52 Sent To B
Notes
2003-03-05 00:00:00ROOFING SUBMITTALS TO HP`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2003-03-04 Cont ID  
Sent By dpalmer Date 2003-03-04 Time 08:36 Rev Time 0.00
Received By dpalmer Date 2003-03-04 Time 08:36 Sent To B
Notes
2003-03-04 00:00:00TO HP`S DESK

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2003-02-28 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 15:50 Rev Time 0.00
Received By btrobaug Date 2003-02-28 Time 15:50 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2003-02-20 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 14:33 Rev Time 0.00
Received By dpalmer Date 2003-02-20 Time 14:33 Sent To B
Notes
2003-02-20 00:00:00TO HHP`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2003-02-20 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 14:32 Rev Time 0.00
Received By dpalmer Date 2003-02-20 Time 14:32 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 10:28 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 10:28 Sent To B
Notes
2003-02-18 00:00:00SUBMITTALS TO HHP DESK.

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2003-02-13 Cont ID  
Sent By dpalmer Date 2003-02-13 Time 16:07 Rev Time 0.00
Received By dpalmer Date 2003-02-13 Time 16:07 Sent To  
Notes
2003-02-13 00:00:004-ROLLS OF REV'S
 TO #53 ON COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2003-02-06 Cont ID  
Sent By btrobaug Date 2003-02-06 Time 15:28 Rev Time 0.00
Received By btrobaug Date 2003-02-05 Time 15:27 Sent To B
Notes
2003-02-06 00:00:00TO HHP./WRT

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 09:05 Rev Time 0.00
Received By dpalmer Date 2003-02-04 Time 09:05 Sent To B
Notes
2003-02-04 00:00:00TO HHP`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2002-12-27 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 12:04 Rev Time 0.00
Received By dpalmer Date 2002-12-27 Time 12:04 Sent To  
Notes
2002-12-27 00:00:00TO COMM BOARD #23

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2002-12-24 Cont ID  
Sent By dpalmer Date 2002-12-24 Time 10:15 Rev Time 0.00
Received By dpalmer Date 2002-12-24 Time 10:15 Sent To M
Notes
2002-12-24 00:00:00TO MECH INBOX.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2002-12-23 Cont ID  
Sent By dpalmer Date 2002-12-23 Time 10:59 Rev Time 0.00
Received By dpalmer Date 2002-12-23 Time 10:59 Sent To  
Notes
2002-12-23 00:00:00TO COMM BOARD, #42

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2002-12-16 Cont ID  
Sent By btrobaug Date 2002-12-16 Time 17:00 Rev Time 0.00
Received By btrobaug Date 2002-12-16 Time 17:00 Sent To B
Notes
2002-12-16 00:00:00TO HAROLD P./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2002-12-11 Cont ID  
Sent By btrobaug Date 2002-12-11 Time 18:44 Rev Time 0.00
Received By btrobaug Date 2002-12-11 Time 18:44 Sent To B
Notes
2002-12-11 00:00:00TO HAROLD P./WRT

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2002-11-25 Cont ID  
Sent By btrobaug Date 2002-11-25 Time 17:58 Rev Time 0.00
Received By btrobaug Date 2002-11-25 Time 17:57 Sent To B
Notes
2002-11-25 00:00:00TO HAROLD P./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2002-11-20 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 10:18 Rev Time 0.00
Received By btrobaug Date 2002-11-19 Time 10:17 Sent To B
Notes
2002-11-20 00:00:00TO HAROLD P./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-19 Cont ID  
Sent By btrobaug Date 2002-11-19 Time 17:15 Rev Time 0.00
Received By btrobaug Date 2002-11-19 Time 17:15 Sent To B
Notes
2002-10-31 00:00:00TO CONN BOARD #48./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-30 Cont ID  
Sent By dpalmer Date 2002-10-30 Time 07:38 Rev Time 0.00
Received By dpalmer Date 2002-10-29 Time 07:38 Sent To M
Notes
2002-10-30 00:00:00SUBMITTALS

Review Stop M MECHANICAL (A/C)
Rev No 30 Status P Date 2003-04-30 Cont ID  
Sent By pkrauss Date 2003-04-30 Time 14:56 Rev Time 0.25
Received By pkrauss Date 2003-04-30 Time 14:56 Sent To  
Notes
2003-04-30 00:00:00SUBMITTAL FOR PLENUM RATED WRAP FOR
 ELEC "SMURF" IN PLENUM

Review Stop M MECHANICAL (A/C)
Rev No 29 Status P Date 2003-04-30 Cont ID  
Sent By pkrauss Date 2003-04-30 Time 10:09 Rev Time 0.30
Received By pkrauss Date 2003-04-30 Time 10:09 Sent To  
Notes
2003-04-30 00:00:00REVISION/AS BUILT EMERGENCY GENERATOR
 EXHAUST & FIRE PUMP EXHAUST

Review Stop M MECHANICAL (A/C)
Rev No 28 Status P Date 2003-04-23 Cont ID  
Sent By pkrauss Date 2003-04-23 Time 15:36 Rev Time 0.50
Received By pkrauss Date 2003-04-23 Time 15:35 Sent To  
Notes
2003-04-23 00:00:00PROVISO:
  
 DUCTS PENETRATING FIRE RATED WALLS OR
 PARTITIONS ARE REQUIRED TO HAVE FIRE
 DAMPERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 27 Status N Date 2003-04-09 Cont ID  
Sent By pkrauss Date 2003-04-09 Time 15:43 Rev Time 0.40
Received By pkrauss Date 2003-04-09 Time 15:43 Sent To  
Notes
2003-04-09 00:00:00PROVIDE THE FOLLOWING INFORMATION:
  
 1.WHAT IS BEING STORED IN THE "POOL
 STORAGE" & "POOL EQUIPMENT" ROOMS.
  
