| Plan Review Stops For Permit 01030147 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
18 |
Status |
F |
Date |
2003-04-14 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-05 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-04-14 00:00:00 | REVISIONS DATED 1/14/03 SHEETS A.4.16.1 | | | AND A 5.1.24. GUARDHOUSE DOORS. | | | | | | SBC 1012.1.2-97 REQUIRES EXIT DOORS TO | | | BE SIDE SWINGING.PLEASE REVISE AS | | | NECESSARY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
17 |
Status |
F |
Date |
2003-04-14 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-04-14 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-04-14 00:00:00 | ENTRANCE DOOR COMPARATIVE ANALYSIS | | | LOCATION L 055. | | | | | | FBC 1707.4.2 REQUIRES TESTING AND | | | LABELING OF WINDOWS AND DOORS. | | | | | | A SEPARATE PERMIT IS REQUIRED FOR | | | WINDOWS AND DOORS NOT INCLUDED WITH THE | | | ORIGINAL PERMIT APPLICATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
16 |
Status |
F |
Date |
2003-04-14 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-04-14 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-04-14 00:00:00 | RE: FIFTEENTH FLOOR FRENCH DOOR PRODUCT | | | APPROVALS. | | | | | | A SEPARATE PERMIT AND FEES ARE REQUIRED | | | FOR WINDOWS, DOORS, ETC. SUBMITTED | | | SUBSEQUENT TO THE PRIME PERMIT BEING | | | ISSUED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
15 |
Status |
F |
Date |
2003-03-19 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-11 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-03-19 00:00:00 | SHEET S5, REVISIONS 2 THROUGH 6, | | | ENGINEER'S SIGNATURE DATE 3/14/03. | | | | | | SHEET S5 OF THE CITY PERMIT SET SHOWS | | | REVISON #1 DATED 5/2/01.THIS SHEET | | | SHOWS REVISIONS NUMBERED UP TO #6 DATED | | | 5/2/02.WHAT ARE THE OTHER REVISIONS | | | AND WHY ARE THEY BEING PROVIDED NEARLY | | | A YEAR LATER AND SUBSEQUENT TO THE WORK | | | BEING ACCOMPLISHED? | | | | | | WHAT IS THE DIMENSION OF THE NEW AREA | | | SHOWN AS #6?WHAT WILL THE FUNCTION | | | AND USE BE?WHERE ARE THE SUPPORTING | | | ARCHITECTURAL PLANS?CHANGES TO THE | | | EXTERIOR ARE SUBJECT TO PRIOR REVIEW BY | | | THE PLANNING DEPARTMENT. | | | | | | IT APPEARS THIS WORK PROVIDES ADDED | | | VALUE TO THE BUILDING AND IS SUBJECT TO | | | ADDITIONAL PERMIT FEES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
14 |
Status |
F |
Date |
2003-03-07 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-17 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-03-07 00:00:00 | ROOFING SUBMITTALS DATED 2/8/02 WEST | | | COAST ROOFING. PERMIT #01050621 | | | | | | THE SITE SPECIFIC ENGINEERING DATED | | | 8/13/01 IS NOT SIGNED AND SEALED, DOES | | | NOT CONTAIN AN INVESTIGATION OF THE | | | "DENS DECK," AND HAS NOT BEEN REVIEWED | | | BY THE ENGINEER OF RECORD. | | | | | | THE SBCCI REPORT 9822A IS NOT CURRENT. | | | | | | THE SITE SPECIFIC ENGINEERING REFERENCES | | | THE CURRENT FBC.SEE FBC 1609.4.3 RE: | | | LOAD REDUCTION AND ALLOWABEL STRESS | | | INCREASES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
13 |
Status |
P |
Date |
2003-02-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-20 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-02-27 00:00:00 | REVISION 8 DATED 11/11/02 FOR PH UNIT G, | | | ARCHITECTURAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
12 |
Status |
F |
Date |
2003-01-16 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-01-16 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-01-16 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2003-01-16 00:00:00 | REVISIONS DATED 12/13/02 MARKED SK1 AND | | | RE: A.4.3.1. | | | | | | PROVIDE A FIRE DESIGN NUMBER FOR THE | | | TWO HR RATED CEILING ON THE STAIR | | | CONNECTOR TO DEMONSTRATE COMPLIANCE | | | WITH FBC 704.2.1.2. | | | | | | SK3 DATED 11/26/2000 "NEW DETAIL" | | | EMERGENCY OVERFLOW SCUPPER.WHAT | | | VOLUME OF WATER IS ANTICIPATED TO FLOW | | | THROUGH THE UNDEFINED FIBERGLASS SCREEN | | | AREA? | | | | | | SK4 DATED 11/26/2000 AND NOTED A.4.12.1 | | | AND SK5 DATED 11/26/2000 AND NOTED | | | A.4.15.1.THE CHANGE FROM ROOF AREA TO | | | BALCONY REQUIRES ADDITIONAL DETAILS FOR | | | THE ALUM GUARD RAIL, FLOOR SURFACE TO BE | | | USED, AND COMPLIANCE WITH THE FAIR | | | HOUSING ACT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
P |
Date |
2002-12-18 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-12-18 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-12-18 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2002-12-18 00:00:00 | REVISIONS 604, 804, 1003, 1004, 603 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
P |
Date |
2002-12-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-16 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-12-10 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2002-12-10 00:00:00 | REVISION #7 DATED 9/2/02 SHEETS 4.7.1, 4 | | | .7.2, & 4.7.3. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2002-11-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-25 |
Time |
17:58 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-11-19 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2002-11-19 00:00:00 | UNIT 803 CITY DATE 11/19/02 4.9.1,2,3 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2002-10-30 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-30 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-30 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2002-10-30 00:00:00 | REVISIONS DATED 10/11/02 FOR UNITS 704, | | | 703, 702 AND 904. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2002-03-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-21 |
Time |
12:49 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-21 00:00:00 | | | | WINDOW AND DOOR SUBMITTAL | | | | | | 1] | | | SUBMIT TEST REPORT AND SPECS FOR THE | | | 2400ST SLIDING GLASS DOORS. | | | ALSO FOR 345PO OPERABLE WINDOW. | | | | | | 2] | | | SHEET 28 AND 29 CALLS FOR DOOR WITH | | | GLAZING, REPORT SUBMITTED HAS SOLID | | | STEEL. | | | | | | 3] | | | ONLY SUBMITTED 2SETS, ALL SUBMITTALS | | | SHALL BE IN THREES. | | | | | | 4] | | | ALL SHOP DRAWINGS SHALL BE REVIEWED AND | | | SIGNED BY DESIGNER OF RECORD. | | | | | | 5] | | | PROVIDE - AND + PRESSURES FOR ALL | | | OPENINGS ON ELEVATIONS, SIGNED AND | | | SEALED BY DESIGNER OF RECORD. | | | | | | | | | L. MARTINEZ | | | 659-8096 | | | #8456 | | | WINDOW AND DOOR SUBMITTAL APPROVED | | | L. MARTINEZ | | | 659 8096 | | | #8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2001-09-21 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-09-21 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2001-09-20 |
Time |
16:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2001-08-29 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-29 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-29 00:00:00 | RE: INFORMATION INCLUDED WITH | | | TRANSMITTAL LETTER DATED 8/28/01 BCBE | | | CONSTRUCTION FROM STUART FALKNOR AND | | | THESTH LETTER DATED 8/13/01 TITLED | | | "THIRD | | | PLAN REVIEW" COMMENTS. | | | | | | TILE ROOF ASSEMBLY NOA 99-1102.04 IS FOR | | | A WOOD DECK ASSEMBLY. TESTING IS | | | REQUIRED FOR THE "DENS DECK" | | | APPLICATION IF THAT IS THE INTENDED | | | PURPOSE OF THE CATALOG SHEET COPIES | | | PROVIDED. | | | | | | THE GAF NOA 00-0331.10 IS MISSING THE | | | PAGES CONTAINING THE DESIGN WIND | | | PRESSURE AND THE LIMITATIONS. | | | | | | THE ABOVE ITEMS CAN BE PROVISIONALLY | | | ACCEPTED. | | | | | | NEW SHEET A.2.2.1 CITES 1999 STANDARD | | | BUILDING CODE.AS STATED IN THE | | | EARLIER REVIEW COMMENTS, THE CITY | | | CURRENTLY INVOKES THE 1997 EDITION. | | | | | | THE STH RESPONSE TO ITEM #6 "THE | | | CALCULATED GARAGE AREA FOR EXHAUSTING | | | DOES NOT INCLUDED THE PRIVATE GARAGES, | | | AS THEY ARE CONDITIONED SPACES." IS OK | | | AS LONG IT IS DEMONSTRATED THAT THE | | | "CONDITIONED AIR" IS EXCHANGED AT THE | | | RATE OF AT LEAST SIX TIMES PER HOUR IN | | | ACCORDANCE WITH SBC 411.4.2,1997. | | | | | | THE SPECIFICATION SHEETS PROVIDED HAVE | | | CONFUSING WIND DESIGN INFORMATION AND | | | SPECIFICATION 08520 FIXED ALUMINUM | | | WINDOWS, DOES NOT ADDRESS HURRICANE | | | MISSILE IMPACT RESISTANCE.THE WIND | | | PRESSURES ARE THOSE SET OUT IN THE WIND | | | TUNNEL TESTING THAT THE BUILDING WAS | | | DESIGNED TO.THE MISSILE IMPACT | | | TESTING MUST MEET SSTD 12-97 OR HAVE A | | | CURRENT DADE COUNTY ACCEPTANCE REPORT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-08-15 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-15 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-15 00:00:00 | SEE PREVIOUS CHECKLIST DATED 7/17/01. | | | | | | THE NOTICE OF ACCEPTANCE REPORT | | | #99-0204.07 FOR THE WINDOW WALL SYSTEM | | | DOES NOT HAVE THE COMPONENTS MARKED OR | | | THEIR LOCATIONS TO BE INSTALLED IN THE | | | BUILDING. | | | | | | NOA 99-0505.08 DOORS IS NOT MARKED. | | | | | | NOA 01-0129.09 STEEL DOOR.SAME. | | | | | | NO CHANGE TO SPECIFICATION RE: WIND | | | DESIGN REQUIREMENTS. | | | | | | PRESSURIZED STAIR CALCULATIONS UNCHANGED | | | GARAGE SMOKE REMOVAL RE: VOLUME AND | | | PRIVATE GARAGES NOT ADDRESSED FROM | | | PREVIOUS CHECKIST. | | | | | | IN SUMMARY.DEMONSTRATE COMPLIANCE WITH | | | SBC 412.6 #5 FOR THE STAIRS.SBC | | | 412.5#3 FOR THE ELEVATOR LOBBY AREA. | | | PROVIDE CURRENT TEST REPORTS FOR THE | | | DOORS, WINDOWS, AND ROOF COVERINGS | | | TOGETHER WITH THE INFORMATION REQUIRED | | | THAT IS CONTAINED WITHIN THOSE REPORTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-07-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-07-17 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-17 00:00:00 | THE PRODUCT TEST REPORTS FOR THE ROOF | | | COVERING, WINDOWS AND DOORS HAVE NOT | | | BEEN PROVIDED.THE SPECIFICATIONS FOR | | | THE WINDOWS AND STOREFRONT SYSTEM CALL | | | A 110 | | | MPH WINDLOAD DESIGN.THIS MUST BE | | | CORRECTED TO REFLECT THE RESULTS OF | | | THE WIND TUNNEL TESTING.AT NO TIME WAS | | | THIS BUILDING CONSIDERED IN A 110 MPH | | | WIND ZONE FOR DESIGN PURPOSES. | | | NOTE 4 UNDER CODES AND STANDARDS | | | CALLS FOR HAND AND GUARD | | | RAILS TO BE DESIGNED TO 1608.2.THE | | | CODE SECTIONS ARE NOT A SUBSTITUTE FOR | | | SPECIFIC INFORMATION.SEE SBC 104.2. | | | | | | THE STAIR PRESSURE CALCULATIONS ARE NOT | | | SIGNED AND SEALED.FURTHER THE | | | CALCULATIONS DO NOT CLEARLY INDICATE | | | HOW THE BAROMETRIC RELIEF VENTS WILL | | | PROVIDE THE 2500 CFM FLOW AS REQUIRED | | | BY SBC 412.11 #5 PLEASE CLARIFY AND | | | REVISE AS NECESSARY. | | | | | | SHEET M.5.0.1 SHOWS THE STAIR | | | PRESSURIZATION FANS IN CLOSE PROXIMITY | | | TO THE LOBBY AND OTHER EXHAUST FANS. | | | | | | HOW WILL THE CALCULATED GARAGE EXHAUST | | | ACCOMMODATE THE "PRIVATE AIR | | | CONDITIONED GARAGES WITH THEIR DOORS | | | CLOSED? | | | | | | THE ARCHITECT PLANS SHEET A.1.1.1 CALL | | | OUT A 14' CEILING HEIGHT AND 698080 SF | | | IN AREA.THE WADSWORTH CALCULATIONS | | | NOTE AN 11' CEILING HEIGHT AND 53017 SF | | | FLOOR AREA.PLEASE JUSTIFY THE | | | DIFFERENCES.NOTE TOO, ALL INFORMATION | | | PREPARED BY AN ARCHITECT OR AN ENGINEER | | | AND SUBMITTED FOR PUBLIC RECORD, ARE | | | REQUIRED TO HAVE THE EMBOSSED SEAL, | | | SIGNATURE AND DATE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-05-29 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-05-29 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-29 00:00:00 | PLEASE PROVIDE A RECENT PROPERTY SURVEY | | | | | | SHOW HOW HURRICANE MISSILE IMPACT | | | RESISTANCE FOR THE GLAZED EXTERIOR | | | PORTIONS WILL BE ACCOMPLISHED. | | | | | | THE PLANS MUST HAVE THE IMPACT FEE STAMP | | | ON THEM. | | | | | | PROVIDE TEST DATA FOR THE WINDOWS, DOORS | | | AND ROOF COVERING. | | | | | | UNIT TYPES E AND G DO NOT COMPLY WITH | | | SBC 1004.1.4 | | | | | | ENTRY VESTIBULES E32 AND G40 DO NOT | | | COMPLY WITH THE ELEVATOR LOBBY | | | SEPARATION REQUIERMENTS OF SBC 412.6. | | | | | | THE USE OF WOOD WITHIN THE CONSTRUCTION | | | OF TYPE I & II BUILDINGS IS REQUIED TO | | | BE FIRE RETARDANT TREATED. | | | | | | CITING A CODE SECTION IS NOT ACCEPTABLE | | | IN LIEU OF SPECIFIC DESIGN INFORMATION | | | WITH REGARDS TO THE HAND AND GUARD | | | RAILS. | | | | | | SHOW HOW DAMP PROOFING WILL BE | | | ACCOMPLISHED ON THE WEST SIDE OF THE | | | GARAGE.SEESBC 1814.3. | | | | | | THE DESIGNERS RESPONSES TO THE FIRST | | | CHECKLIST WERE REVIEWED AND THESE ARE | | | THE SUBSEQUENT FINDINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-04-05 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-04-05 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2001-03-30 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2001-04-05 00:00:00 | 1 THIS BUILDING WILL BE IN AN FLOOD | | | ZONE A5 WITH A 7.0' BFE | | | 2THIS WILL BE A THRESHOLD BUILDING AND | | | REQUIRES AN THRESHOLD INSPECTION PLAN | | | AND INSPECTOR.CONTACT DON NEELY FOR | | | ADDITIONAL INFORMATION659-8096 X 8333. | | | 3PLEASE PROVIDE A RECNT PROPERTY | | | SURVEY WITH THE PERMIT APPLICATION. | | | 4SHOW HOW THE GLAZED PORTIONS OF THE | | | BLDG WILL COMPLY WITH THE CITY'S | | | HURRICANE MISSILE IMPACT ORDINANCE. | | | 5IMPACT FEES MUST BE PAID TO THE | | | COUNTY BEFORE A PERMIT CAN BE ISSUED. | | | CALL 233-5025 FOR MORE INFORMATION. | | | 6AT TIME OF PERMIT APPLICATION PROVIDE | | | TEST DATA - PRODUCT APPROVALS FOR THE | | | DOORS WINDOWS AND ROOF COVERING.SEE | | | SBC 104.2. | | | 7RESIDENTIAL UNIT TYPES A AND D HAVE | | | TRAVEL DISTANCES > 75' AND MUST COMPLY | | | WITH SBC 1004.1.4 AND SBC 1004.1.2. | | | 8THE EXIT STAIR LAYOUT DOES NOT COMPLY | | | WITH SBC 1004.1.4. | | | 9SBC 412.6.2 REQUIRES AT LEAST ONE | | | EXIT ACCESS WITHOUT TRAVEL THROUGH AN | | | ELEVATOR LOBBY. | | | 10THE EXIT DISCHARGE FOR THE NORTH | | | HALF OF THE STAIRS DOES NOT COMPLY WITH | | | SBC 1010. | | | 11 PROVIDE COPIES OF THE SOIL AND WIND | | | TUNNEL REPORTS. | | | 12SPECIFY FIRE RETARDANT LUMBER ON | | | SHEET A6 AND AS NECESSARY THROUGHOUT. | | | 13SHEET S7 DOES NOT SHOW DESIGN LOADS | | | FO CORRIDORS OR PUBLIC ROOMS AND THE | | | LOBBIES ARE SHOWN AS 40 PSF.SEE SBC | | | 1604.1. | | | 14LATERAL SOIL PRESSURE IS NOT SHOWN | | | IN THE DESIGN LOADS FOR THE GARAGE. | | | SEE SBC 1608.1. | | | 15SHOW THE DESIGN LOADS FOR THE | | | VARIOUS RAILINGS.SEE SBC 1608.2 | | | 16WATER PROOFING OR DAMP PROOFING | | | MEASURES ARE NOT SHOWN FOR THE PORTIONS | | | OF THE GARAGE BELOW GRADE.SBC 1814. | | | 17SHOW THE LOCATION OF THE RELIEF | | | VENTS IN THE STAIRS AND THE | | | CALCULATIONS AND OPERATION TO MAINTAIN | | | THE 2500CFM REQUIRED BY SBC 412.11 #5. | | | OR COMPLY WITH SBC 1005.6. | | | 18HOW WILL SMOKE CONTROL FOR THE | | | WINDOWLESS ROOMS BE PROVIDED?SBC | | | 412.5. | | | 19SHOW THE VENTILATION FOR THE GARAGE. | | | SBC 411.4.2. | | | 20ELECTRICAL PANELS E17A AND E17B BOTH | | | SHOW NORTH STAIRS FANS.THE MECHA | | | PLANS SHOW 5 HP AND THE LEEC PLANS SHOW | | | 10 HP FANS.PLEASE CLARIFY. | | | 21SHOW THE EMERGENCY ROOF DRAIN | | | OVERFLOW METHOD.SBC 1517.6.4.3. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
33 |
Status |
P |
Date |
2003-05-08 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-05 |
Time |
14:01 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-05-08 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2003-05-08 00:00:00 | SUBMITTAL/ CERTIFICATIONLETTER FOR | | | EM GEN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
32 |
Status |
P |
Date |
2003-05-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-05-07 |
Time |
14:48 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-05-07 |
Time |
14:48 |
Sent To |
P |
|
| Notes |
| 2003-05-07 00:00:00 | REV FOR WATERFALL EQUIPMENT RM. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
31 |
Status |
P |
Date |
2003-04-22 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-05 |
Time |
10:27 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-04-22 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2003-04-22 00:00:00 | REV FO RUNIT #1001 OK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
30 |
Status |
P |
Date |
2003-04-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-04-22 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-04-22 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2003-04-22 00:00:00 | REV OK FOR UNIT #803 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
29 |
Status |
P |
Date |
2003-04-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-04-22 |
Time |
15:46 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-04-22 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2003-04-22 00:00:00 | REV OK, FOR UNTI #301 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
28 |
Status |
P |
Date |
2003-04-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-04-22 |
Time |
15:42 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-04-22 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2003-04-22 00:00:00 | ELECTRICAL RISER REV,FOR 400A DISC`S |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
27 |
Status |
P |
Date |
2003-04-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-04-22 |
Time |
15:42 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-04-22 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2003-04-22 00:00:00 | OK, LOBBY EQUIPMENT RM REV . |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
26 |
Status |
P |
Date |
2003-04-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-04-22 |
Time |
13:36 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-04-22 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2003-04-22 00:00:00 | REV FOR UNIT #1204 OK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
25 |
Status |
P |
Date |
2003-04-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-04-22 |
Time |
12:56 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2003-04-22 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2003-04-22 00:00:00 | UNIT # 603 | | | REDLINED RECEPT FOR 210-52 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
24 |
Status |
P |
Date |
2003-03-18 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-18 |
Time |
15:15 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-03-18 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2003-03-18 00:00:00 | ****** POOL EQUIPMENT ROOM ************ |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
23 |
Status |
F |
Date |
2003-02-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-26 |
Time |
18:14 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-02-26 |
Time |
18:13 |
Sent To |
|
|
| Notes |
| 2003-02-26 00:00:00 | *************** UNSAT ************** | | | | | | UNIT G/FIRST FLOOR/PENTHOUSE | | | | | | 1)NOTE: PLEASE CORRELATE LOADS ON G1, | | | W/ LOADS ON G2, G3. | | | | | | 2)NOTE: PLEASE SEE MAX LOAD ON 15A/#14 | | | 1440. PLEASE SEE SOME SHOWN OVER. | | | PLEASE CLARIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
22 |
Status |
F |
Date |
2003-02-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-26 |
Time |
17:37 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-02-26 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2003-02-26 00:00:00 | **************** UNSAT ************* | | | PH-3 | | | 1)NOTE: PLEASE SEE PANEL SCHEDULE FOR | | | F1, PLEASE CORRELATE LOADS FOR SUB | | | PANELS F2 AND F3. | | | | | | 2)NOTE: PLEASE SEE LOADS ON 15A BRKRS | | | LOADS EXCEED 80%, PLEASE CLARIFY IF | | | LOADS THAT ARE ON 20A CIRCUITS, SHOWN AS | | | 1440 ARE SWITCHED WITH 15A CIRCUTIS?? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IFTHERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
21 |
Status |
F |
Date |
2003-02-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-26 |
Time |
16:03 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-02-26 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2003-02-26 00:00:00 | ********** UNSAT *************** | | | UNIT 1204 | | | 1)NOTE: PLEASE SEE LOADS SHOWN ON 15A | | | BRKRS. LOADS EXCEED 80%. | | | | | | 2)NOTE: PLEASE SEE LOADS ON PANEL "A" | | | FEEDING SUB PANEL. PLEASE CORRELATE. | | | | | | 3)NOTE: PLEASE SEE RECEPT AT MASTER | | | BATH SINK LOCATION. MIN 3" PER 210-52D | | | | | | UNIT 1204 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
20 |
Status |
P |
Date |
2003-02-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-26 |
Time |
16:02 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-02-26 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2003-02-26 00:00:00 | REV FOR LOBBY /LOWER LEVEL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
19 |
Status |
F |
Date |
2003-02-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-18 |
Time |
07:17 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2003-02-18 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2003-02-18 00:00:00 | ************** UNSAT *************** | | | | | | PLANS HAVE BEEN SUBMITTED FOR FINAL | | | "AS-BUILT" REVISED DRAWINGS, PLEASE | | | SEE THE FOLLOWING NOTES. | | | | | | 1)NOTE: PLEASE SEE UNIT 301, EQUIPMENT | | | GROUNDING CONDUCTOR SHOWN AS ALUM. | | | AS PER LOCAL AMENDMENTS, 310-2 ALUM | | | SHALL NOT BE USED FOR GROUNDING. PLEASE | | | NOTE, ALL OTHER UNITS ARE SHOWN AS CU. | | | | | | 2)NOTE: PLEASE SEE UNIT #803, PLEASE | | | SEE LOADS SHOWN ON 15A BRKRS. MAX VA | | | ON 15A IS 1440. (80%) THIS HAS BEEN | | | CORRECTED ON ALL OF THE OTHER SHEETS | | | SUBMITTED. | | | | | | | | | 3)NOTE: PLEASE SEE LOADS THAT DO NOT | | | CORRELATE. MAIN PANELS SHOW ONE LOAD | | | AND SUB PANELS SHOW DIFFERENT LOAD. | | | UNIT 1001,603, PH-3. | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
18 |
Status |
P |
Date |
2003-02-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-14 |
Time |
05:51 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-02-14 |
Time |
05:51 |
Sent To |
|
|
| Notes |
| 2003-02-14 00:00:00 | REV FOR CONDUITS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
17 |
Status |
P |
Date |
2003-02-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-06 |
Time |
19:07 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-02-06 |
Time |
19:07 |
Sent To |
|
|
| Notes |
| 2003-02-06 00:00:00 | UNIT #804 ONLY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
16 |
Status |
P |
Date |
2003-01-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-14 |
Time |
07:01 |
Rev Time |
6.00 |
| Received By |
dpalmer |
Date |
2003-01-14 |
Time |
07:01 |
Sent To |
|
|
| Notes |
| 2003-01-14 00:00:00 | NOTES TO FOLLOW. | | | ********** NOTES/PROVISO *********** | | | | | | BEFORE MARCH 1ST, 2003 | | | | | | PLEASE NOTE, THESE ARE MOSTLY THE SAME | | | NOTES FOR ALL OF THE FOLLOWING UNITS. | | | PLEASE NOTE SOME UNITS MAY BE DIFFERENT | | | DUE TO MODEL AND OWNER CHANGES. | | | | | | 1)NOTE: PLEASE CORRELATE ALL LOAD | | | CALCULATIONS AND PANEL SCHEDULES PER | | | UNIT. PLEASE SEE LOADS SHOWN ON | | | SUB-PANELS, THESE DO NOT CORRELATE WITH | | | MAIN PANEL LOAD SCHEDULE. | | | | | | 2)NOTE: PLEASE NOTE SOME UNITS APPEAR TO | | | HAVE RECEPTS MORE THAN 3' FROM SINKS, | | | PER 210-52D. | | | | | | 3)NOTE: PLEASE ALSO NOTE SOME UNITS ARE | | | MISSING OUTLETS IN ORDER TO MEET 210-52. | | | | | | 4)NOTE: PLEASE NOTE, ORIG PLANS WERE | | | SUBMITTED FOR MOSTLY GAS APPL/DRYERS, | | | DUE TO MANY CHANGES IN LOADS TO UNIT | | | PLANS. PLEASE RECONFIGURE LOAD CALCULAT- | | | IONS FOR BLDG SERVICE AND SUBMIT REVISED | | | PLAN. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE 03/01/03. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | UNITS, 603,604,804,1003,1004, | | | 704,904 702,703 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
15 |
Status |
F |
Date |
2003-01-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-07 |
Time |
08:30 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-01-07 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2003-01-07 00:00:00 | ************* UNSAT ***************** | | | 6TH FLR UNIT 601 REV. | | | | | | 1)NOTE: PLEASE SEE OVERLOADING OF | | | CIRCUITS IN PANEL. | | | PLEASE BREAK DOWN LOAD CALACULATIONS | | | TO SEE IF 200AQ PANEL IS ADEQUATE FOR | | | UNIT. LOAD IS SHOWN AT OVER 345 A'S??? | | | | | | PLEASE SUBMITTHE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
14 |
Status |
F |
Date |
2002-12-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-27 |
Time |
12:06 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-12-27 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2002-12-27 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE REVISED PANEL SCHED. | | | LOAD EXCEEDS RATING OF EQUIPMENT.PLEASE | | | ALSO NOTE, LOAD CALCS NEED TO CORRELATE | | | TO ART 220 OFTHE NEC. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
13 |
Status |
F |
Date |
2002-12-16 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2002-12-16 |
Time |
08:58 |
Rev Time |
4.30 |
| Received By |
jleahy |
Date |