 2.CLARIFY WERE THE EXHAUST LOUVER
 WILL BE DISCHARGING THE AIR FROM THESE
 ROOMS (IN THE GARAGE, WALKWAY OR TO THE
 OUTSIDE).
  
 3.DOES THIS ROOM HAVE A FIRE RATING?
  
 4.SUBMITTAL FOR SUPPLY FAN SF-3 (ROOM
 #?) - WHAT IS THIS ROOM TO BE USED FOR?
 IS THIS ROOM FIRE RATED? PLEASE NOTE
 FIRE DAMPER IS INDICATED ON DUCT RUNNING
 THROUGH THIS SPACE.

Review Stop M MECHANICAL (A/C)
Rev No 26 Status P Date 2003-04-03 Cont ID  
Sent By pkrauss Date 2003-04-03 Time 14:52 Rev Time 0.40
Received By pkrauss Date 2003-04-03 Time 14:52 Sent To  
Notes
2003-04-03 00:00:00REVISION-RELIEF DAMPER FOR STAIRWELL
 PRESSURIZATION.

Review Stop M MECHANICAL (A/C)
Rev No 25 Status F Date 2003-03-19 Cont ID  
Sent By pkrauss Date 2003-03-19 Time 07:22 Rev Time 0.35
Received By pkrauss Date 2003-03-19 Time 07:21 Sent To  
Notes
2003-03-19 00:00:00DENIED:MECHANICAL PERMIT 01050618
  
 PLEASE CLARIFY HOW THIS DESIGN WILL
 WORK SHOULD THE OWNER CLOSE-IN THE
 BALCONY OR COVER THE LOUVER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 24 Status F Date 2003-03-31 Cont ID  
Sent By pkrauss Date 2003-02-26 Time 10:18 Rev Time 2.00
Received By pkrauss Date 2003-02-26 Time 10:18 Sent To  
Notes
2003-02-26 00:00:00AS PER CONVERSATION WITH JERRY INGRAM,
 WADSWORTH ENG.CEILING CHANGES TO LOBBY
 AREA DICTATED DIFFUSER LOCATION CHANGES.
 ALL AREAS. (PLAN SHEET M2.0.0 & M2.0.1
  
 1.REVISIONS ARE NOT CLOUDED.NOTE ON
 DENIED:PLAN SHEET M2.0.0 & M2.0.1
  
 PLAN DOES NOT INDICATE THE SPECIFIC
 REVISION MADE.NOTE ON PLAN INDICATES
 REVISION #22 BUT FAILS TO CLOUD THE
 ACTUAL CHANGE.
  
 REVISION FOR PLAN SHEET M3.1.3, M4.3.1,
 & M4.4.1 ARE APPROVED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 23 Status P Date 2003-01-27 Cont ID  
Sent By pkrauss Date 2003-01-27 Time 09:03 Rev Time 0.45
Received By pkrauss Date 2003-01-27 Time 09:03 Sent To  
Notes
2003-01-27 00:00:00MECHANICAL PERMIT 01050618
 REVISIONS FOR UNITS #804 904 & 1103.
 RETURN AIR REVISIONS.

Review Stop M MECHANICAL (A/C)
Rev No 22 Status P Date 2003-01-08 Cont ID  
Sent By pkrauss Date 2003-01-07 Time 15:26 Rev Time 0.50
Received By pkrauss Date 2003-01-07 Time 14:40 Sent To  
Notes
2003-01-07 00:00:00MECHANICAL PERMIT 01050618
 UNIT #601
 PLEASE NOTE PLAN SHEET P3 (P.0.0.5) GAS
 FOR RANGE, TWO-SIDED FIRE PLACE & DRYER,
 PROVIDE CALCULATIONINDICATING IF
 LAUNDRY ROOM IS CLASSIFIED AS A CONFINED
 OR UNCONFINED SPACE.(COMBUSTION AIR).
 PROVIDE MANUFACTURER SUBMITTAL DATA
 ON THE TWO-SIDED FIRE PLACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 21 Status P Date 2002-12-19 Cont ID  
Sent By dpalmer Date 2002-12-24 Time 10:18 Rev Time 0.30
Received By pkrauss Date 2002-12-19 Time 16:25 Sent To  
Notes
2002-12-19 00:00:00MECH PERMIT 01050618
 MECH REV PLAN SHEET M3.1.1, DUCTWORK IN
 GRAND SALON, DINING RM, LIBRARY, BAR &
 FOYER.

Review Stop M MECHANICAL (A/C)
Rev No 20 Status P Date 2002-12-06 Cont ID  
Sent By pkrauss Date 2002-12-06 Time 12:16 Rev Time 0.25
Received By pkrauss Date 2002-12-06 Time 12:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 19 Status F Date 2002-10-31 Cont ID  
Sent By pkrauss Date 2002-10-31 Time 09:30 Rev Time 1.00
Received By pkrauss Date 2002-10-31 Time 09:29 Sent To  
Notes
2002-10-31 00:00:00DENIED:
  
 UNIT 702 "B" MODEL - REVISIONS ARE NOT
 IDENTIFIED BY CLOUDS OR TRIANGLES OR
 NUMBERED AS TO THE LATEST REVION.THE
 PLAN SHEET SUBMITTED IS IDENTIFIED AS
 M1, THIS IS NOT PROPER PLAN SHEET
 IDENTIFICATION NUMBER FOR THIS UNIT.
 PLEASE CORRELATE REVISION SHEETS TO THE
 ORIGINAL APPROVED SET OF PLANS TO HELP
 EXPEDITE THE PLAN REVIEW PROCESS.
  
 THE ABOVE COMMENTS ALSO PERTAIN TO UNITS
 703, 704 & 904.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 18 Status F Date 2002-08-29 Cont ID  
Sent By dpalmer Date 2002-10-30 Time 07:38 Rev Time 1.00
Received By ndenmark Date 2002-08-29 Time 09:09 Sent To  
Notes
2002-08-29 00:00:00REVISION DENIED
 SHOP DRAWING UNACCEPTABLE FOR REVSION
 PROVIDE SIGNED AND SEALED DRAWINGS
 CLEARLY INDICATING CHANGES TO RETURN
 AIR OPENINGS, INCLUDING SIZES OF
 OPENINGS.

Review Stop M MECHANICAL (A/C)
Rev No 17 Status F Date 2002-08-22 Cont ID  
Sent By pkrauss Date 2002-08-22 Time 15:21 Rev Time 0.20
Received By pkrauss Date 2002-08-22 Time 15:21 Sent To  
Notes
2002-08-22 00:00:00PLEASE INDICATE ALL REVISIONS BY CLOUDS
 & TRIANGLES.INDENTIFY REVISION NUMBER
 & DATE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 16 Status F Date 2002-08-20 Cont ID  
Sent By ndenmark Date 2002-08-20 Time 14:00 Rev Time 0.25
Received By ndenmark Date 2002-08-20 Time 14:00 Sent To  
Notes
2002-08-20 00:00:00NEEDS TO BE RAISED SEAL AND SIGNED BY
 THE DESIGNER OF RECORD

Review Stop M MECHANICAL (A/C)
Rev No 15 Status N Date 2002-08-01 Cont ID  
Sent By pkrauss Date 2002-08-01 Time 09:13 Rev Time 0.25
Received By pkrauss Date 2002-08-01 Time 09:13 Sent To  
Notes
2002-08-01 00:00:00PLEASE IDENTIFY CHANGES ON PLAN.
 (REVISION TO APT 301)

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date 2002-06-10 Cont ID  
Sent By pkrauss Date 2002-06-10 Time 12:52 Rev Time 0.45
Received By pkrauss Date 2002-06-10 Time 12:44 Sent To  
Notes
2002-06-10 00:00:00REVISION #12

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2002-06-10 Cont ID  
Sent By pkrauss Date 2002-06-10 Time 11:05 Rev Time 1.00
Received By pkrauss Date 2002-06-10 Time 09:23 Sent To  
Notes
2002-06-10 00:00:00REVISION #9

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2002-05-20 Cont ID  
Sent By pkrauss Date 2002-05-20 Time 10:02 Rev Time 0.35
Received By pkrauss Date 2002-05-20 Time 10:02 Sent To  
Notes
2002-05-20 00:00:00MECHANICAL PERMIT 01050618
  
 REVISION PAGES M.1.1.1 & M.1.1.2.

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2002-05-14 Cont ID  
Sent By pkrauss Date 2002-05-14 Time 15:19 Rev Time 2.00
Received By pkrauss Date 2002-05-14 Time 12:35 Sent To  
Notes
2002-05-14 00:00:00PROVISO:
  
 PVC OR CPVC CANNOT BE USED IN THE RETURN
 AIR PLENUM AS PER 1997 SMC 609.1.1.
  
 CPVC IS NOT APPROVED FOR CONDENSATE AS
 PER 1997 SMC 304.8.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2002-05-02 Cont ID  
Sent By pkrauss Date 2002-05-02 Time 14:11 Rev Time 0.40
Received By pkrauss Date 2002-05-02 Time 09:37 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2001-11-08 Cont ID  
Sent By pkrauss Date 2001-11-08 Time 12:41 Rev Time 0.40
Received By pkrauss Date 2001-11-08 Time 12:35 Sent To  
Notes
2001-11-08 00:00:00INSTALLED HP-01-L TO TELE/ELEC RM # GA05
 CONTROLLED BY A HUMIDISTAT.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2001-11-01 Cont ID  
Sent By pkrauss Date 2001-11-01 Time 16:00 Rev Time 0.40
Received By pkrauss Date 2001-11-01 Time 16:00 Sent To  
Notes
2001-11-01 00:00:00*******************PROVISO**************
  
  
 REFERENCE LETTER DATED 10-10-01 2B.
 STAIR PRESSURIZATION SYSTEMS TEST
 CRITERIA, TEST TO BE WITNESSED BY (IN
 ADDITION TO ENGINEER) MECHANICAL AND
 FIRE DEPT. INSPECTOR AND A CERTIFIED
 TEST AND BALANCE COMPANY.
  
 TEST CRITERIA FOR SMOKE EVAC SYSTEM HAS
 NOT BEEN SUBMITTED FOR REVIEW.PLEASE
 SUBMIT PRIOR TO FINAL INSPECTION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2001-09-21 Cont ID  
Sent By pkrauss Date 2001-09-21 Time 10:42 Rev Time 0.45
Received By pkrauss Date 2001-09-21 Time 10:42 Sent To  
Notes
2001-09-21 00:00:00******************PROVISO***************
  
  
 1.SUBMITTAL OF VENTILATION OF PRIVATE
 PARKING GARAGE SPACES DOES NOT ADDRESS
 AN EMERGENCY POWER SEQUENCE.PLEASE
 PROVIDE APPROPRIATE PLANS TO COMPLY
 WITH ELECTRICAL, FIRE AND MECHCANICAL
 FOR EMERGENCY POWER SITUATION. (SUBMIT
 PRIOR TO ROUGH INSPECTION OF GARAGE.)
  