2002-12-16 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2002-12-16 00:00:00 | UNIT 603PANEL C2#4,8 OVERLOADED | | | | | | UNIT 604PANEL D2#6 OVERLOADED | | | SUB POANEL LOADS DO NOT MATCH | | | LOAD SHOWN IN MAIN PANEL | | | | | | UNIT804CIRCUIT #6 OVERLOADED | | | | | | UNIT 1003CIRCUIT 4,8OVERLOADED | | | | | | UNIT 1004CIRCUIT 6 OVERLOADED | | | | | | ALSO NEED TO SUPPLY CUT SHEET FOR FIXTUR | | | RA-600LM/RA-AD |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
12 |
Status |
F |
Date |
2002-12-16 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2002-12-16 |
Time |
08:52 |
Rev Time |
4.00 |
| Received By |
jleahy |
Date |
2002-12-13 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2002-12-13 00:00:00 | UNIT 702 CIRCUIT #3 IS OVERLOADED PER | | | PLAN.LOAD ON SUB PANEL NOT THE SAME | | | WHEN PUT INTO MAIN PANEL. | | | | | | UNIT 703 SAME WITHN SUB PANEL, CIRCUIT | | | #4,8 IN C2 ARE OVERLOADED PER PLAN. | | | | | | UNIT 704 SAME WITH PANELS, CIRCUIT #6 | | | IN D2 IS OVERLOADED PER PLAN. | | | | | | UNIT 904SAME WITH PANELS, CIRCUIT #6 IS | | | OVERLOADED PER PLAN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
11 |
Status |
F |
Date |
2002-12-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-06 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-12-06 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2002-12-27 00:00:00 | SEE OTHER NOTES ON PREVIOUS REVIEWS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
10 |
Status |
F |
Date |
2002-08-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-08-07 |
Time |
06:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-08-07 |
Time |
06:33 |
Sent To |
|
|
| Notes |
| 2002-08-07 00:00:00 | ************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE REVISIONS NEED TO | | | BE SHOWN AS CLOUDS OR TRIANGLES. | | | NO REV INDICATED. | | | | | | 2)NOTE: PLEASE NOTE THAT GROUNDING | | | CONDUCTOR SHOWN FEEDING PANELS SHALL NOT | | | BE ALUM. PER LOCAL AMENDMENTS. 310-2-B-2 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
F |
Date |
2002-06-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-07 |
Time |
06:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-07 |
Time |
06:24 |
Sent To |
|
|
| Notes |
| 2002-06-07 00:00:00 | ************* UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE LAST FOUR | | | REVISIONS THAT HAVE BEEN SUBMITTED HAVE | | | HAD COMMENTS AND EACH TIME ANOTHER REV | | | COMES IN, IT HAS NOTHING TO DO WITH | | | COMMENTS FROM ANY OF THE OTHER REV OR | | | COMMENTS. PLEASE NOTE THAT REV FROM | | | NOV OF 2001 ARE NOW BEING SUBMITTED.WE | | | HAVE ALREADY HAD REVS THAT WERE A LATER | | | DATE THAT HAVE ALREADY BEEN SUBMITTED?? | | | PLEASE SEE COMMENTS FROM OTHER REVIEWS | | | AND SUBMIT THOSE TO INCLUDE ALL REVISION | | | S. | | | | | | 2)NOTE: PLEASE NOTE THATSOME SHEETS | | | DO NOT INDICATE ON PANEL SCHEDULES OF | | | THE REV MADE? PLEASE NOTE E.3.1.3,E.2.1. | | | 1,E.4.1.3. | | | | | | 3)NOTE: PLEASE ALSO NOTE THAT TWO DIFFER | | | -ENT SETS AND ROLLS WERE SUBMITTED AND | | | ONLY REV FEES FOR ONE ROLL WERE ADDED. | | | PLEASE NOTE THERE ARE ADDTIONAL FEES DUE | | | | | | PLEASE SUBMIT UP-DATED REVISIONS, AND | | | ADDRESS COMMENTS FROM THIS REVIEW AND | | | ALL PREVIOUS REVIEWS THAT HAVE STILL NOT | | | BEEN ADDRESSED. ONCE AGAIN,,,,IF THERE | | | ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
F |
Date |
2002-05-07 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-07 |
Time |
19:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-07 |
Time |
18:36 |
Sent To |
|
|
| Notes |
| 2002-05-07 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT A NOTE FROM | | | PREVIOUS TWO REVIEWS HAS NOT BEEN | | | ADDRESSED AND STILLS SHOWS UP ON PLANS?? | | | PLEASE NOTE IF PLANS ARE SUBMITTED FOR | | | THE THIRD TIME FOR THE SAME COMMENTS | | | AND THEY ARE NOT ADDRESS, UNDER 553-80 | | | OF THE FS/FAC, PLANS CAN BE SUBJECT TO | | | A 4X THE PLAN REVIEW/REVISION FEE. | | | PLEASE NOTE THAT A PANEL SCHEDULE WAS | | | NOT SUBMITTED THIS TIME TO VERIFY THE | | | SAME CIRCUITS AS ASK FOR ON THE OTHER | | | REVIEWS. | | | | | | 2)NOTE: PLEASE NOTE THAT PLANS ARE NOW | | | BEING SUBMITTED FOR ADDING TWO NEW | | | 1600A SERVICES. PLEASE NOTE THAT ALL | | | REQ`MENTS OF 230-2 WOULD NEED TO BE MET | | | AND PLANS ARE COMPLETE ENOUGHT FOR THAT. | | | PLEASE ALSO NOTE THAT PLANS ARE SHOWING | | | NEW OVER HEAD FEEDS WHICH SHOWS MORETHAN | | | 8'FT OF UNPROTECTED CONDUCTORS INSIDE | | | THE BLDG. THIS IS NOT PERMITTED PER | | | LOCAL AMENDMENTS 230-70 | | | | | | 3)NOTE:PLEASE ALSO NOTE THAT A COMPLETE | | | 2HR SEPARATION WOULD BE NEEDED BETWEEN | | | EXISTING BLDG AND NEW ELECTRICAL ROOM | | | WITH A SEPARATE FEED FROM FPL IF A | | | SECOND SERVICE WAS PERMITTED TO THE SAME | | | BLDG. | | | | | | 4)NOTE: PLEASE NOTE GROUPING OF MAINS | | | PER 230-72. IDENTIFICATION PER 230-2E | | | | | | 5)NOTE:PLEASE NOTE THAT SERVICE ENTRANCE | | | CONDUCTORS DO NOT MEET 240-3C. 310-16 | | | 110-14C | | | | | | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2001-12-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-24 |
Time |
06:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-24 |
Time |
06:51 |
Sent To |
|
|
| Notes |
| 2001-12-24 00:00:00 | ***************** UNSAT *********** | | | | | | 1)NOTE: PLEASE NOTE THAT LIGHTNING | | | PROTECTION SYSTEM MUST BE SUBMITTED WITH | | | A SEPARATE PERMIT APPLICATION AND PLANS. | | | MUST PAY FOR PERMIT FEES ETC UNDER NEW | | | APPLICATION. | | | PLEASENOTE THAT THIS IS THE SAME | | | FROM THE LAST TIME THE LIGHTNING SUB- | | | -MITTALS WERE TURNED IN. | | | | | | PLEASE SUBMIT SEPARATELY WITH SEPARATE | | | PERMIT APPLICATION. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2001-11-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-05 |
Time |
20:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-05 |
Time |
20:10 |
Sent To |
|
|
| Notes |
| 2001-11-05 00:00:00 | **************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT OUTLETS SHOWN | | | ON E.1.2.1 ARE SHOWN AS 2-POLE AND NOTED | | | AS 208V 3-PHASE AND 30AMPS? PLEASE NOTE | | | THAT PANEL SCHEDULES SHOW AS 1-POLE | | | 20AMP OUTLETS. | | | CIRCUITS ARE SHOWN AS 2-POLE? | | | | | | PLEASE CLARIFY AND CORRECT. PLEASE | | | SUBMIT FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2001-11-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-02 |
Time |
06:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-02 |
Time |
06:49 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-08-15 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2001-08-15 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2001-08-15 |
Time |
11:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-07-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2001-07-12 |
Time |
14:10 |
Rev Time |
2.00 |
| Received By |
jleahy |
Date |
2001-07-12 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2001-07-12 00:00:00 | MISSING ALL BUT 5 PAGES NEED ALL | | | DRAWINGS FOR THE ELECTRICAL WORK!!!!! |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-05-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2001-05-30 |
Time |
10:33 |
Rev Time |
5.00 |
| Received By |
jleahy |
Date |
2001-05-30 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2001-05-30 00:00:00 | E6.1.1 SHOWS RISER WITH NO WIRE SIZES | | | AND/OR CONDUIT SIZES. | | | | | | NEED A SCHEDULE FOR MCC SIZE OF WIRES TO | | | THE DIFFERNET LOADS, SHOW SIZES OF FUSE | | | OR CIRCUIT BREAKERS TO LOADS FED BY MCC | | | | | | PLEASE SHOW HOW IN THE PENTHOUSES THAT | | | ONE METER WILL BE FEEDING THREE PANELS | | | FOR UNITS F(2), G , AND JSUBMIT RISER | | | | | | PLANS ARE GENERALY IN GOOD SHAPE BUT | | | THERISER DIAGRAM IS VERY CONFUSING, A | | | ONE | | | LINE FOR THE NORMAL AND ONE FOR THE | | | EMERGENCY RISERS WOULD BE GREAT SHOWING | | | WHATFEEDS WHAT WITHOUT HAVING TO GO TO | | | SEVER | | | AL PAGES TO GET THE INFORMATION! |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-03-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-29 |
Time |
06:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-28 |
Time |
19:12 |
Sent To |
|
|
| Notes |
| 2001-03-29 00:00:00 | ****************UNSAT **************** | | | | | | 1)NOTE:PLEASE NOTE WIRE SIZE SHOWN FOR | | | "MCC" AT 500MCM AL. PLEASE SEE 75DEGREE | | | COLLUMN IN 310-16. "310A"`S | | | 2)NOTE: PLEASE NOTE THAT MANY PAGES ARE | | | NOT READABLE. PRINT IS BLURRED AND VERY | | | SMALL. MOSTLY ON SHEETS THAT GIVE YOU | | | A COMPLETE OVER VIEW OF BLDG. | | | | | | 3)NOTE:E.2.2.2 MISSING OUTLETS PER LOCAL | | | CODE. PLEASE NOTE THAT THE LOCAL CODE | | | REQ`S MIN OUTLET SPACING OF EVERY 12` IN | | | OFFICE SPACE AND EVERY 20`OF WALL SPACE | | | IN STORAGE/HALLWAY AREAS. ONLY WALLS OF | | | UNENCUMBERED SPACE. 210-50 | | | | | | 4)NOTE: PLEASE NOTE THAT THERE ARE SHEET | | | S WITH NO ELECTRICAL SHOWN.E.2.2.2, | | | E.4.1.2,E.4.1.3,E.4.2.0,E.4.2.2 ,,,,,, | | | | | | 5)NOTE: PLEASE NOTE ALL HOUSE LOADS THAT | | | ARE CONTINUOUS NEED TO BE SHOWN AT 125% | | | WHERE ARE LOADS SHOWN FOR "MCC". | | | RISER DIAGRAM IS MISSING CONDUIT/WIRE | | | SIZE FROM MCC MAIN TO MCC.? PLEASE CLARI | | | FY. | | | | | | 6)NOTE: IN ADDITION; PLEASE SHOW CONDUIT | | | AND WIRE SIZES ON LINE DIAGRAM FOR | | | RISER. WE HAVE RUN INTO MANY PROBLEMS | | | ON JOBS WHERE CONTRACTORS ARE NOT LOOKIN | | | G AT PANEL SCHEDULES FOR CONDUIT AND WIR | | | E SIZES. CONDUIT AND WIRE SIZES CAN BE S | | | HOWN AS TYPICAL FOR COMMON UNITS. | | | | | | 7)NOTE: PLEASE CLARIFY GROUNDING ELECTRO | | | DE SYSTEM.PER 250-50 | | | | | | 8)NOTE: PLEASE CLARIFY TYPE OF FUEL FOR | | | GENERATOR. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS OR | | | IF YOU WOULD LIKE A MEETING, PLEASE CALL | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2001-09-17 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-09-17 |
Time |
14:32 |
Rev Time |
3.00 |
| Received By |
mamini |
Date |
2001-09-17 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2001-09-17 00:00:00 | PASSED WITH PROVISOS: | | | | | | 1. THIS PERMIT INCLUDES ALL UNDERGROUND | | | UTILITY WORKS & PAVEMENTS ON THE | | | PROPOSED SITE.WATER CROSS CONNECTIONS | | | MUST BE DONE AFTER THE WATER MAIN DESIGN | | | IN N. FLAGLER DR. IS FINAL & APPROVED | | | BY THE PUBLIC UTILITIES ENGINEERING | | | SERVICES DEPARTMENT. | | | | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2001-05-25 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-05-25 |
Time |
15:59 |
Rev Time |
4.00 |
| Received By |
mamini |
Date |
2001-05-25 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2001-05-25 00:00:00 | FAILED: | | | 1. PLEASE REFER TO PREVIOUS REVIEW | | | COMMENTS DATED 3-8-01 AND ADDRESS ITEMS | | | 2, 11 AND 12. | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | | EXT. 8492 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-03-08 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-03-08 |
Time |
13:04 |
Rev Time |
4.00 |
| Received By |
mamini |
Date |
2001-03-08 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2001-03-07 00:00:00 | FAILED: | | | 1. THE "APPLICATION FOR COSTRUCTION | | | WITHIN PUBLIC R.O.W MUST BE SUBMITTED TO | | | CITY ENGINEERS OFFICE PRIOR TO COMMENCE- | | | MENT OF ANY WORK IN PUBLIC R.O.W. | | | 2. SUBMIT CONSTRUCTION PLANS, DETAILS, | | | SPECIFICATION, HYDRAULIC, STORM WARTER | | | CALCULATION AND ALSO SUBMIT PERVIOUS & | | | IMPERVIOUS CALCULATION ON 8 1/2 X 11 | | | SHEETS WHICH INCLUDE NAME, ADDRESS, | | | PROPERTY CONTROL NUMBER SIGNED AND | | | SEALED BY DESIGN ENGINEER TO: | | | 1000 45TH STREET SUITE # 15 | | | WEST PALM BEACH, FL 33407 | | | 3. A TRUCK WASHOUT AREA SHOULD BE ADDED | | | TO SITE PLAN AT EXITS AND MAINTAINED | | | DURING CONSTRUCTION. | | | 4. ALL BROKEN SIDEWALK, CURBS(& GUTTERS) | | | ALONG THE PROPERTY (ALL SIDES) SHOULD BE | | | REPLACED. | | | 5. ALL DRIVEWAYS THAT WILL NOT BE USED | | | MUST BE REMOVED AND REPLACED WITH | | | REGULAR CURBS (& GUTTERS). | | | 6. ALL DRIVEWAY MUST BE CONSTRUCTED PER | | | CITY OF WPB STANDARD. | | | 7. SHOW CLEAN OUT LOCATION ON SANITARY | | | SEWER LATERAL, ON THE PROPERTY AT BACK | | | OF THE SIDEWALK IF POSSIBLE. | | | 8. SHOW LOCATION OF DUMPSTER IF KNOWN. | | | 9. IF KITCHEN FACILITIES ARE PLANED, | | | THEN OIL SEPARATORS WILL NEED TO BE | | | INSTALLED TO MEET THE CITY WASTEWATER | | | DISCHARGE ORDINANCE. | | | 10. LOCATION OF METERS AND BACKFLOW | | | PREVENTERS TO BE COORDINATED WITH THE | | | CITY. | | | 11. DISCHARGE INTO THE INTERCOASTAL | | | WATER WAY SHOULD BE MAINTAINED AT PRE- | | | BUILDING RATES. | | | 12. PERMITS FROM SFWMD AND DEP MUST BE | | | OBTAINED FOR DISCHARGING INTO THE | | | INTERCOASTAL WATER WAY. | | | 13. SANITARY MANHOLES ON SHEET C4 ARE | | | LABELED SM-1 THROUGH SM-3.PROFILE FOR | | | SANITARY SEWER ON SHEET C8, THEY ARE | | | LABELED MH-1 THROUGH MH-4 AND SM-4 IS | | | MISSING ON SHEET C4, PLEASE VERIFY. | | | 14. ADD NOTES INDICATING THE REQUIRED | | | CLEARANCES FOR WATER CROSSING OVER | | | STORM OR SANITARY LINES AND IN CASE OF | | | CONFILECT. | | | 15. PROVIDE CHARTS, DETAILS FOR THRUST | | | BLOCKS. | | | 16. FOR STANDARD DETAILS CONTACT 561- | | | 659-8088 EXT. 2303 | | | 17. PROVIDE ADDITIONAL INFORMATIONS AND | | | SCHEDULES FOR REMOVAL OF EXISTING | | | CONCRETE RETAINING WALL. | | | 17. A SEPARATE PERMITS APPLICATION | | | MUST BE SUBMITTED TO CONSTRUCTION | | | SERVICES (B&Z) FOR REMOVAL OF EXISTING | | | CONCRETE RETAINIG WALL. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