  
 2.SEQUENCE OF OPERATION & TEST CRITERIA
 AS NOT BEEN SUBMITTED FOR REVIEW.
 (SUBMIT PRIOR FINAL INSPECTIONS.)
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2001-08-31 Cont ID  
Sent By ndenmark Date 2001-08-31 Time 13:32 Rev Time 0.33
Received By ndenmark Date 2001-08-31 Time 13:32 Sent To  
Notes
2001-08-31 00:00:00REVISION # 3 SHOWS 10 FOOT SEPARATION
 FROM STAIR PRESSURIZATION FAN AND
 EXHAUST FANS.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-08-10 Cont ID  
Sent By pkrauss Date 2001-08-10 Time 16:41 Rev Time 0.35
Received By pkrauss Date 2001-08-10 Time 16:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-08-10 Cont ID  
Sent By pkrauss Date 2001-08-10 Time 16:03 Rev Time 4.00
Received By pkrauss Date 2001-08-10 Time 07:05 Sent To  
Notes
2001-08-10 00:00:00******************PROVISO***************
  
  
 1.PLEASE ADD NOTE TO HEAT PUMP
 SCHEDULE THAT HEAT PUMPS IN "PRIVATE
 GARAGE"SHALL BE CONTROLLED BY
 A HUMIDISTAT NOT A THERMOSTAT.
  
 2.ALL CALCULATIONS SUBMITTED BY
 WADSWORTH ENGINEERING MUST BE
 SEALED, SIGNED AND DATED.
  
 3.PLEASE SUBMIT TEST CRITERIA FOR
 STAIRWELL PRESSURIZATION.
  
 4.PLEASE PROVIDE DETIAL SHOWING
 COMPLIANCE WITH 1997 SMC 405, AIR
 INTAKE SHALL NOT BE LOCATED CLOSER
 THAN 10' FROM ANY SANITARY VENT
 UNLESS SUCH OUTLET IS 24" ABOVE AIR
 INTAKE.SHOULD EXHAUST AND SUPPLY
 NOT HAVE THIS DISTANCE SEF-7 SHALL
 INTERLOCK TO SHUTDOWN UPON
 ACTIVATION OF SSF-1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2001-07-03 Cont ID  
Sent By pkrauss Date 2001-07-02 Time 13:01 Rev Time 4.30
Received By pkrauss Date 2001-07-02 Time 09:51 Sent To  
Notes
2001-07-02 00:00:00 
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
  
 PLEASE PROVIDE SEQUENCE OF OPERATION AS
 WELL AS TEST CRITERIA FOR SMOKE EVAQ.
  
 ENG COMMENTS 6 & 7 POOL HEATERS & FLUE
 VENTS HAVE BEEN ADDED ON DWG M.1.1.1,
 NO SUCH DWG.
  
 MISSING DWGS M.0.0.3, 0.0.4, M.1.1.1, M.
 1.1.4, M.2.0.1, M.2.1.1, M.2.1.2, M.4.1.
 2, M.4.2.1, M.4.3.1.
  
 PLEASE PROVIDE MANUFACTURER DATA FOR
 THE GENERATOR.
  
 NO DETAILS/PLANS FOR COMMON AREAS SUCH A
 AS SPA, LOBBY, MANAGERS OFFICE, BILLIARD
 RM, BOARD RM AND FITNESS RM.
  
 PLEASE PROVIDE A DETAIL FOR SYMBOLS USED
 ON MECHANICAL PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-05-18 Cont ID  
Sent By pkrauss Date 2001-05-18 Time 13:11 Rev Time 5.30
Received By pkrauss Date 2001-05-18 Time 08:41 Sent To  
Notes
2001-05-18 00:00:00*******************DENIED***************
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS
 COMMON/ASSEMBLY AREAS IN BUILDING.
 (AS PER ASHRAE 62-89)
  
 2.PROVIDE AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2.
  
 3.PLEASE SHOW COMPLIANCE WITH FLORIDA
 ENERGY CODE FOR BUILDING CON-
 STRUCTION SECTION 101.5.8, #1 - FOR
 CONDITIONED PARKING GARAGES.
  
 4.DRYER SHAFTS HAVE LIMITED CLEAN
 OUTS, HOW IS COMBUSTIBLE LINT
 REMOVED FROM DRYER SHAFTS.
  
 5.THE GAS METER PROVIDED FOR PLAN
 REVIEW, HAS NO UL OR FM APPROVAL
 ON MANUFACTURE SUBMITTAL DATA.
  
 5.NO CUT SHEETS PROVIDED FOR GAS
 FIREPLACES OR THE APPARTMENT
 KITCHEN HOODS.PROVIDE INFORMATION
 ON FLUE PIPE (CONSTRUCTION, SIZE
 AND TERMINATION).
  
 6.PLEASE EXPLAIN DISCREPANCY BETWEEN
 AIRWAY ROOM PLANS.AIRWAY ON
 "A" DRAWINGS INDICATES A DOOR AND
 "M" DRAWINGS NO DOOR IS DEPICTED.
  
 7.PROVIDE STAIRWELL PRESSURIZATION
 CALCULATIONS.
  
 8.PLEASE PROVIDE INFORMATION ON THE
 "FAN ROOMS"ON THE ROOF.
  
 9.PROVIDE INFORMATION ON "SHAFT
 GRILLE ABOVE" LOCATED IN THE
 GARAGE.
  
 10.PLEASE PROVIDE CALCULATIONS FOR
 VENTILATION IN PARKING GARAGE, SHOW
 COMPLIANCE WITH 1997 SBC 411.4.2.
  
  
 NOTE:NO COMBUSTIBLES ABOVE CEILING IF
 USED AS RETURN AIR PLENUM.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-30 Cont ID  
Sent By pkrauss Date 2001-03-30 Time 15:33 Rev Time 6.00
Received By pkrauss Date 2001-03-30 Time 15:33 Sent To  
Notes
2001-03-30 00:00:00*****************DENIED*****************
  
 1.PLEASE PROVIDE INFORMATION ON
 VENTILATION FOR GARAGE AREA AS PER
 1997 SBC 411.4.2.
  
 2.PLEASE PROVIDE DETAILS ON SHAFTS:
 WHERE THEY TERMINATE ON ROOF,
 DETAILS OF PENETRATION AND CURB.
 DETAILS AND LOCATIONS OF ACCESS
 DOORS IN SHAFT.
  
 3.PLEASE PROVIDE DETAILS FOR GAS
 FIREPLACE, GAS LINE AND FLUE.
  
 4.PLEASE PROVIDE DETAILS FOR DRYER
 VENTS.
  
 5.PROVIDE MANUFACTURE DETAILS OF
 KITCHEN HOOD.
  
 6.NO COMBUSTIBLES ABOVE CEILING IN
 RETURN AIR PLENUM.

Review Stop P PLUMBING
Rev No 26 Status P Date 2003-05-12 Cont ID  
Sent By pschmitz Date 2003-05-12 Time 08:37 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2003-05-12 00:00:00REVISION, PORTE COCHERE O/F SCUPPERS.

Review Stop P PLUMBING
Rev No 25 Status P Date 2003-05-12 Cont ID  
Sent By pschmitz Date 2003-05-12 Time 08:04 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2003-05-12 00:00:00REVISION, FOUNTAIN EQUIPMENT RM RELIEF
 VENT.PES

Review Stop P PLUMBING
Rev No 24 Status P Date 2003-04-26 Cont ID  
Sent By kstevens Date 2003-04-26 Time 13:06 Rev Time 0.33
Received By kstevens Date 2003-04-26 Time 13:06 Sent To  
Notes
2003-04-26 00:00:00REVISION OK - LOCATION OF NEW SCUPPERS
 ONLY - NO REFERENCE TO CODE COMPLIANCE.

Review Stop P PLUMBING
Rev No 23 Status F Date 2003-04-22 Cont ID  
Sent By kstevens Date 2003-04-22 Time 15:08 Rev Time 2.00
Received By kstevens Date 2003-04-22 Time 15:08 Sent To  
Notes
2003-04-22 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) RELIEF VENT REQUIRED PER SEC 905.7.1
 (2)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 22 Status P Date 2003-04-14 Cont ID  
Sent By kstevens Date 2003-04-14 Time 17:22 Rev Time 0.50
Received By kstevens Date 2003-04-14 Time 17:22 Sent To  
Notes
2003-04-14 00:00:00REVISION OK - ADD SCUPPER - DELETE ROOF
 DRAINS FROM ELEVATOR MACH. ROOM, PITCH
 ROOF AND ADD 2 NEW ROOF DRAINS AND 2 NEW
 SCUPPERS AT LOW END OF ROOF

Review Stop P PLUMBING
Rev No 21 Status F Date 2003-04-08 Cont ID  
Sent By kstevens Date 2003-04-08 Time 09:02 Rev Time 0.33
Received By kstevens Date 2003-04-08 Time 09:02 Sent To  
Notes
2003-04-08 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 BUILDING
  
 1) REVISION STATES THAT DRAINS & EMER-
 GENCY OVERFLOW DRAINS ARE VERTICAL, BUT
 DRAWINGS INDICATE THAT THE DRAINS & OVER
 FLOWS ARE HORIZONTAL. PLEASE CLAIRFY.
 INDICATE TYPE OF MATERIAL AND SLOPE OF
 PIPE.
 2) DETAILS SUBMITTED WITH REVISION DO
 NOT INDICATE HEIGHT ABOVE ROOF TO THE
 INLET FLOW LINE AS REQUIRED IN SECTION
 1503.4.2. ALSO SHOW DETAIL FOR ROOF
 DRAIN INSTALLED SHOWING ALL REQUIRED
 MEASUREMENTS.
 3) ALL DETAILS SHALL BE SIGNED & SEALED
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 20 Status F Date 2003-04-04 Cont ID  
Sent By kstevens Date 2003-04-04 Time 18:02 Rev Time 1.00
Received By kstevens Date 2003-04-04 Time 18:02 Sent To  
Notes
2003-04-04 00:00:00DENIED
 REFERENCE: SPC-94-SBC-97
  
 1) FROM PREVIOUS REVIEW, SUBMIT A DETAIL
 TO SHOW COMPLIANCE WITH 1517.6.4.3. THE
 DETAILS SUBMITTED ARE NOT SIGNED AND
 SEALED AND SHOW NO DIMENTIONS. HOW IS
 THE PIPE SEALED WHERE IT PASSES THRU THE
 VERTICAL WALL?
 2) PLEASE NOTE YOUR REPLY 2(A) INDICATES
 A VERTICAL OVERFLOW, NOT A SCUPPER, BUT
 2(C) INDICATES 1/8" PER FOOT SLOPE. ALSO
 THE DIFINITION OF A SCUPPER ID AN OPEN-
 ING IN A WALL OR PARAPET THAT ALLOWS
 WATER TO DRAIN FROM A ROOF WHICH IS WHAT
 THE REVISION INDICATES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 19 Status P Date 2003-04-04 Cont ID  
Sent By kstevens Date 2003-04-04 Time 17:59 Rev Time 0.50
Received By kstevens Date 2003-04-04 Time 17:37 Sent To  
Notes
2003-04-04 00:00:00REVISION OK - REVISE FLOOR DRAIN & PIP-
 ING FOR MECH ROOM. SHT P306