16 |
Status |
P |
Date |
2003-04-22 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-04-22 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-04-22 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2003-04-22 00:00:00 | REVISION TO LOBBY WATERWALL EQUIPMENT | | | ROOM OK 04/22/03 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
15 |
Status |
P |
Date |
2003-04-10 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-04-10 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-04-10 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2003-04-10 00:00:00 | PROVISO: | | | 1) WHAT IS BEING STORED IN THE POOL | | | STORAGE AND POOL EQUIPMENT ROOMS. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
14 |
Status |
F |
Date |
2003-03-18 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-03-18 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-03-17 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2003-03-18 00:00:00 | 1) REVISION ON SHEET F.4.1.3 | | | | | | 2) SEPARATE PLAN AND PERMIT BY FIRE | | | SPRINKLER CONTRACTOR IS REQUIRED. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
13 |
Status |
F |
Date |
2003-03-17 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-03-17 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-03-17 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2003-03-17 00:00:00 | 1) REVISION FOR SHEET F.3.2.3/1204 | | | | | | 2) SEPARATE PLAN AND PERMIT BY FIRE | | | SPRINKLER CONTRACTOR IS REQUIRED. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
12 |
Status |
F |
Date |
2003-03-17 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-03-17 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-03-17 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2003-03-17 00:00:00 | 1) REVISION FOR SHEET F.4.2.2/PH3 | | | | | | 2) SEPARATE PLAN AND PERMIT BY FIRE | | | SPRINKLER CONTRACTOR IS REQUIRED. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
11 |
Status |
F |
Date |
2003-03-17 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-03-17 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-03-17 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2003-03-17 00:00:00 | 1) REVISION ON SHEETS F.2.1.1 , F.2.1.2 | | | AND F.2.1.3 | | | | | | 2) SEPARATE PLAN AND PERMIT BY SPRINKLER | | | CONTRACTOR IS REQUIRED. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
10 |
Status |
P |
Date |
2002-12-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-02-28 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-12-26 |
Time |
09:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
9 |
Status |
P |
Date |
2002-12-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-12-06 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-12-06 |
Time |
14:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
8 |
Status |
P |
Date |
2002-05-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-23 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-23 |
Time |
08:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
7 |
Status |
P |
Date |
2001-12-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-28 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-28 |
Time |
13:07 |
Sent To |
|
|
| Notes |
| 2001-12-28 00:00:00 | INSTALLATION OF TEMPORARY FIRE HYDRANT. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2001-11-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-02 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-01 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2001-11-01 00:00:00 | VARIOUS CUT SHEETS FOR REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-30 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-30 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | 1) ELECTRICAL PAGES SUBMITTED. PLEASE | | | EXPLAIN INFORMATION WITH REGARDS TO | | | PERMIT APPLICATION "GARAGE VENTILATION | | | SYSTEM". | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2001-08-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-01 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-01 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2001-08-01 00:00:00 | 1) LOCATIONS OF ILLUMINATED EXIT SIGNS | | | AND EMERGENCY LIGHTS (ADDITIONAL ONES) | | | MAY BE NECESSARY AS REQUIRED BY FIRE | | | RESCUE PERSONNEL. | | | 2) STAIRWAY PRESSURIZATION SHALL COMPLY | | | WITH NFPA 101, THE LIFE SAFETY CODE, | | | SECTION 5-2.3.9. | | | 3) ENTIRE BUILDING AND MECHANICAL, | | | ELECTRICAL, AND FIRE SYSTEMS TO COMPLY | | | WITH APPLICABLE CODES AND RECOGNIZED | | | STANDARDS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-07-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-31 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-31 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2001-07-31 00:00:00 | GENERATOR CUT SHEETS FOR DIESEL UNIT | | | PLANNED FOR ROOM. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-05-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-24 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-24 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | 1) GAS METER PRODUCT APPROVAL DISPLAYS | | | NO UL OR FM APPROVALS. | | | 2) NO PLAN REVIEW COMMENTS REGARDING GAS | | | INSTALLATION BY GAS COMPANY. | | | 3) DRYER SHAFTS NOT PROVIDED WITH ENOUGH | | | CLEAN-OUT LOCATIONS FOR THE REMOVAL | | | OF COMBUSTIBLE LINT. ONLY TWO ARE SHOWN | | | AT CHANGE OF DIRECTIONS. | | | 4) EXPLAIN DOORS AND BALCONIES. | | | 5) PLEASE PROVIDE PERCENTAGE OF OPENINGS | | | PER EXTERIOR WALLS IN PARKING GARAGE. | | | PLEASE INDICATE ON PLANS WHETHER THE | | | PARKING GARAGE IS CONSIDERED OPEN OR | | | CLOSED. | | | 6) TRASH CHUTES ARE NOT PERMITTED TO | | | OPEN INTO THE ELEVATOR EQUIPMENT ROOMS. | | | THESE CHUTES ARE TO TERMINATE INTO THE | | | OPEN AIR WITH A MINIMUM OF THREE FEET | | | ABOVE THE ROOF. PLEASE PROVIDE DETAILS | | | FOR TRASH CHUTE TERMINATIONS. | | | 7) HOW IS ACCESS PROVIDED TO GAS METER | | | AND GAS SHUT-OFF VALVE. | | | 8) PLEASE EXPLAIN HOW PRODUCTS OF | | | COMBUSTION WILL NOT ENTER THE | | | STAIRTOWERS WHERE OPENINGS ARE PRESENT | | | NEAR THE DUAL BALCONIES. THIS OFFICE | | | DOES UNDERSTAND THAT THESE MATERIALS | | | WILL RISE, BUT WHAT PREVENTS ANY | | | CONTAMINATION. | | | 9) PLEASE INDICATE WHERE THE ELEVATOR | | | LOCATED IN THE NORTHWEST CORNER OF | | | THE PROPERTY TRAVELS TO. | | | 10) PLEASE INDICATE EMERGENCY LIGHTING | | | IN GARAGE. | | | 11) PLEASE EXPLAIN GARAGE EXHAUST FANS | | | ON/OFF CONTROLS IN FIRE COMMAND ROOM. | | | 12) PLEASE EXPLAIN ELEVATOR SECURITY | | | SWITCHES. | | | 13) HOW DOES BUILDING SECURITY FEATURES | | | AFFECT EXITING. | | | 14) EXIT DOOR ON PAGE E.1.1.1 NEAR | | | GENERATOR ROOM DOES NOT SWING IN THE | | | DIRECTION OF EXIT TRAVEL. | | | 15) PLEASE NOTE ON THE PLANS THAT A | | | MINIMUM OF SIX AIR CHANGES ARE REQUIRED | | | WITHIN THE CLOSED PARKING GARAGE. GARAGE | | | VENTILATION FANS ARE TO BE PROVIDED | | | WITH EMERGENCY POWER. | | | 16) NO LITERATURE PROVIDED BY BCBE OR | | | CIVIL ENGINEERS. NO LITERATURE PROVIDED | | | FOR GAS FIREPLACES. | | | 17) PLEASE INDICATE THE WIDTH OF THE | | | OPENINGS AT THE STAIRS NEAR THE | | | BALCONIES. | | | | | | WRITER DID SPEAK TO MIKE GOTWALT AND | | | OBTAINED SOME ANSWERS TO SOME OF THESE | | | PLAN REVIEW COMMENTS HOWEVER WRITER WAS | | | NOT COMPLETED. | | | | | | PLEASE INDICATE HOW SMOKE COULD BE | | | REMOVED FROM THE CORE AREAS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-03-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-08 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-08 |
Time |
09:27 |
Sent To |
|
|
| Notes |
| 2001-03-08 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY | | | CODE REQUIREMENTS. | | | 2) PLEASE DEFINE FIRE INGRESS AND EGRESS | | | ROUTES FOR THE BUILDING. | | | 3) FUTURE DOCK CONSTRUCTION AND FIRE | | | PROTECTION FOR THEM NOT SHOWN. | | | 4) ONLY ONE FIRE DEPARTMENT CONNECTION | | | IS SHOWN ON THE DRAWING. SINCE THE | | | BUILDING IS CONSIDERED HIGH-RISE, TWO | | | FIRE DEPARTMENT CONNECTIONS ARE | | | REQUIRED. | | | 5) THE LANE AROUND THE BUILDING IS TO BE | | | A FIRE LANE WITH APPROPRIATE SIGNAGE AND | | | PAVEMENT MARKINGS. | | | 6) THE PORTACOCHERE MUST BE AT LEAST | | | 13'- 6" HIGH SO FIRE AND PARAMEDICAL | | | APPARATUS CAN PASS UNDERNEATH IT. | | | 7) ELEVATORS TO COMPLY WITH ANSI A17.1, | | | PHASE ONE AND PHASE TWO ELEVATOR RECALL. | | | ELEVATORS TO COMPLY WITH THE STRETCHER | | | REQUIREMENTS OF STANDARD BUILDING CODE, | | | SECTION 3003.4. | | | 8) SIGNS ARE REQUIRED IN THE STAIRWELLS | | | INDICATING THE STORY, THE TERMINUS OF | | | THE STAIR AT THE TOP AND BOTTOM, AND THE | | | IDENTIFICATION OF THE STAIR. | | | 9) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR THE WALLS | | | AND CEILINGS. | | | 10) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS IN THE | | | ASSEMBLY AREAS OF THE BUILDING. | | | 11) TEMPORARY STANDPIPES AND STAIRS WILL | | | BE REQUIRED DURING CONSTRUCTION. | | | 12) PLEASE PROVIDE MORE DETAILS ON THE | | | GAS METER ROOMS LOCATED ON EACH FLOOR. | | | 13) WHAT WILL THE DEAD SPACE ON PAGE | | | A.3.2.1 BE USED FOR. | | | 14) HOW IS THE GAS SHUTOFF VALVE SHOWN | | | ON PAGE P.0.0.1 "TYPICAL FUEL GAS | | | APPLIANCE PIPING DETAIL" MADE | | | ACCESSIBLE. | | | 15) NO HYDRAULIC CALCULATIONS PROVIDED | | | WITH FIRE SPRINKLER DRAWINGS. | | | 16) A KNOX-BOX RAPID ENTRY SYSTEM IS | | | REQUIRED FOR THE BUILDING. | | | 17) PLEASE PROVIDE PRODUCT LITERATURE | | | FOR THE GAS FIREPLACES. | | | 18) A TWO HOUR FIRE SEPARATION IS | | | REQUIRED BETWEEN THE PARKING GARAGE AND | | | THE BUILDING. | | | 19) A CODE SUMMARY IS REQUIRED FOR THE | | | PARKING GARAGE AND RESIDENTIAL TOWER. | | | PLEASE INDICATE TYPE OF CONSTRUCTION | | | AND CODES USED FOR DESIGN. PLEASE | | | INDICATE NUMBER OF OPENINGS FOR THE | | | PARKING GARAGE. | | | 20) ROOMS IN THE GARAGE SHALL BE | | | SEPARATED FROM THE PARKING AREAS BY | | | AT LEAST ONE HOUR. THE GENERATOR AND | | | FIRE PUMP ROOM IF DIESEL FUEL IS | | | PRESENT, MUST BE SEPARATED BY TWO HOUR | | | CONSTRUCTION. | | | 21) FIRE DAMPERS TO COMPLY WITH UL 555. | | | 22) STAIR PRESSURIZATION FANS ARE TO | | | ACTIVATE WHEN THE FIRE SPRINKLER SYSTEM | | | OR FIRE ALARM SYSTEM HAS OPERATED. | | | 23) EMERGENCY LIGHTING REQUIRED IN FIRE | | | PUMP ROOM. | | | 24) WILL THE GUARD HOUSE BE STAFFED | | | FULL TIME. | | | 25) WHAT ROUTE DOES FIRE RESCUE USE TO | | | GET TO THE UPPER LEVEL. | | | 26) THE SCISSOR STAIRS MUST BE SEPARATED | | | FROM ONE ANOTHER SINCE A SINGLE SHAFT | | | IS BEING USED TO PROVIDE TWO SEPARATE | | | EXITS FROM SINGLE AREAS. TWO HOUR FIRE | | | SEPARATIONS WILL BE REQUIRED BETWEEN THE | | | TWO SCISSOR STAIRS LOCATED IN A SINGLE | | | TWO HOUR RATED FIRE SHAFT. | | | 27) PLEASE PROVIDE INCLINE DRAWINGS TO | | | THE SECOND LEVEL WHERE THE FIRE COMMAND | | | ROOM WILL BE LOCATED. | | | 28) STAIRS TO COMPLY WITH NEW STAIR | | | REQUIREMENTS OF THE LIFE SAFETY CODE. | | | 29) HANDRAILS AND GUARDS TO COMPLY WITH | | | REQUIREMENTS OF THE LIFE SAFETY CODE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
59 |
Status |
N |
Date |
2003-06-05 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-05 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-05 |
Time |
14:01 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
58 |
Status |
N |
Date |
2003-05-20 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-20 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-20 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2003-05-20 00:00:00 | DON NEELEY DESK, SUBMITTAL LETTER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
57 |
Status |
N |
Date |
2003-05-15 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-15 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-15 |
Time |
08:57 |
Sent To |
Z |
|
| Notes |
| 2003-05-15 00:00:00 | SITE PLAN FOR LANDSCAPING |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
56 |
Status |
N |
Date |
2003-05-12 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-12 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-12 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2003-05-12 00:00:00 | DON NEELY DESK, LETTERS FOR SUBMITTAL. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
55 |
Status |
N |
Date |
2003-05-09 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-09 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-09 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2003-05-09 00:00:00 | DON NEELY DESK. ACEPTANCE LETTER SUBMITT | | | ALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
54 |
Status |
N |
Date |
2003-05-09 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-09 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-09 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2003-05-09 00:00:00 | DON NEELY DESK, TWO SUBMITTALS WITH | | | LETTERS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
53 |
Status |
N |
Date |
2003-05-07 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-07 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-07 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2003-05-07 00:00:00 | DON NEELY DESK. CERTIFICATIONS AND | | | LETTERS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
52 |
Status |
N |
Date |
2003-05-05 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-05 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-05 |
Time |
11:22 |
Sent To |
B |
|
| Notes |
| 2003-05-05 00:00:00 | SUBMITTAL LETTERS, GAVE TO MIKE SIZEMORE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
51 |
Status |
N |
Date |
2003-05-05 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-05 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-05 |
Time |
10:35 |
Sent To |
P |
|
| Notes |
| 2003-05-05 00:00:00 | 2 REV, ONE SUBMITTAL ON KS DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
50 |
Status |
N |
Date |
2003-05-05 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-05 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-05 |
Time |
10:29 |
Sent To |
FIRE |
|
| Notes |
| 2003-05-05 00:00:00 | FIRE ALARM CERT. SUBMITTAL. PLACED ON | | | FIRE CHAIR. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
49 |
Status |
N |
Date |
2003-05-05 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-05 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-05 |
Time |
10:26 |
Sent To |
E |
|
| Notes |
| 2003-05-05 00:00:00 | DP DESK. GENERATOR CERT. SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
48 |
Status |
N |
Date |
2003-05-05 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-05 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-05 |
Time |
10:23 |
Sent To |
B |
|
| Notes |
| 2003-05-05 00:00:00 | HP DESK. 2 SUBMITTALS.5/5 2 ADDT'L | | | SUBMITTALS FOR PRODUCT APPROVALS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
47 |
Status |
N |
Date |
2003-04-25 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-25 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-25 |
Time |
16:41 |
Sent To |
P |
|
| Notes |
| 2003-04-25 00:00:00 | KSTEVENS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
46 |
Status |
N |
Date |
2003-04-25 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-25 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-25 |
Time |
09:09 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
45 |
Status |
N |
Date |
2003-04-24 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-24 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-24 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2003-04-24 00:00:00 | SUBMITTAL, LETTERS TO MIKE SIZEMORE PER | | | HIS REQUEST. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
44 |
Status |
N |
Date |
2003-04-23 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-23 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-23 |
Time |
10:34 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
43 |
Status |
N |
Date |
2003-04-22 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-22 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-22 |
Time |
16:38 |
Sent To |
B |
|
| Notes |
| 2003-04-22 00:00:00 | HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
42 |
Status |
N |
Date |
2003-04-18 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-18 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-18 |
Time |
15:15 |
Sent To |
E |
|
| Notes |
| 2003-04-18 00:00:00 | DP DESK.REVISIONS FOR 6 DIFFERENT UNITS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
41 |
Status |
N |
Date |
2003-04-17 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-17 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-17 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2003-04-17 00:00:00 | COMM BOARD #9 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
40 |
Status |
N |
Date |
2003-04-17 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-17 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-17 |
Time |
11:26 |
Sent To |
B |
|
| Notes |
| 2003-04-17 00:00:00 | HP DESK | | | TWO SUBMITTALS ENCLOSED |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
39 |
Status |
N |
Date |
2003-04-14 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-14 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-14 |
Time |
16:43 |
Sent To |
B |
|
| Notes |
| 2003-04-14 00:00:00 | HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
38 |
Status |
N |
Date |
2003-04-14 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-14 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-14 |
Time |
16:42 |
Sent To |
B |
|
| Notes |
| 2003-04-14 00:00:00 | HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
37 |
Status |
N |
Date |
2003-04-11 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-11 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-11 |
Time |
13:37 |
Sent To |
B |
|
| Notes |
| 2003-04-11 00:00:00 | HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
36 |
Status |
N |
Date |
2003-04-11 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-11 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-11 |
Time |
13:37 |
Sent To |
B |
|
| Notes |
| 2003-04-11 00:00:00 | HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
35 |
Status |
N |
Date |
2003-04-11 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-11 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-11 |
Time |
13:36 |
Sent To |
B |
|
| Notes |
| 2003-04-11 00:00:00 | HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
34 |
Status |
N |
Date |
2003-04-11 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-11 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-11 |
Time |
13:35 |
Sent To |
B |
|
| Notes |
| 2003-04-11 00:00:00 | HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
33 |
Status |
N |
Date |
2003-04-11 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-11 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-11 |
Time |
13:34 |
Sent To |
B |
|
| Notes |
| 2003-04-11 00:00:00 | HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
32 |
Status |
N |
Date |
2003-04-07 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-07 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-07 |
Time |
16:09 |
Sent To |
B |
|
| Notes |
| 2003-04-07 00:00:00 | HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
31 |
Status |
N |
Date |
2003-04-04 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-04 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-04 |
Time |
15:14 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
30 |
Status |
N |
Date |
2003-04-04 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-04 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-04 |
Time |
15:09 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
29 |
Status |
N |
Date |
2003-04-03 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-03 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-03 |
Time |
16:08 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
28 |
Status |
N |
Date |
2003-04-03 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-03 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-03 |
Time |
11:10 |
Sent To |
B |
|
| Notes |
| 2003-04-03 00:00:00 | HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
27 |
Status |
N |
Date |
2003-03-31 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-03-31 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-03-31 |
Time |
15:54 |
Sent To |
B |
|
| Notes |
| 2003-03-31 00:00:00 | TO HHP./WRT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
26 |
Status |
N |
Date |
2003-03-25 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-25 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-25 |
Time |
17:03 |
Sent To |
|
|
| Notes |
| 2003-03-25 00:00:00 | SUBMITTALS | | | | | | 1.)ACCEPTANCE LETTER FOR ON SITE | | | SANITARY LINE FROM ENGINEER OF RECORD - | | | TO PLUMBING IN BOX | | | | | | 2.)ROOFING SUBMITTALS RE-SUBMITTED | | | IN RESPONSE TO HP COMMENTS - TO HP | | | DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
25 |
Status |
N |
Date |
2003-03-24 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-24 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-24 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2003-03-24 00:00:00 | 1.)MECHANICAL REVISION TO MECH BOX | | | (REVISION AT MEDIA ROOM) | | | | | | 2.)LETTER FROM STRUCTURAL ENGINEER | | | REGARDING SCUPPER HEIGHTS AT THE ROOF | | | AND THE ROOF DECK'S ABILIT TO HOLD THE | | | PROPER WATER DEPTH TO MATCH THESE | | | SCUPPER HEIGHTS - TO HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
24 |
Status |
N |
Date |
2003-03-24 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-24 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-24 |
Time |
08:17 |
Sent To |
B |
|
| Notes |
| 2003-03-24 00:00:00 | TO HP DESK | | | ENGINEERING FOR STOREFRONT ALUM AT NW | | | ELEVATOR STRUCTURE MISSING FROM ORIGINAL | | | DRAWING |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
23 |
Status |
N |
Date |
2003-03-17 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-17 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-17 |
Time |
08:51 |
Sent To |
B |
|
| Notes |
| 2003-03-17 00:00:00 | 1.) WRITTEN REQUEST FROM ARCHITECT OF | | | RECORD T REMOVE 4 UNITS FROM CO OF | | | THE NOTED PERMIT NUMBER. | | | | | | 2.) STRUCTURAL REVISION TO UNIT 15F | | | BALCONY. | | | | | | SENT TO HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
22 |
Status |
N |
Date |
2003-03-13 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-13 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-13 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2003-03-13 00:00:00 | COMM BOARD #3 - REVISIONS TO E,P,M | | | | | | 1.REVISED POOL EQUIPMENT ROOM | | | DRAWINGS | | | | | | 2.FOUNTAIN MECHANICAL ROOM ADDITION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
21 |
Status |
N |
Date |
2003-03-13 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-13 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-13 |
Time |
10:47 |
Sent To |
M |
|
| Notes |
| 2003-03-13 00:00:00 | REVISION TO CHANGE SLOT DIFFUSER | | | DIMENSIONS AT LOBBY LEVEL SOCAL ROOM | | | AND MAIN LOBBY AREA |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
20 |
Status |
N |
Date |
2003-03-13 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-13 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-13 |
Time |
10:01 |
Sent To |
P |
|
| Notes |
| 2003-03-13 00:00:00 | RESUB FOR UNIT 601 PLUMBING/GAS COMMENTS | | | FROM 1/14/03 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
19 |
Status |
N |
Date |
2003-03-13 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-13 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-13 |
Time |
09:57 |
Sent To |
B |
|
| Notes |