Review Stop P PLUMBING
Rev No 18 Status F Date 2003-04-03 Cont ID  
Sent By kstevens Date 2003-04-03 Time 11:34 Rev Time 0.75
Received By kstevens Date 2003-04-03 Time 11:29 Sent To  
Notes
2003-04-03 00:00:00REVISION - DENIED
  
 PLEASE PROVIDE DETAIL TO SHOW COMPLIANCE
 WITH SECTION 1517.6.4.3 ALSO SHOW TYPE
 OF MATERIAL, SLOPE OF PIPE AND INDICATE
 AREA OF ROOF TO BE DRAINED BY SCUPPER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 17 Status P Date 2003-03-25 Cont ID  
Sent By kstevens Date 2003-03-25 Time 10:23 Rev Time 0.33
Received By kstevens Date 2003-03-25 Time 10:23 Sent To  
Notes
2003-03-25 00:00:00SUBMITTAL OK - GAS FIREPLACE FOR UNIT
 #601 - NEED REVISION RESUBMITTED UNDER
 GAS PERMIT NUMBER

Review Stop P PLUMBING
Rev No 16 Status P Date 2003-03-06 Cont ID  
Sent By kstevens Date 2003-03-06 Time 10:11 Rev Time 1.33
Received By kstevens Date 2003-03-06 Time 10:11 Sent To  
Notes
2003-03-06 00:00:00REVISION OK - SHEETS P.2.0.2 & P.2.0.5
 TO COMMON AREA LOBBY FLOOR

Review Stop P PLUMBING
Rev No 15 Status P Date 2003-03-06 Cont ID  
Sent By kstevens Date 2003-03-06 Time 07:33 Rev Time 1.00
Received By kstevens Date 2003-03-06 Time 08:43 Sent To  
Notes
2003-03-06 00:00:00REVISION OK - BUTLER PANTRY CHANGES -
 DELETE BAR SINK - MOVE SANT. RISER -
 SHEETS P.9.0.1 - P.9.0.2 - P.9.0.3 AND
 P.9.0.4 UNITS "G"

Review Stop P PLUMBING
Rev No 14 Status P Date 2003-03-06 Cont ID  
Sent By kstevens Date 2003-03-06 Time 07:36 Rev Time 0.60
Received By kstevens Date 2003-03-05 Time 17:56 Sent To  
Notes
2003-03-06 00:00:00REVISION OK - CHANGE BATHROOM LAYOUTS -
 ADD/DELETE BAR SINKS - SHEETS P.8.0.2 &
 P.8.0.4 - 15TH FLOOR PENTHOUSE

Review Stop P PLUMBING
Rev No 13 Status P Date 2003-03-05 Cont ID  
Sent By kstevens Date 2003-03-05 Time 17:47 Rev Time 0.33
Received By kstevens Date 2003-03-05 Time 17:39 Sent To  
Notes
2003-03-05 00:00:00REVISION OK - UNIT 1204 - SHTS P.6.0.3
 & P.6.0.5 - DELETE SINK AND ALL PIPING

Review Stop P PLUMBING
Rev No 12 Status P Date 2003-01-22 Cont ID  
Sent By kstevens Date 2003-01-22 Time 09:48 Rev Time 0.50
Received By kstevens Date 2003-01-22 Time 09:48 Sent To  
Notes
2003-01-22 00:00:00SUBMITTAL OK - TYPICAL FLOOR PLAN FOR
 WATER SUPPLY - CPVC PIPE & FITTINGS

Review Stop P PLUMBING
Rev No 11 Status P Date 2003-01-11 Cont ID  
Sent By kstevens Date 2003-01-11 Time 14:12 Rev Time 1.50
Received By kstevens Date 2003-01-11 Time 14:12 Sent To  
Notes
2003-01-11 00:00:00REVISION OK - SECONDARY DRAINS ON MECH.
 ROOFS - SCUPPERS ON BALCONYS - REMOVE
 DRAINS FROM ONE BALCONY

Review Stop P PLUMBING
Rev No 10 Status P Date 2002-12-20 Cont ID  
Sent By kstevens Date 2002-12-20 Time 15:46 Rev Time 1.00
Received By kstevens Date 2002-12-20 Time 15:46 Sent To  
Notes
2002-12-20 00:00:00REVISION OK ADD ROOF DRAIN FOR ROOF
 EQUIPMENT ROOM. ADDED PIPING.

Review Stop P PLUMBING
Rev No 9 Status P Date 2002-12-20 Cont ID  
Sent By kstevens Date 2002-12-20 Time 13:41 Rev Time 1.50
Received By kstevens Date 2002-12-20 Time 13:43 Sent To  
Notes
2002-12-20 00:00:00REVISIONS OK - SANT. AND WATER FOR UNITS
 SHTS P6.0.2 & P6.0.5
 603, 604, 804, 1003, & 1004

Review Stop P PLUMBING
Rev No 8 Status P Date 2002-12-20 Cont ID  
Sent By kstevens Date 2002-12-20 Time 10:57 Rev Time 2.50
Received By kstevens Date 2002-12-20 Time 10:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 7 Status F Date 2002-06-27 Cont ID  
Sent By kstevens Date 2002-06-27 Time 13:15 Rev Time 0.00
Received By kstevens Date 2002-06-27 Time 13:15 Sent To  
Notes
2002-06-27 00:00:00REVISION/DENIED
 REFERENCE: SPC-94
  
 1) SHT P.2.0.2 PORTE COCHERE ROOF DRAINS
 (3) DRAINING INTO 4" HORIZONTAL STORM
 DRAIN. HORIZONTAL STORM DRAIN NOT SIZED
 CORRECTLY.
 2) SHT P.2.0.5 PLEASE PROVIDE MANUF.
 INSTALLATION INSTRUCTIONS FOR REMOTE
 CHILLER (CONDENSER) IN CEILING FOR E.W.C
 (LETTER FROM WADSWORTH - O'NEAL RECIEVED
 REQUESTING INFORMATION FROM MANUF.)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 6 Status P Date 2002-06-08 Cont ID  
Sent By kstevens Date 2002-06-08 Time 05:57 Rev Time 0.00
Received By kstevens Date 2002-06-08 Time 05:57 Sent To  
Notes
2002-06-08 00:00:00REVISION OK - C/O BASE OF STACK DETAIL
 SHT P.0.0.1 - (PER SEC 307.2)

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-11-10 Cont ID  
Sent By pkrauss Date 2002-05-02 Time 14:14 Rev Time 0.33
Received By kstevens Date 2001-11-10 Time 10:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-11-10 Cont ID  
Sent By kstevens Date 2001-11-10 Time 09:24 Rev Time 3.00
Received By kstevens Date 2001-11-10 Time 09:23 Sent To  
Notes
2001-11-10 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
 RE: SUBMITTALS
  
 1) SPECIFICATION(S) 15120P.2.05A AIR
 CHAMBERS NOT APPROVED AS SUBMITTED.
 SUBMIT INFORMATION ON ACCESS PANELS AND
 SHOW COMPLIANCE WITH WH-PDI 201, SHOW
 HOW AIR CHAMBERS WILL BE RECHARGEALBE.
 SPC SEC 607.8.3
 2) SPECIFICATIONS(S) 15160P, 15160P.2.01
 AND 15160P.2.04, SHOW LISTING FOR EACH
 PUMP SUBMITTED.
 3) PLEASE PROVIDE NSF APPROVAL FOR ALL
 VALVES.
 4) EXPANSION TANK MANUFACTURE SHEETS AND
 APPROVAL REQUIRED.
 5) MORE INFORMATION REQUIRED FOR HEAT
 EXCHANGER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-08-08 Cont ID  
Sent By pschmitz Date 2001-08-08 Time 08:50 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-08-08 00:00:00PLUMBING PLAN REVIEW, PROVISO.
  
 SEPERATE PERMIT REQUIRED FOR GAS.
  
 GAS PERMIT APPLICATION REQUIRMENTS
 PREVIOUS COMMENTS DATED 03-25-01 NOTE #8
 SEE ATTACHED PLEASE ADDRESS EACH ITEM.
  
 BELOW IS ADDITONAL NOTES
 (1A) LOCATION OF GAS METER FOR BOILERS.
 (1B) THE RESIDENTAL GASPIPING SHALL BE
 DESIGNED PER MANUFACTURE MANUAL, SPECIFY
 SERIES OR PARALLEL PIPING ARRANGEMENT.
 (1C) CUT SHEETS FOR ALL COMPONENTS OF
 THE SYSTEM, WITH PIPE SIZING TABEL.
 THE ABOVE INFORMATION IS REQUIRED BEFORE
 A GAS PIPING PERMIT IS ISSUED.
 STANDARD GAS CODE-97 SEC 104.3 PLANS.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS 561-659-8096X8233