| 2003-03-13 00:00:00 | SUBMITTALS/REVISIONS SENT TO HP DESK: | | | | | | 1. FIRE CAULK DETAIL AT SCISSOR STAIRS | | | TO WALL | | | | | | 2.REVERSE DOOR SWING AT 04 (D-UNIT) | | | UNIT MECHANICAL ROOM | | | | | | 3.STAIR PRESSURIZATION LOUVER | | | RELOCATED BY ARCHITECT/ENGINEER | | | | | | 4.ADD RAILING/GATES TO POOL DECK PER | | | REQUEST OF NEIL MELNICK, DON NEELY, RICK | | | JONES MEETING ON 2/26/03 | | | | | | 5.DELETION OF MECHANICAL ROOM CEILING | | | AND FLOOR ISOLATION DETAIL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
18 |
Status |
N |
Date |
2003-03-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-03-05 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-03-05 |
Time |
10:52 |
Sent To |
B |
|
| Notes |
| 2003-03-05 00:00:00 | ROOFING SUBMITTALS TO HP`S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
17 |
Status |
N |
Date |
2003-03-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-03-04 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-03-04 |
Time |
08:36 |
Sent To |
B |
|
| Notes |
| 2003-03-04 00:00:00 | TO HP`S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
16 |
Status |
N |
Date |
2003-02-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-02-28 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-02-28 |
Time |
15:50 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
15 |
Status |
N |
Date |
2003-02-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-20 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-02-20 |
Time |
14:33 |
Sent To |
B |
|
| Notes |
| 2003-02-20 00:00:00 | TO HHP`S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2003-02-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-20 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-02-20 |
Time |
14:32 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2003-02-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-18 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-02-18 |
Time |
10:28 |
Sent To |
B |
|
| Notes |
| 2003-02-18 00:00:00 | SUBMITTALS TO HHP DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2003-02-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-13 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-02-13 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2003-02-13 00:00:00 | 4-ROLLS OF REV'S | | | TO #53 ON COMM BOARD. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2003-02-06 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-02-06 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-02-05 |
Time |
15:27 |
Sent To |
B |
|
| Notes |
| 2003-02-06 00:00:00 | TO HHP./WRT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2003-02-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-04 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-02-04 |
Time |
09:05 |
Sent To |
B |
|
| Notes |
| 2003-02-04 00:00:00 | TO HHP`S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2002-12-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-27 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-12-27 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2002-12-27 00:00:00 | TO COMM BOARD #23 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2002-12-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-24 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-12-24 |
Time |
10:15 |
Sent To |
M |
|
| Notes |
| 2002-12-24 00:00:00 | TO MECH INBOX. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2002-12-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-23 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-12-23 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2002-12-23 00:00:00 | TO COMM BOARD, #42 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2002-12-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-16 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-16 |
Time |
17:00 |
Sent To |
B |
|
| Notes |
| 2002-12-16 00:00:00 | TO HAROLD P./WRT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2002-12-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-11 |
Time |
18:44 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-11 |
Time |
18:44 |
Sent To |
B |
|
| Notes |
| 2002-12-11 00:00:00 | TO HAROLD P./WRT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2002-11-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-25 |
Time |
17:58 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-25 |
Time |
17:57 |
Sent To |
B |
|
| Notes |
| 2002-11-25 00:00:00 | TO HAROLD P./WRT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2002-11-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-20 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-19 |
Time |
10:17 |
Sent To |
B |
|
| Notes |
| 2002-11-20 00:00:00 | TO HAROLD P./WRT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2002-11-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-19 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-19 |
Time |
17:15 |
Sent To |
B |
|
| Notes |
| 2002-10-31 00:00:00 | TO CONN BOARD #48./WRT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-10-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-30 |
Time |
07:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-10-29 |
Time |
07:38 |
Sent To |
M |
|
| Notes |
| 2002-10-30 00:00:00 | SUBMITTALS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
30 |
Status |
P |
Date |
2003-04-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-04-30 |
Time |
14:56 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2003-04-30 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2003-04-30 00:00:00 | SUBMITTAL FOR PLENUM RATED WRAP FOR | | | ELEC "SMURF" IN PLENUM |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
29 |
Status |
P |
Date |
2003-04-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-04-30 |
Time |
10:09 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2003-04-30 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2003-04-30 00:00:00 | REVISION/AS BUILT EMERGENCY GENERATOR | | | EXHAUST & FIRE PUMP EXHAUST |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
28 |
Status |
P |
Date |
2003-04-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-04-23 |
Time |
15:36 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2003-04-23 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2003-04-23 00:00:00 | PROVISO: | | | | | | DUCTS PENETRATING FIRE RATED WALLS OR | | | PARTITIONS ARE REQUIRED TO HAVE FIRE | | | DAMPERS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
27 |
Status |
N |
Date |
2003-04-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-04-09 |
Time |
15:43 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-04-09 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2003-04-09 00:00:00 | PROVIDE THE FOLLOWING INFORMATION: | | | | | | 1.WHAT IS BEING STORED IN THE "POOL | | | STORAGE" & "POOL EQUIPMENT" ROOMS. | | | | | | 2.CLARIFY WERE THE EXHAUST LOUVER | | | WILL BE DISCHARGING THE AIR FROM THESE | | | ROOMS (IN THE GARAGE, WALKWAY OR TO THE | | | OUTSIDE). | | | | | | 3.DOES THIS ROOM HAVE A FIRE RATING? | | | | | | 4.SUBMITTAL FOR SUPPLY FAN SF-3 (ROOM | | | #?) - WHAT IS THIS ROOM TO BE USED FOR? | | | IS THIS ROOM FIRE RATED? PLEASE NOTE | | | FIRE DAMPER IS INDICATED ON DUCT RUNNING | | | THROUGH THIS SPACE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
26 |
Status |
P |
Date |
2003-04-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-04-03 |
Time |
14:52 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-04-03 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2003-04-03 00:00:00 | REVISION-RELIEF DAMPER FOR STAIRWELL | | | PRESSURIZATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
25 |
Status |
F |
Date |
2003-03-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-03-19 |
Time |
07:22 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2003-03-19 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2003-03-19 00:00:00 | DENIED:MECHANICAL PERMIT 01050618 | | | | | | PLEASE CLARIFY HOW THIS DESIGN WILL | | | WORK SHOULD THE OWNER CLOSE-IN THE | | | BALCONY OR COVER THE LOUVER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
24 |
Status |
F |
Date |
2003-03-31 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-02-26 |
Time |
10:18 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2003-02-26 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2003-02-26 00:00:00 | AS PER CONVERSATION WITH JERRY INGRAM, | | | WADSWORTH ENG.CEILING CHANGES TO LOBBY | | | AREA DICTATED DIFFUSER LOCATION CHANGES. | | | ALL AREAS. (PLAN SHEET M2.0.0 & M2.0.1 | | | | | | 1.REVISIONS ARE NOT CLOUDED.NOTE ON | | | DENIED:PLAN SHEET M2.0.0 & M2.0.1 | | | | | | PLAN DOES NOT INDICATE THE SPECIFIC | | | REVISION MADE.NOTE ON PLAN INDICATES | | | REVISION #22 BUT FAILS TO CLOUD THE | | | ACTUAL CHANGE. | | | | | | REVISION FOR PLAN SHEET M3.1.3, M4.3.1, | | | & M4.4.1 ARE APPROVED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
23 |
Status |
P |
Date |
2003-01-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-01-27 |
Time |
09:03 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-01-27 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2003-01-27 00:00:00 | MECHANICAL PERMIT 01050618 | | | REVISIONS FOR UNITS #804 904 & 1103. | | | RETURN AIR REVISIONS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
22 |
Status |
P |
Date |
2003-01-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-01-07 |
Time |
15:26 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2003-01-07 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2003-01-07 00:00:00 | MECHANICAL PERMIT 01050618 | | | UNIT #601 | | | PLEASE NOTE PLAN SHEET P3 (P.0.0.5) GAS | | | FOR RANGE, TWO-SIDED FIRE PLACE & DRYER, | | | PROVIDE CALCULATIONINDICATING IF | | | LAUNDRY ROOM IS CLASSIFIED AS A CONFINED | | | OR UNCONFINED SPACE.(COMBUSTION AIR). | | | PROVIDE MANUFACTURER SUBMITTAL DATA | | | ON THE TWO-SIDED FIRE PLACE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
21 |
Status |
P |
Date |
2002-12-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-24 |
Time |
10:18 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-12-19 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2002-12-19 00:00:00 | MECH PERMIT 01050618 | | | MECH REV PLAN SHEET M3.1.1, DUCTWORK IN | | | GRAND SALON, DINING RM, LIBRARY, BAR & | | | FOYER. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
20 |
Status |
P |
Date |
2002-12-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-12-06 |
Time |
12:16 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2002-12-06 |
Time |
12:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
19 |
Status |
F |
Date |
2002-10-31 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-31 |
Time |
09:30 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-10-31 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2002-10-31 00:00:00 | DENIED: | | | | | | UNIT 702 "B" MODEL - REVISIONS ARE NOT | | | IDENTIFIED BY CLOUDS OR TRIANGLES OR | | | NUMBERED AS TO THE LATEST REVION.THE | | | PLAN SHEET SUBMITTED IS IDENTIFIED AS | | | M1, THIS IS NOT PROPER PLAN SHEET | | | IDENTIFICATION NUMBER FOR THIS UNIT. | | | PLEASE CORRELATE REVISION SHEETS TO THE | | | ORIGINAL APPROVED SET OF PLANS TO HELP | | | EXPEDITE THE PLAN REVIEW PROCESS. | | | | | | THE ABOVE COMMENTS ALSO PERTAIN TO UNITS | | | 703, 704 & 904. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
18 |
Status |
F |
Date |
2002-08-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-30 |
Time |
07:38 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2002-08-29 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2002-08-29 00:00:00 | REVISION DENIED | | | SHOP DRAWING UNACCEPTABLE FOR REVSION | | | PROVIDE SIGNED AND SEALED DRAWINGS | | | CLEARLY INDICATING CHANGES TO RETURN | | | AIR OPENINGS, INCLUDING SIZES OF | | | OPENINGS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
17 |
Status |
F |
Date |
2002-08-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-08-22 |
Time |
15:21 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2002-08-22 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2002-08-22 00:00:00 | PLEASE INDICATE ALL REVISIONS BY CLOUDS | | | & TRIANGLES.INDENTIFY REVISION NUMBER | | | & DATE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
16 |
Status |
F |
Date |
2002-08-20 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-08-20 |
Time |
14:00 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2002-08-20 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2002-08-20 00:00:00 | NEEDS TO BE RAISED SEAL AND SIGNED BY | | | THE DESIGNER OF RECORD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
15 |
Status |
N |
Date |