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-06-24 Cont ID  
Sent By kstevens Date 2001-06-24 Time 11:53 Rev Time 4.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-24 00:00:00REVIEW OF PLUMBING COMMENTS 06-06-01
 FROM ARCHITECTURAL GROUP
 (1A) SEE CIVIL DRAWINGS
 (1B) DOCKS ARE STILL REFERENCED ON
 ARCHITCURAL DRAWINGS.
 (1C) FLORIDA PUBLIC UTILITIES TO FURNISH
 GAS PIPING PLAN UP TO POINT OF SERVICE.
 CONTACT MR DAVID PELLICO 561-838-1752
 (2A) SHT P.0.0.1 ALL ABBREVATIONS ON
 PLANS NOT LISTED.
 (2B) SHT P.0.01 DETAIL, ELEVATOR NOT
 DELETED.
 (3) SHT P.1.0.1 CAR WASH INTERCEPTOR
 DRAIN HAS NOT BEEN CORRECTED, CONNECT TO
 SANITARY SEWER.
 (4) SHTS FOR DOMESTIC WATER PLANS HAVE
 NOT BEEN CORRECTED, A MAXIMUM OF 2 PLBG
 FIXTURES ON 1/2" C/W AND 4 ON 1/2" H/W.
 (6) CUT SHT SUBMITTALS TO BE REVIEWED BY
 ARCHITECT PRIOR TO PLUMBING REVIEW.
 (7A) SHT P.1.0.2 BUILDING SANITARY DRAIN
 NOT APPROVED, USE SPC 94 TAB 714.1 SIZE
 (7B) SHT P.2.0.5 DOMESTIC WATER PLAN,
 USE TAB 607,MINIMUM SIZE OF PLBG FIXTURE
 SUPPLY, HOT AND COLD WATER, 1/2".
 (7C) SHT P.2.0.5 LOBBY WATER FEATURE
 POOL, WATER SUPPLY, BACK FLOW PREVENTER
 REQUIRED, SEC 606.
 (8) SHT P.0.0.1, GAS PIPING BEYOND METER
 NOT ADDRESSED,SEE GAS PERMIT APPLICATION
 REQUIRMENTS, ATTACHED. SEC 104.3
 (9,10) SHT P.3.0.6 ROOF DRAINS, SCUPPER
 DRAINS, USE DESIGN CRITERIA,SPC 94 CH 11
 TAB 1108.1,1108.2,1108.3 FIG.1108.4,
 SECONDARY DRAINS 1109 (SCUPPERS) FIG.
 1109.3 RAINFALL RATES.
 APPENDIX "A", TAB A101.2 SIZING TAB.
 SEC 104.3 ISOMETRIC DRWG, SHOW ALL CALCU
 LATIONS,VERTIAL WALLS, UPPER ROOFS.
 (11) FAIR HOUSING ACT REV 98, OPTION "B"
 USED,SHOW LAYOUT OF GRAB BAR REQUIRMENT
 FOR ALL FIXTURES AS REQUIRED.
 ONE OF EACH TYPE OF FIXTURE MUST BE
 USEABLE IN OPTION 'B",BIDET IS INCLUDED.
 (12) SOVENT SYSTEM, AS/ YOUR COMMENT.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-03-25 Cont ID  
Sent By pschmitz Date 2001-03-25 Time 11:45 Rev Time 8.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-03-25 00:00:00PLUMBING PLAN REVIEWDENIED
 CODE REFERENCE SPC 94,SGC 97.
 (1A)SHT C-4 ALL SITE WATER,SANITARY
 SEWER TO COMPLY WITH CITY OF W PALM BCH.
 UTILITY STDS.
 (B) DOMESTIC WATER TO DOCK,BACK FLOW
 PREVENTER REQ. SEC. 606
 (C)SHOW LOCATION OF GAS SERVICE & METER.
 (2A)SHT P001 PROVIDE A COMPLETE LIST OF
 ALL ABBREVATIONS USED ON PLBG PLANS.
 (B) ELEVATOR SUMP,SHOW DISCHARGE TERMIN-
 ATION, IF HYDURALIC,OIL INTERCEPTOR REQ,
 WITH AN INDIRECT WASTE CONNECTION.
 (C) PLANS DO NOT INCLUDE SHTS POO2,P103,
 P203,P204,P404,P504,P604,P703,P803,P903.
 (3) SHT P101 CAR WASH,SEC 1004.6 SAND
 INTERCEPTOR REQ.
 (4) SHT P103 COMPLY WITH SEC 607 WATER
 SUPPLY SIZING, SHOW CALCULATIONS FOR
 SIZING THE DEMAND LOAD FOR THE ENTIRE
 SYSTEM, BASED ON DFU.
 (5) SEC 104.2.4 STRUCTURAL AND FIRE
 RESISTANCE INTEGRITY. UL LISTING FOR ALL
 RATED FLOOR,WALL PENETRATIONS.
 (6) SEC 104.2 SUBMITALS FOR ALL MATERIAL
 AND SPECIFICATIONS.
 (7) SEC 104.2 DRAWINGS:PROVIDE ISOMETRIC
 DRAWINGS FOR WATER & DRAIN WASTE,VENT
 SYSTEM, DWV SHOW SIZING CALCULATIONS.
 (8) SEC 104.2 PROVIDE A GAS ISOMETRIC,
 SEE ATTACHED REQUIRMENTS FOR GAS PERMIT
 DRAWINGS & APPLICATION.
 (9) SHT P306 ROOF & SCUPPER DRAINS SEC.
 1109.1 & APPEX "A",SEC 1108.3 VERTIAL
 WALLS,SHOW AREA DRAINED IN SQUARE FEET
 PLUS 1/2 THE VERTICAL AREA OF WALLS &
 PARAPETS,ISOMETRIC DRAWING OF SYSTEM.
 (10) SEC 1109 SECONDARYROOF DRAINS:
 PROVIDE CALCULATIONS FOR SIZING,LOCATION
 OF THE SECONDARY DRAINS.
 (11) ALL KITCHENS & BATH ROOMS SHALL
 COMPLY WITH THE U S DEPT OF HOUSING AND
 URBAN DEVELOPMENT (HUD) FAIR HOUSING ACT
 REGULATIONS,24 CODE OF FEDERAL REGULAT-
 IONS (CFR) 100.205 (C) (3) (IV).
 REQUIRMENT#7 PARAGRAPH 2. DESIGNATE
 WHICH DESIGN SPECIFICATION IS BEING USED
 A OR B OF THE FAIR HOUSING ACT.
 SHOW DETAILS,AS ILLUSTRATED IN THE
 FAIR HOUSING ACT DESIGN MANUAL.
 END OF COMMENTS QUESTIONS CONTACT
 PAUL SCHMITZ 561-659-8096 X 8233

Review Stop Z ZONING
Rev No 2 Status P Date 2001-08-15 Cont ID  
Sent By sgraham Date 2001-08-15 Time 11:37 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2001-06-04 Cont ID  
Sent By sgraham Date 2001-06-04 Time 10:38 Rev Time 0.50
Received By sgraham Date   Time   Sent To  
Notes
2001-06-04 00:00:00SITE PLAN MUST BE AAMENDED