2002-08-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-08-01 |
Time |
09:13 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2002-08-01 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2002-08-01 00:00:00 | PLEASE IDENTIFY CHANGES ON PLAN. | | | (REVISION TO APT 301) |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
14 |
Status |
P |
Date |
2002-06-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-10 |
Time |
12:52 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-06-10 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2002-06-10 00:00:00 | REVISION #12 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
13 |
Status |
P |
Date |
2002-06-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-10 |
Time |
11:05 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-06-10 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2002-06-10 00:00:00 | REVISION #9 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
12 |
Status |
P |
Date |
2002-05-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-20 |
Time |
10:02 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-05-20 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2002-05-20 00:00:00 | MECHANICAL PERMIT 01050618 | | | | | | REVISION PAGES M.1.1.1 & M.1.1.2. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
11 |
Status |
P |
Date |
2002-05-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-14 |
Time |
15:19 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2002-05-14 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2002-05-14 00:00:00 | PROVISO: | | | | | | PVC OR CPVC CANNOT BE USED IN THE RETURN | | | AIR PLENUM AS PER 1997 SMC 609.1.1. | | | | | | CPVC IS NOT APPROVED FOR CONDENSATE AS | | | PER 1997 SMC 304.8.4 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
10 |
Status |
P |
Date |
2002-05-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-02 |
Time |
14:11 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-05-02 |
Time |
09:37 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
9 |
Status |
P |
Date |
2001-11-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-08 |
Time |
12:41 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-11-08 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2001-11-08 00:00:00 | INSTALLED HP-01-L TO TELE/ELEC RM # GA05 | | | CONTROLLED BY A HUMIDISTAT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
P |
Date |
2001-11-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-01 |
Time |
16:00 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-11-01 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2001-11-01 00:00:00 | *******************PROVISO************** | | | | | | | | | REFERENCE LETTER DATED 10-10-01 2B. | | | STAIR PRESSURIZATION SYSTEMS TEST | | | CRITERIA, TEST TO BE WITNESSED BY (IN | | | ADDITION TO ENGINEER) MECHANICAL AND | | | FIRE DEPT. INSPECTOR AND A CERTIFIED | | | TEST AND BALANCE COMPANY. | | | | | | TEST CRITERIA FOR SMOKE EVAC SYSTEM HAS | | | NOT BEEN SUBMITTED FOR REVIEW.PLEASE | | | SUBMIT PRIOR TO FINAL INSPECTION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2001-09-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-21 |
Time |
10:42 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-09-21 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2001-09-21 00:00:00 | ******************PROVISO*************** | | | | | | | | | 1.SUBMITTAL OF VENTILATION OF PRIVATE | | | PARKING GARAGE SPACES DOES NOT ADDRESS | | | AN EMERGENCY POWER SEQUENCE.PLEASE | | | PROVIDE APPROPRIATE PLANS TO COMPLY | | | WITH ELECTRICAL, FIRE AND MECHCANICAL | | | FOR EMERGENCY POWER SITUATION. (SUBMIT | | | PRIOR TO ROUGH INSPECTION OF GARAGE.) | | | | | | | | | 2.SEQUENCE OF OPERATION & TEST CRITERIA | | | AS NOT BEEN SUBMITTED FOR REVIEW. | | | (SUBMIT PRIOR FINAL INSPECTIONS.) | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2001-08-31 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-08-31 |
Time |
13:32 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2001-08-31 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2001-08-31 00:00:00 | REVISION # 3 SHOWS 10 FOOT SEPARATION | | | FROM STAIR PRESSURIZATION FAN AND | | | EXHAUST FANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2001-08-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-10 |
Time |
16:41 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-08-10 |
Time |
16:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-08-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-10 |
Time |
16:03 |
Rev Time |
4.00 |
| Received By |
pkrauss |
Date |
2001-08-10 |
Time |
07:05 |
Sent To |
|
|
| Notes |
| 2001-08-10 00:00:00 | ******************PROVISO*************** | | | | | | | | | 1.PLEASE ADD NOTE TO HEAT PUMP | | | SCHEDULE THAT HEAT PUMPS IN "PRIVATE | | | GARAGE"SHALL BE CONTROLLED BY | | | A HUMIDISTAT NOT A THERMOSTAT. | | | | | | 2.ALL CALCULATIONS SUBMITTED BY | | | WADSWORTH ENGINEERING MUST BE | | | SEALED, SIGNED AND DATED. | | | | | | 3.PLEASE SUBMIT TEST CRITERIA FOR | | | STAIRWELL PRESSURIZATION. | | | | | | 4.PLEASE PROVIDE DETIAL SHOWING | | | COMPLIANCE WITH 1997 SMC 405, AIR | | | INTAKE SHALL NOT BE LOCATED CLOSER | | | THAN 10' FROM ANY SANITARY VENT | | | UNLESS SUCH OUTLET IS 24" ABOVE AIR | | | INTAKE.SHOULD EXHAUST AND SUPPLY | | | NOT HAVE THIS DISTANCE SEF-7 SHALL | | | INTERLOCK TO SHUTDOWN UPON | | | ACTIVATION OF SSF-1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2001-07-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-02 |
Time |
13:01 |
Rev Time |
4.30 |
| Received By |
pkrauss |
Date |
2001-07-02 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2001-07-02 00:00:00 | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | | | | PLEASE PROVIDE SEQUENCE OF OPERATION AS | | | WELL AS TEST CRITERIA FOR SMOKE EVAQ. | | | | | | ENG COMMENTS 6 & 7 POOL HEATERS & FLUE | | | VENTS HAVE BEEN ADDED ON DWG M.1.1.1, | | | NO SUCH DWG. | | | | | | MISSING DWGS M.0.0.3, 0.0.4, M.1.1.1, M. | | | 1.1.4, M.2.0.1, M.2.1.1, M.2.1.2, M.4.1. | | | 2, M.4.2.1, M.4.3.1. | | | | | | PLEASE PROVIDE MANUFACTURER DATA FOR | | | THE GENERATOR. | | | | | | NO DETAILS/PLANS FOR COMMON AREAS SUCH A | | | AS SPA, LOBBY, MANAGERS OFFICE, BILLIARD | | | RM, BOARD RM AND FITNESS RM. | | | | | | PLEASE PROVIDE A DETAIL FOR SYMBOLS USED | | | ON MECHANICAL PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-05-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-18 |
Time |
13:11 |
Rev Time |
5.30 |
| Received By |
pkrauss |
Date |
2001-05-18 |
Time |
08:41 |
Sent To |
|
|
| Notes |
| 2001-05-18 00:00:00 | *******************DENIED*************** | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS | | | COMMON/ASSEMBLY AREAS IN BUILDING. | | | (AS PER ASHRAE 62-89) | | | | | | 2.PROVIDE AIR BALANCE SCHEDULE AS PER | | | 1997 SMC 501.2. | | | | | | 3.PLEASE SHOW COMPLIANCE WITH FLORIDA | | | ENERGY CODE FOR BUILDING CON- | | | STRUCTION SECTION 101.5.8, #1 - FOR | | | CONDITIONED PARKING GARAGES. | | | | | | 4.DRYER SHAFTS HAVE LIMITED CLEAN | | | OUTS, HOW IS COMBUSTIBLE LINT | | | REMOVED FROM DRYER SHAFTS. | | | | | | 5.THE GAS METER PROVIDED FOR PLAN | | | REVIEW, HAS NO UL OR FM APPROVAL | | | ON MANUFACTURE SUBMITTAL DATA. | | | | | | 5.NO CUT SHEETS PROVIDED FOR GAS | | | FIREPLACES OR THE APPARTMENT | | | KITCHEN HOODS.PROVIDE INFORMATION | | | ON FLUE PIPE (CONSTRUCTION, SIZE | | | AND TERMINATION). | | | | | | 6.PLEASE EXPLAIN DISCREPANCY BETWEEN | | | AIRWAY ROOM PLANS.AIRWAY ON | | | "A" DRAWINGS INDICATES A DOOR AND | | | "M" DRAWINGS NO DOOR IS DEPICTED. | | | | | | 7.PROVIDE STAIRWELL PRESSURIZATION | | | CALCULATIONS. | | | | | | 8.PLEASE PROVIDE INFORMATION ON THE | | | "FAN ROOMS"ON THE ROOF. | | | | | | 9.PROVIDE INFORMATION ON "SHAFT | | | GRILLE ABOVE" LOCATED IN THE | | | GARAGE. | | | | | | 10.PLEASE PROVIDE CALCULATIONS FOR | | | VENTILATION IN PARKING GARAGE, SHOW | | | COMPLIANCE WITH 1997 SBC 411.4.2. | | | | | | | | | NOTE:NO COMBUSTIBLES ABOVE CEILING IF | | | USED AS RETURN AIR PLENUM. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-03-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-30 |
Time |
15:33 |
Rev Time |
6.00 |
| Received By |
pkrauss |
Date |
2001-03-30 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2001-03-30 00:00:00 | *****************DENIED***************** | | | | | | 1.PLEASE PROVIDE INFORMATION ON | | | VENTILATION FOR GARAGE AREA AS PER | | | 1997 SBC 411.4.2. | | | | | | 2.PLEASE PROVIDE DETAILS ON SHAFTS: | | | WHERE THEY TERMINATE ON ROOF, | | | DETAILS OF PENETRATION AND CURB. | | | DETAILS AND LOCATIONS OF ACCESS | | | DOORS IN SHAFT. | | | | | | 3.PLEASE PROVIDE DETAILS FOR GAS | | | FIREPLACE, GAS LINE AND FLUE. | | | | | | 4.PLEASE PROVIDE DETAILS FOR DRYER | | | VENTS. | | | | | | 5.PROVIDE MANUFACTURE DETAILS OF | | | KITCHEN HOOD. | | | | | | 6.NO COMBUSTIBLES ABOVE CEILING IN | | | RETURN AIR PLENUM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
26 |
Status |
P |
Date |
2003-05-12 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2003-05-12 |
Time |
08:37 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-05-12 00:00:00 | REVISION, PORTE COCHERE O/F SCUPPERS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
25 |
Status |
P |
Date |
2003-05-12 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2003-05-12 |
Time |
08:04 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-05-12 00:00:00 | REVISION, FOUNTAIN EQUIPMENT RM RELIEF | | | VENT.PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
24 |
Status |
P |
Date |
2003-04-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-26 |
Time |
13:06 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-04-26 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2003-04-26 00:00:00 | REVISION OK - LOCATION OF NEW SCUPPERS | | | ONLY - NO REFERENCE TO CODE COMPLIANCE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
23 |
Status |
F |
Date |
2003-04-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-22 |
Time |
15:08 |
Rev Time |
2.00 |
| Received By |
kstevens |
Date |
2003-04-22 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2003-04-22 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | 1) RELIEF VENT REQUIRED PER SEC 905.7.1 | | | (2) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
22 |
Status |
P |
Date |
2003-04-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-14 |
Time |
17:22 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-04-14 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2003-04-14 00:00:00 | REVISION OK - ADD SCUPPER - DELETE ROOF | | | DRAINS FROM ELEVATOR MACH. ROOM, PITCH | | | ROOF AND ADD 2 NEW ROOF DRAINS AND 2 NEW | | | SCUPPERS AT LOW END OF ROOF |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
21 |
Status |
F |
Date |
2003-04-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-08 |
Time |
09:02 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-04-08 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2003-04-08 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 BUILDING | | | | | | 1) REVISION STATES THAT DRAINS & EMER- | | | GENCY OVERFLOW DRAINS ARE VERTICAL, BUT | | | DRAWINGS INDICATE THAT THE DRAINS & OVER | | | FLOWS ARE HORIZONTAL. PLEASE CLAIRFY. | | | INDICATE TYPE OF MATERIAL AND SLOPE OF | | | PIPE. | | | 2) DETAILS SUBMITTED WITH REVISION DO | | | NOT INDICATE HEIGHT ABOVE ROOF TO THE | | | INLET FLOW LINE AS REQUIRED IN SECTION | | | 1503.4.2. ALSO SHOW DETAIL FOR ROOF | | | DRAIN INSTALLED SHOWING ALL REQUIRED | | | MEASUREMENTS. | | | 3) ALL DETAILS SHALL BE SIGNED & SEALED | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
20 |
Status |
F |
Date |
2003-04-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-04 |
Time |
18:02 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-04-04 |
Time |
18:02 |
Sent To |
|
|
| Notes |
| 2003-04-04 00:00:00 | DENIED | | | REFERENCE: SPC-94-SBC-97 | | | | | | 1) FROM PREVIOUS REVIEW, SUBMIT A DETAIL | | | TO SHOW COMPLIANCE WITH 1517.6.4.3. THE | | | DETAILS SUBMITTED ARE NOT SIGNED AND | | | SEALED AND SHOW NO DIMENTIONS. HOW IS | | | THE PIPE SEALED WHERE IT PASSES THRU THE | | | VERTICAL WALL? | | | 2) PLEASE NOTE YOUR REPLY 2(A) INDICATES | | | A VERTICAL OVERFLOW, NOT A SCUPPER, BUT | | | 2(C) INDICATES 1/8" PER FOOT SLOPE. ALSO | | | THE DIFINITION OF A SCUPPER ID AN OPEN- | | | ING IN A WALL OR PARAPET THAT ALLOWS | | | WATER TO DRAIN FROM A ROOF WHICH IS WHAT | | | THE REVISION INDICATES. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
19 |
Status |
P |
Date |
2003-04-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-04 |
Time |
17:59 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-04-04 |
Time |
17:37 |
Sent To |
|
|
| Notes |
| 2003-04-04 00:00:00 | REVISION OK - REVISE FLOOR DRAIN & PIP- | | | ING FOR MECH ROOM. SHT P306 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
18 |
Status |
F |
Date |
2003-04-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-03 |
Time |
11:34 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2003-04-03 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2003-04-03 00:00:00 | REVISION - DENIED | | | | | | PLEASE PROVIDE DETAIL TO SHOW COMPLIANCE | | | WITH SECTION 1517.6.4.3 ALSO SHOW TYPE | | | OF MATERIAL, SLOPE OF PIPE AND INDICATE | | | AREA OF ROOF TO BE DRAINED BY SCUPPER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
17 |
Status |
P |
Date |
2003-03-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-25 |
Time |
10:23 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-03-25 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2003-03-25 00:00:00 | SUBMITTAL OK - GAS FIREPLACE FOR UNIT | | | #601 - NEED REVISION RESUBMITTED UNDER | | | GAS PERMIT NUMBER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
16 |
Status |
P |
Date |
2003-03-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-06 |
Time |
10:11 |
Rev Time |
1.33 |
| Received By |
kstevens |
Date |
2003-03-06 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2003-03-06 00:00:00 | REVISION OK - SHEETS P.2.0.2 & P.2.0.5 | | | TO COMMON AREA LOBBY FLOOR |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
15 |
Status |
P |
Date |
2003-03-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-06 |
Time |
07:33 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-03-06 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2003-03-06 00:00:00 | REVISION OK - BUTLER PANTRY CHANGES - | | | DELETE BAR SINK - MOVE SANT. RISER - | | | SHEETS P.9.0.1 - P.9.0.2 - P.9.0.3 AND | | | P.9.0.4 UNITS "G" |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
14 |
Status |
P |
Date |
2003-03-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-06 |
Time |
07:36 |
Rev Time |
0.60 |
| Received By |
kstevens |
Date |
2003-03-05 |
Time |
17:56 |
Sent To |
|
|
| Notes |
| 2003-03-06 00:00:00 | REVISION OK - CHANGE BATHROOM LAYOUTS - | | | ADD/DELETE BAR SINKS - SHEETS P.8.0.2 & | | | P.8.0.4 - 15TH FLOOR PENTHOUSE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
13 |
Status |
P |
Date |
2003-03-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-05 |
Time |
17:47 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-03-05 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2003-03-05 00:00:00 | REVISION OK - UNIT 1204 - SHTS P.6.0.3 | | | & P.6.0.5 - DELETE SINK AND ALL PIPING |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
12 |
Status |
P |
Date |
2003-01-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-22 |
Time |
09:48 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-01-22 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2003-01-22 00:00:00 | SUBMITTAL OK - TYPICAL FLOOR PLAN FOR | | | WATER SUPPLY - CPVC PIPE & FITTINGS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
11 |
Status |
P |
Date |
2003-01-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-11 |
Time |
14:12 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2003-01-11 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2003-01-11 00:00:00 | REVISION OK - SECONDARY DRAINS ON MECH. | | | ROOFS - SCUPPERS ON BALCONYS - REMOVE | | | DRAINS FROM ONE BALCONY |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
10 |
Status |
P |
Date |
2002-12-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-20 |
Time |
15:46 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2002-12-20 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2002-12-20 00:00:00 | REVISION OK ADD ROOF DRAIN FOR ROOF | | | EQUIPMENT ROOM. ADDED PIPING. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
P |
Date |
2002-12-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-20 |
Time |
13:41 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2002-12-20 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2002-12-20 00:00:00 | REVISIONS OK - SANT. AND WATER FOR UNITS | | | SHTS P6.0.2 & P6.0.5 | | | 603, 604, 804, 1003, & 1004 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2002-12-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-20 |
Time |
10:57 |
Rev Time |
2.50 |
| Received By |
kstevens |
Date |
2002-12-20 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2002-06-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-06-27 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-27 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2002-06-27 00:00:00 | REVISION/DENIED | | | REFERENCE: SPC-94 | | | | | | 1) SHT P.2.0.2 PORTE COCHERE ROOF DRAINS | | | (3) DRAINING INTO 4" HORIZONTAL STORM | | | DRAIN. HORIZONTAL STORM DRAIN NOT SIZED | | | CORRECTLY. | | | 2) SHT P.2.0.5 PLEASE PROVIDE MANUF. | | | INSTALLATION INSTRUCTIONS FOR REMOTE | | | CHILLER (CONDENSER) IN CEILING FOR E.W.C | | | (LETTER FROM WADSWORTH - O'NEAL RECIEVED | | | REQUESTING INFORMATION FROM MANUF.) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2002-06-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-06-08 |
Time |
05:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-08 |
Time |
05:57 |
Sent To |
|
|
| Notes |
| 2002-06-08 00:00:00 | REVISION OK - C/O BASE OF STACK DETAIL | | | SHT P.0.0.1 - (PER SEC 307.2) |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2001-11-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-02 |
Time |
14:14 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-11-10 |
Time |
10:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2001-11-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-10 |
Time |
09:24 |
Rev Time |
3.00 |
| Received By |
kstevens |
Date |
2001-11-10 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2001-11-10 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 - SGC-97 | | | RE: SUBMITTALS | | | | | | 1) SPECIFICATION(S) 15120P.2.05A AIR | | | CHAMBERS NOT APPROVED AS SUBMITTED. | | | SUBMIT INFORMATION ON ACCESS PANELS AND | | | SHOW COMPLIANCE WITH WH-PDI 201, SHOW | | | HOW AIR CHAMBERS WILL BE RECHARGEALBE. | | | SPC SEC 607.8.3 | | | 2) SPECIFICATIONS(S) 15160P, 15160P.2.01 | | | AND 15160P.2.04, SHOW LISTING FOR EACH | | | PUMP SUBMITTED. | | | 3) PLEASE PROVIDE NSF APPROVAL FOR ALL | | | VALVES. | | | 4) EXPANSION TANK MANUFACTURE SHEETS AND | | | APPROVAL REQUIRED. | | | 5) MORE INFORMATION REQUIRED FOR HEAT | | | EXCHANGER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-08-08 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-08-08 |
Time |
08:50 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-08 00:00:00 | PLUMBING PLAN REVIEW, PROVISO. | | | | | | SEPERATE PERMIT REQUIRED FOR GAS. | | | | | | GAS PERMIT APPLICATION REQUIRMENTS | | | PREVIOUS COMMENTS DATED 03-25-01 NOTE #8 | | | SEE ATTACHED PLEASE ADDRESS EACH ITEM. | | | | | | BELOW IS ADDITONAL NOTES | | | (1A) LOCATION OF GAS METER FOR BOILERS. | | | (1B) THE RESIDENTAL GASPIPING SHALL BE | | | DESIGNED PER MANUFACTURE MANUAL, SPECIFY | | | SERIES OR PARALLEL PIPING ARRANGEMENT. | | | (1C) CUT SHEETS FOR ALL COMPONENTS OF | | | THE SYSTEM, WITH PIPE SIZING TABEL. | | | THE ABOVE INFORMATION IS REQUIRED BEFORE | | | A GAS PIPING PERMIT IS ISSUED. | | | STANDARD GAS CODE-97 SEC 104.3 PLANS. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-06-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-06-24 |
Time |
11:53 |
Rev Time |
4.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-24 00:00:00 | REVIEW OF PLUMBING COMMENTS 06-06-01 | | | FROM ARCHITECTURAL GROUP | | | (1A) SEE CIVIL DRAWINGS | | | (1B) DOCKS ARE STILL REFERENCED ON | | | ARCHITCURAL DRAWINGS. | | | (1C) FLORIDA PUBLIC UTILITIES TO FURNISH | | | GAS PIPING PLAN UP TO POINT OF SERVICE. | | | CONTACT MR DAVID PELLICO 561-838-1752 | | | (2A) SHT P.0.0.1 ALL ABBREVATIONS ON | | | PLANS NOT LISTED. | | | (2B) SHT P.0.01 DETAIL, ELEVATOR NOT | | | DELETED. | | | (3) SHT P.1.0.1 CAR WASH INTERCEPTOR | | | DRAIN HAS NOT BEEN CORRECTED, CONNECT TO | | | SANITARY SEWER. | | | (4) SHTS FOR DOMESTIC WATER PLANS HAVE | | | NOT BEEN CORRECTED, A MAXIMUM OF 2 PLBG | | | FIXTURES ON 1/2" C/W AND 4 ON 1/2" H/W. | | | (6) CUT SHT SUBMITTALS TO BE REVIEWED BY | | | ARCHITECT PRIOR TO PLUMBING REVIEW. | | | (7A) SHT P.1.0.2 BUILDING SANITARY DRAIN | | | NOT APPROVED, USE SPC 94 TAB 714.1 SIZE | | | (7B) SHT P.2.0.5 DOMESTIC WATER PLAN, | | | USE TAB 607,MINIMUM SIZE OF PLBG FIXTURE | | | SUPPLY, HOT AND COLD WATER, 1/2". | | | (7C) SHT P.2.0.5 LOBBY WATER FEATURE | | | POOL, WATER SUPPLY, BACK FLOW PREVENTER | | | REQUIRED, SEC 606. | | | (8) SHT P.0.0.1, GAS PIPING BEYOND METER | | | NOT ADDRESSED,SEE GAS PERMIT APPLICATION | | | REQUIRMENTS, ATTACHED. SEC 104.3 | | | (9,10) SHT P.3.0.6 ROOF DRAINS, SCUPPER | | | DRAINS, USE DESIGN CRITERIA,SPC 94 CH 11 | | | TAB 1108.1,1108.2,1108.3 FIG.1108.4, | | | SECONDARY DRAINS 1109 (SCUPPERS) FIG. | | | 1109.3 RAINFALL RATES. | | | APPENDIX "A", TAB A101.2 SIZING TAB. | | | SEC 104.3 ISOMETRIC DRWG, SHOW ALL CALCU | | | LATIONS,VERTIAL WALLS, UPPER ROOFS. | | | (11) FAIR HOUSING ACT REV 98, OPTION "B" | | | USED,SHOW LAYOUT OF GRAB BAR REQUIRMENT | | | FOR ALL FIXTURES AS REQUIRED. | | | ONE OF EACH TYPE OF FIXTURE MUST BE | | | USEABLE IN OPTION 'B",BIDET IS INCLUDED. | | | (12) SOVENT SYSTEM, AS/ YOUR COMMENT. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-03-25 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-03-25 |
Time |
11:45 |
Rev Time |
8.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-25 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | CODE REFERENCE SPC 94,SGC 97. | | | (1A)SHT C-4 ALL SITE WATER,SANITARY | | | SEWER TO COMPLY WITH CITY OF W PALM BCH. | | | UTILITY STDS. | | | (B) DOMESTIC WATER TO DOCK,BACK FLOW | | | PREVENTER REQ. SEC. 606 | | | (C)SHOW LOCATION OF GAS SERVICE & METER. | | | (2A)SHT P001 PROVIDE A COMPLETE LIST OF | | | ALL ABBREVATIONS USED ON PLBG PLANS. | | | (B) ELEVATOR SUMP,SHOW DISCHARGE TERMIN- | | | ATION, IF HYDURALIC,OIL INTERCEPTOR REQ, | | | WITH AN INDIRECT WASTE CONNECTION. | | | (C) PLANS DO NOT INCLUDE SHTS POO2,P103, | | | P203,P204,P404,P504,P604,P703,P803,P903. | | | (3) SHT P101 CAR WASH,SEC 1004.6 SAND | | | INTERCEPTOR REQ. | | | (4) SHT P103 COMPLY WITH SEC 607 WATER | | | SUPPLY SIZING, SHOW CALCULATIONS FOR | | | SIZING THE DEMAND LOAD FOR THE ENTIRE | | | SYSTEM, BASED ON DFU. | | | (5) SEC 104.2.4 STRUCTURAL AND FIRE | | | RESISTANCE INTEGRITY. UL LISTING FOR ALL | | | RATED FLOOR,WALL PENETRATIONS. | | | (6) SEC 104.2 SUBMITALS FOR ALL MATERIAL | | | AND SPECIFICATIONS. | | | (7) SEC 104.2 DRAWINGS:PROVIDE ISOMETRIC | | | DRAWINGS FOR WATER & DRAIN WASTE,VENT | | | SYSTEM, DWV SHOW SIZING CALCULATIONS. | | | (8) SEC 104.2 PROVIDE A GAS ISOMETRIC, | | | SEE ATTACHED REQUIRMENTS FOR GAS PERMIT | | | DRAWINGS & APPLICATION. | | | (9) SHT P306 ROOF & SCUPPER DRAINS SEC. | | | 1109.1 & APPEX "A",SEC 1108.3 VERTIAL | | | WALLS,SHOW AREA DRAINED IN SQUARE FEET | | | PLUS 1/2 THE VERTICAL AREA OF WALLS & | | | PARAPETS,ISOMETRIC DRAWING OF SYSTEM. | | | (10) SEC 1109 SECONDARYROOF DRAINS: | | | PROVIDE CALCULATIONS FOR SIZING,LOCATION | | | OF THE SECONDARY DRAINS. | | | (11) ALL KITCHENS & BATH ROOMS SHALL | | | COMPLY WITH THE U S DEPT OF HOUSING AND | | | URBAN DEVELOPMENT (HUD) FAIR HOUSING ACT | | | REGULATIONS,24 CODE OF FEDERAL REGULAT- | | | IONS (CFR) 100.205 (C) (3) (IV). | | | REQUIRMENT#7 PARAGRAPH 2. DESIGNATE | | | WHICH DESIGN SPECIFICATION IS BEING USED | | | A OR B OF THE FAIR HOUSING ACT. | | | SHOW DETAILS,AS ILLUSTRATED IN THE | | | FAIR HOUSING ACT DESIGN MANUAL. | | | END OF COMMENTS QUESTIONS CONTACT | | | PAUL SCHMITZ 561-659-8096 X 8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2001-08-15 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-08-15 |
Time |
11:37 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2001-06-04 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-06-04 |
Time |
10:38 |
Rev Time |
0.50 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-04 00:00:00 | SITE PLAN MUST BE AAMENDED |
|
|